ge best in class tle ups

Download Report

Transcript ge best in class tle ups

G.E.
UPS Productline
Uninterruptible Power Supplies | 1 Phase
Delivering reliable power in a compact footprint
IT & Match Series
GT Series
Line Interactive topology, automatic
voltage regulation, step-wave output
with internal hot swappable batteries.
Double conversion, parallel-ready
technology with modular battery and power
components for easy expansion and
retrofit.
Application
Telecom equipment, server racks,
small to medium data networks
Application
Point-of-sale (POS), ISDN switches PCs,
routers, & small IT servers
Rating
600 VA – 2 kVA
Output
120 Vac
Cert.
UL
500 VA – 3 kVA
230 Vac
CE
Rating
1 – 2kVA
3kVA
5 - 10kVA
6 & 10kVA
Output
120 Vac
120/208 Vac
120/208/240 Vac
220/230/240 Vac
Cert.
UL
UL
UL
CE
VH Series
LP11 / LP31T / LP31 Series
Double conversion technology,
hardened design, peak load handling,
and wide temperature operating range.
Double conversion, high efficiency (up to 97%)
and redundant parallel capable, with galvanic
isolation and GE’s battery management for load
security.
Application
Medium data networks, telecom
equipment, local site protection
Application
Healthcare & marine, wind turbine,
controls, all IT & high speed processing
Rating
2 kVA
700 VA-3 kVA
Output
208/220/230/240 Vac
208/220/230/240 Vac
Cert.
UL
CE
Rating
5-10 kVA
Output
120/208/240 Vac
3-10 kVA
5-20 kVA
220/230/240 Vac
220/230/240 Vac
Cert.
UL &
CE
CE
CE
Uninterruptible Power Supplies | 3 Phase
Clean, reliable and energy efficient power
SG Series
LP33 Series
The high efficiency SG series provides
fast step/transient load response while
eliminating single points of failure.
The LP33 series is a transformer-less
design reducing install footprint and
installation time.
Application
Enterprise class data networks,
large data centers, healthcare
equipment
Application
Large data networks, telecom equipment
Rating
10 - 750
kVA
60 - 500
kVA
Output
480 Vac
Cert.
UL
400 Vac
CE
SitePro
The SitePro model is a robust, double
conversion UPS that provides true online operation and galvanic isolation.
Application
Manufacturing & process control
healthcare equipment, data centers
Rating
10 - 40 kVA
Output
380/400/415 Vac
Cert.
CE
Rating
10 - 100
kVA
10 - 120
kVA
Output
208 Vac
Cert.
UL
380/400/415 Vac
CE
Leading the industry through innovation
Redundant Parallel Architecture (RPA)
Increasing reliability by eliminating single points of failure. Paralleling
multiple UPS’ for true redundancy without adding complexity.
ECO Mode
Power supplied from mains via UPS bypass circuit. Immediate transfer to
inverter power during disturbance. Energy efficiency of up to 98.5%.
PurePulse ®
Delivers pure clean waveform from the mains, reducing sizing
of upfront equipment and eliminating additional input filters.
GE
Critical Power
TLE Series Platform
225 – 1500 kW
TLE Series platform
Introducing TLE Series
UPS
What is it?
Differentiated Value Proposition
TLE Series is a new high power transformer less 3 phase
UPS platform with best in class multi-mode efficiency (eBoost
and double conversion), and modular scalable from 200 kW
up to 1500 kW for global UPS markets (CE and UL).
•
Why is it important?
This TLE platform establishes GE technology leadership in
mid/high power UPS applications with industry leading
differentiation in efficiency, output power capacity and
footprint.
•
•
•
•
Best in class multi-mode efficiency
•
96.5% Double Conversion mode (VFI)
•
99.0% eBoost mode (VFD)
Highest output power (up to 1.5 MW)
High reliability:
•
Improved serviceability and lower MTTR
•
Standard building blocks 250 kw
•
Inherent redundancy inside UPS module
High power density and small foot print
Excellent input , output performance
Page 5
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Creating Value – Low TCO
Ultra High
Efficiency
Improved
Serviceability
Excellent
Performance
High output
power
Improved
Diagnostic
High Reliability
Page 6
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Creating Value – Low TCO
Ultra high
Efficiency
Page 7
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
High Efficiency at all loads
Reduced customer operation costs and cost saving in air conditioning
design
Double conversion Efficiency – 96.5%
High efficiency performances
High efficiency at full and partial loads for
real benefit in operating conditions
Energy cost saving
Reduced cost of customer equipment
operation at all loads
Air conditioning cost saving
Reducing size and cost of air condition
system
Reducing consumption and related
operating cost
GE Sets the Bar for highest UPS Operating
Efficiency
Page 8
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
High Efficiency – eBoost mode
eBoost high efficiency (up to 99%)
fast transfer to inverter <2ms
"GE's eBoost feature expands a classic mode On-Line Double Conversion
UPS System to a multi-mode UPS capable of maximizing operating
efficiency commensurate with the stability of utility voltage and frequency
eBoost can be operated in RPA mode, up to 6 UPS modules in parallel,
with all units operating and switching as one through redundant
communication bus
Page 9
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
High Efficiency – Low TCO
High efficiency up to 96.5%
Considerable life cycle cost savings
Reduction in UPS operating cost
Reduction in cooling cost
Assumptions:
Power cost = $ 0.10 /kw-hr
Operating hours/year = 8760
Cooling factor = 0.35
Configuration = S+S operating at 50% load
93%
96.5%
99%
5 MW IT load - TLE series life cycle savings of $1.5 MM while operating in VFI
Page 10
mode
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
High Efficiency – Low TCO
High efficiency up to 96.5%
Considerable life cycle cost savings
Reduction in UPS operating cost
Reduction in cooling cost
Assumptions:
Power cost = $ 0.10 /kw-hr
Operating hours/year = 8760
Cooling factor = 0.35
Configuration = 500 kW UPS @ 50%
load
TLE Series UPS annual savings
Compared to
92% efficiency UPS > $ 14,980
94% efficiency UPS > $ 8,140
95% efficiency UPS > $ 4,830
Page 11
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Creating Value – Low TCO
Excellent
Performance
Page 12
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Best in class input performance
UPS input performances
 Total Current Harmonic Distortion – THDi <5%
 UPS input power factor: 0.99
Constant behavior at all loads
 Negligible harmonics contents at full and
partial loads
Programmable Soft Start Feature
Benefit on input mains
 Saving in the sizing of upfront equipment
e.g. GenSet, cablings, circuit breakers, …
 No disturbances to nearby equipment
 Saving cost due to additional filters
Page 13
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Input performances benefit
High input performance means saving:
 GenSet size ( From 2 X Load kVA to 1.3 X Load kVA)
- Stable & longer life due to absence of harmonics
 Circuit breaker size
 Cabling section/size
 Investment & space
 Improved life for nearby equipments
 No reactive power – saves on power compensation
Page 14
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
UPS output power capability
Power capability – Unity power factor (kVA = kW)
 Designed to supply real power for Unity power
factor data centers load
 Suitable for modern power supply application
with unit or capacitive power factor (e.g. new
servers generation), crest factor up to 3:1
No output voltage distortion with linear and nonlinear loads

Voltage distortion
- linear loads:
THDv < 2-3%
- non-linear loads:
THDv <
5%
11% more kW power compared to UPS with
PF=0.9
Page 15
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
UPS Input-Output Performance
Module size optimization/ Electrical infrastructure
utilization
4000 A Input Bus
3000 A Input Bus
2000 A Input Bus
6 x TLE 500 kW
4 x TLE 750 kW
3 x TLE 1000 kW
2 x 1500 KW
4 x TLE 500 kW
3 x TLE 750 kW
2 X 1000 kW
3 x TLE 500 kW
2 x TLE 750 kW
1 x 1500 kW
3 MW Power
2.25 / 2 MW Power
1.5MW Power
11% more kW power compared to UPS with
PF=0.9
Competitors units with 0.9 power factor provides
less output power from same input bus size
Page 16
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Creating Value – Low TCO
Improved
Diagnostic High
Reliability
Page 17
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
New FLEX DSP board: the black-box
•
•
•
•
Waveform capture, diagnostic and trend analysis
Simultaneous acquisition of 32 channels
Sampling frequency up to 10kHz
Smart trigger capability with up to 16 indipendent trigger sources to
record only specific events with pre/post trigger data acquisition
• Buffer depth of 1000 samples per channel: each event is recorded
for 100ms @ s.f. 10kHz
• 8 buffers to record up to 8 events without losing older events – can
be extended with external USB mass storage devices
WAVEFORMS
•
Inverter voltages
•
Bypass voltages
•
Input mains voltages
•
Output voltages:
•
Output current Phases:
•
Input capacitors “Cin” voltages:
•
Inverter primary current:
•
Input current:
•
IDC current:
•
Battery current:
•
Bypass current:
•
UDC
•
Communication status RPA
•
Auxiliary status
•
SSM status
•
Fuses status
•
Phase error slave master.
Page 18
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Creating Value – Low TCO
Ease of Installation
Improved
Serviceability
Page 19
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Compact design
TLE Series 250 kW
Reduced footprint
 Compact design saving space in installation
- 225-250 kW: (w x d x h)
44.4 x 33.9 x 75.1 inch
-400-500 kW:
66.9 x 33.9 x 75.1 inch
Standard Top-bottom cable entry
Easier to handle
High power density
Savings in installation space
1907 / 75.1”




1100 / 43.3”
Page 20
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Improved serviceability
Improving Mean Time to Repair & Installation
 Front access construction/design
 Draw out construction for fans & power modules
 Common 250 kW power block & common
components
 Faster power block MTTR
 Easy access to customer connections
 Easy access to connectivity
Improved diagnostic capability
iUPS Guard – Remote monitoring
Standard back feed protection
Internal Option - Q2 (TLE 250-500)
External Option – Q2 (TLE 750 -1500)
Page 21
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Installation flexibility – RPA Cable Saver
Bypass input to UPS
1A
2A
1B
3A
2B
3B
Competitors – 1A=2A=3A and 1B=2B=3B or max 10%
difference
TLE Series with inductor = allows variation up to 20-25%
(depends on UPS rating & cable section
Output from UPS
Page 22
GE– Internal & Confidential
TLE Series 160-400 kVA/kW CE
Advanced User Interface
Menu driven touch screen 7” display





Critical measurement of input, output and battery included with mimic diagram
Quick operational status
Different access level for user and service
Different mimic diagram based on configuration
Multilanguage communication interface
Metering
Alarm
Set up
Command
RPA System
Page 23
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Advanced User Interface
Menu driven touch screen display
Page 24
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Advanced User Interface
Menu driven touch screen display





Separate screen for RPA system with status and measurements
Metering screen by tabs
Home button inside each screen
Improved alarm and events screen
Easy to use set up screen
Page 25
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Creating Value – Low TCO
Summary
Page 26
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Differentiated TLE Series UPS
Efficiency
96.5%
Font access
New control panel
Draw out construction
THDi 3-5%,
Input pf 0.99
Output pf -1
Black Box
Limited life
component monitoring
Small foot print
Product options
High Reliability
Page 27
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
TLE Series UPS
Differentiating:
•
•
•
•
•
•
•
Best in class double conversion efficiency - up to 96.5%
Ultra high efficiency in eBoost mode of operation - up to 99%
Static bypass inductor
Compact foot print provides very high power density
Excellent input, output performance
Improved diagnostic capability with black box
Ease of installation and Improved serviceability
Page 28
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
High Efficiency at all loads
Reduced customer operation costs and cost saving in air conditioning
design
3-Level topology
High efficiency performances
The TLE Series UPS uses a three level technology with an Advanced Neutral Point Clamped
topology implemented with true Reverse Blocking IGBT. These result in reduced switching and filter
losses with respect to a standard two level technology
Page 29
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Improved diagnostic, High Reliability
Improving Reliability & Diagnostic
 AC Capacitor health monitoring
 Component life time counters
 Dedicated supply path for bypass logic
 Redundant Isolated power supply
 Robust RPA communication
 No total OFF button to avoid human error
 Heat sink & input, output filter coils temperature monitoring
Improving Mean Time to Repair
 Wave form capture capability
 Fan failure detection
Page 30
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
UPS configuration
Optional – TLE Series 225-500 kW
TLE Series 225-500 kW
• Double conversion (VFI) technology
• Automatic bypass for overloads, short circuit and UPS disturbances conditions
• Manual bypass Q2 (optional) for UPS maintenance operations without load
interruption (225-500 kW internal option)
• Standard common mains
• Number of battery blocks – 40-42
- back feed protection K6 standard
Page 31
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Installation flexibility - Product options
Supplemental Cabinetry
• VRLA Battery Cabinet Systems
• Flywheel DC Energy Storage
• 480/480V External Maintenance Bypass
• 480/208V External Maintenance Bypass (250kw max)
Optional Equipment
• 480/415VAC Input Isolation Xfmr
• 600VAC Input Isolation Xfmr
• Remote Alarm Status Panel
• Dual Input
• RPA Card for parallel operation
• eBoost Software for multi-mode operation
ISM (intelligent Synchronization module) – not
supported
Page 32
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Remote monitoring – TLE Series
iUPSGuard – Remote monitoring
 Improved response time
 24 x7 monitoring & alarm notification
of UPS
 Improved pre dispatch diagnostic &
first time fix
 Regular status reports
 Highly secure communication
Page 33
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Customer Connectivity
Easy integration with Building Management System (BMS)
UPS supervision capability
1x RS232 Serial Communication Port
6 programmable potential free alarm
contacts:
- D plug
- Terminals blocks
1x Emergency Power OFF contact
1x Gen-ON Input contact
1x Control Input contact
Additional interface:
SNMP Interface Card
(10/100Mbps auto-select)
MODBUS Interface (RS232 or RS485)
iUPSGuard (free license during warranty)
- SNMP card required for iUPSGuard
Customer interface
Page 34
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Redundant Parallel Architecture
System reliability improved by RPA
Configurable up to 6 units in parallel
Future expansion
Safe and reliable power supply
Redundant Communication Bus
Easy to install and maintain
Easy system upgrade/downgrade
Maintenance operation without
load interruption
RPA cable saver allows installation
flexibility
Page 35
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL
Page 36
GE– Internal & Confidential
TLE Series 250-500 kVA/kW UL