"An Overview on FACTS and Power Quality Issues:
Technical Challenges, Research Opportunities
and Cost Considerations."
Paulo F. Ribeiro, BSEE, MBA, PHD, PE
CALVIN COLLEGE
Engineering Department
Grand Rapids, MI 49546
http://engr.calvin.edu/PRibeiro_WEBPAGE/
[email protected]
P. Ribeiro
June, 2002
1
FACTS
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
P. Ribeiro
The Concept
History / Background - Origin of FACTS, Opportunities, Trends
System Architectures and Limitations
Power Flow Control on AC Systems
Application Studies and Implementation
Basic Switching Devices
Systems Studies
AC Transmission Fundamentals
Voltage Source vs. Current Source
Voltage Sources
Static Var Compensator (SVC), STATCOM, TCSC, UPFC, SMES
System Studies (by EMTP, ATP, Saber, EDSA, EMTDC)
Systems Integration, Specification, Cost Considerations and Technology Trends
Impact of FACTS in interconnected networks
Market Assessment, Deregulation and Predictions
June, 2002
2
Power Quality
Objectives - Motivation - Background
Limitation of Traditional Tools
Advanced Techniques:
· Wavelet Theory
· Expert Systems
· Fuzzy Logic
· Neural Networks
· Genetic Algorithms
· Combining Techniques
• Power Electronics
P. Ribeiro
Making Waves
To Sag or Not to Sag: This is The ?
Not Really a Harmonic Distortion
Remembering Wave Signatures
Evolutionary Distortions
Power Quality Diagnostic System
Implementing Advanced Power
Concepts
June, 2002
3
The reason, therefore, that some intuitive minds are not mathematical is that they
cannot at all turn their attention to the principles of mathematics. But the reason
that mathematicians are not intuitive is that they do not see what is before them,
and that, accustomed to the exact and plain principles of mathematics, and not
reasoning till they have well inspected and arranged their principles, they are
lost in matters of intuition where the principles do not allow of such
arrangement. They are scarcely seen; they are felt rather than seen; there is the
greatest difficulty in making them felt by those who do not of themselves perceive
them. These principles are so fine and so numerous that a very delicate and very
clear sense is needed to perceive them, and to judge rightly and justly when they
are perceived, without for the most part being able to demonstrate them in order
as in mathematics, because the principles are not known to us in the same way,
and because it would be an endless matter to undertake it. We must see the matter
at once, at one glance, and not by a process of reasoning, at least to a certain
degree.
1660 PENSEES by Blaise Pascal
P. Ribeiro
June, 2002
4
The Concept
P. Ribeiro
X
V
P P P P
X
V
tg
June, 2002
5
The Concept
A transmission system can carry power up to its thermal loading limits. But in practice the
system has the following constraints:
-Transmission stability limits
-Voltage limits
-Loop flows
Transmission stability limits: limits of transmittable power with which a transmission system can
ride through major faults in the system with its power transmission capability intact.
Voltage limits: limits of power transmission where the system voltage can be kept within
permitted deviations from nominal. Voltage is governed by reactive power (Q). Q in its turn
depends of the physical length of the transmission circuit as well as from the flow of active
power. The longer the line and/or the heavier the flow of active power, the stronger will be the
flow of reactive power, as a consequence of which the voltage will drop, until, at some critical
level, the voltage collapses altogether.
Loop flows can be a problem as they are governed by the laws of nature which may not be
coincident with the contracted path. This means that power which is to be sent from point ”A” to
point ”B” in a grid will not necessarily take the shortest, direct route, but will go uncontrolled
P. Ribeiro
June, 2002
and fan out to take unwanted paths available
in the grid.
6
The Concept
FACTS devices
FACTS are designed to remove such constraints and to meet planners´, investors´ and operators´ goals
without their having to undertake major system additions. This offers ways of attaining an increase of
power transmission capacity at optimum conditions, i.e. at maximum availability, minimum
transmission losses, and minimum environmental impact. Plus, of course, at minimum investment cost
and time expenditure.
The term ”FACTS” covers several power electronics based systems used for AC power transmission.
Given the nature of power electronics equipment, FACTS solutions will be particularly justifiable in
applications requiring one or more of the following qualities:
-Rapid dynamic response
-Ability for frequent variations in output
-Smoothly adjustable output.
Important applications in power transmission involving FACTS and Power Quality devices:
SVC (Static Var Compensators), Fixed * as well as Thyristor-Controlled Series Capacitors (TCSC) and
Statcom. Still others are PST (Phase-shifting Transformers), IPC (Interphase Power Controllers), UPFC
(Universal Power Flow Controllers), and DVR (Dynamic Voltage Restorers).
P. Ribeiro
June, 2002
7
History, Concepts, Background, and Issues
Origin of FACTS
-Oil Embargo of 1974 and 1979
-Environmental Movement
-Magnetic Field Concerns
-Permit to build new transmission lines
-HVDC and SVCs
-EPRI FACTS Initiative (1988)
-Increase AC Power Transfer (GE and DOE Papers)
-The Need for Power semiconductors
Why we need transmission interconnection
-Pool power plants and load centers to minimize generation cost
-Important in a deregulated environment
Opportunities for FACTS
Increase power transfer capacity
SVC (Nebraska GE 1974, Minnesota Westinghouse 1975, Brazil Siemens 1985)
TCSC, UPFC AEP 1999
Trends
-Generation is not being built
-Power sales/purchases are being
P. Ribeiro
June, 2002
8
System Architectures and Limitations
System Architecture
Radial, interconnected areas, complex network
Power Flow in an AC System
Power Flow in Parallel and Meshed Paths
Transmission Limitations
Steady-State (angular stability, thermal limits, voltage limits)
Stability Issues (transient, dynamic, voltage and SSR)
System Issues (Post contingency conditions, loop flows, short-circuit levels)
Power Flow and Dynamic Stability Considerations
Controllable Parameters
Basic FACTS Devices - Impact of Energy Storage
P. Ribeiro
June, 2002
9
System Architectures and Limitations
The relative importance of transmission interconnection
Interconnections in a European type system are not very important because the system is built by
providing generation close to the loads and therefore, transmission is mainly for emergency
conditions.
In the US,very large power plants far from the load centers were built to bring "coal or water by
wire". Large plants provided the best solution - economy of scale. Also, seasonal power exchanges
have been used to the economic advantage of the consumers.
Newer generation technologies favor smaller plants which can be located close to the loads and
therefore, reduces the need for transmission. Also, if distributed generation takes off, then generation
will be much closer to the loads which would lessen the need for transmission even further.
However, for major market players, once the plant is built, the transmission system is the only way to
bring power to the consumer that is willing to pay the most for the power. That is, without
transmission, we will not get a well functioning competitive market for power.
P. Ribeiro
June, 2002
10
Power Flow Control on AC Systems
Radial
Parallel
Meshed
Power Flow in Parallel Paths
Power Flow in a Meshed Systems
What limits the loading capability?
Power Flow and Dynamic Considerations
P. Ribeiro
June, 2002
11
Power Flow Control on AC Systems
50% Series Compensation
Relative Importance of Controllable Parameters
Control of X can provide current control
When angle is large X can provide power control
Injecting voltage in series and perpendicular to the current flow, can increase or
decrease
P. Ribeiro
June, 2002
12
FACTS Applications and Implementations
Transmission Transfer Capacity Enhancement
Steady State
Issues
Voltage Limits
Thermal Limits
Angular Stability Limits
Loop Flows
Dynamic
Issues
Traditional Solutions
Breaking
Resistors Load
Shedding
Advanced Solutions
FACTS
Energy Storage
Fixed
Compensation
Line
Reconfiguration
Transmission
Link
Better
Protection
FACTS
Increased
Inertia
P. Ribeiro
Devices
June, 2002
Transient Stability
Damping Power Swings
Post-Contingency Voltage
Control
Voltage Stability
Subsynchronous Res.
Enhanced
Power Transfer
and Stability
SVC
STATCOM
TCSC, SSSC
UPFC
13
FACTS Devices
Shunt Connected
Static VAR Compensator (SVC)
Static Synchronous Compensator (STATCOM)
Static Synchronous Generator - SSG
Battery Energy Storage System (BESS)
Superconducting Magnetic Energy Storage (SMES)
Energy Storage
Combined Series and Series-Shunt Connected
Static Synchronous Series Controllers (SSSC)
Thyristor Controlled Phase-Shifting Transformer or
Phase Angle Regulator (PAR)
Interline Power Flow Controller (IPFC)
Thyristor Controlled Series Capacitor (TCSC)
Unified Power Flow Controller (UPFC)
Relative Importance of Different Types of Controllers
Shunt, Shunt-Serie
P. Ribeiro
June, 2002
Energy Storage
14
Power Electronics - Semiconductor Devices
Diodes
Transistors
IGBT
Thyristors
SCR, GTO, MTO, ETO, GCT, IGCT, MCT
Devices
Diode (pn Junction)
Silicon Controlled Rectifier (SCR)
Gate Turn-Off Thyristor (GTO) GE
MOS Turn-Off Thyristor (MTO) SPCO
Emitter Turn-Off Thyristor (ETO) Virginia Tech
Integrated Gate-Commutated Thyristor (IGCT) Mitsubishi, ABB
MOS-Controlled Thyristor (MCT) Victor Temple
Insulated Gate Bipolar Transistor (IGBT)
P. Ribeiro
June, 2002
15
Power Electronics - Semiconductor Devices
Principal Characteristics
Voltage and Current
Losses and Speed of Switching
Speed of Switching
Switching Losses
Gate-driver power and energy requirements
Parameter Trade-off
Power requirements for the gate
di/dt and dv/dt capability
turn-on and turn-off time
Uniformity
Quality of silicon wafers
IGBT has pushed out the conventional GTO as IGBTs ratings go up.
IGBTs - Low-switching losses, fast switching, current-limiting capability
GTOs - large gate-drive requirements, slow-switching, high-switching losses
IGBTs (higher forward voltage drop)
P. Ribeiro
June, 2002
16
Power Electronics - Semiconductor Devices
Decision-Making Matrix
System
VSI
CSI
Commutation
Approach
Natural
Forced
Switching
Technology
Synchronous
PWM
Transition
Approach
Hard
Soft
Circuit
Topology
Two-Level
Multi-Level
Device
Type
P. Ribeiro
SCR
GTO
June, 2002
IGBT
MCT
MTO
17
Planing Studies
Evaluate the technical and economic benefits of a range of FACTS alternative solutions which may allow
enhancement of power transfer across weak transmission links. Part I of this effort should concentrate on
preliminary feasibility studies to assess the technical merits of alternative solutions to correct real and
reactive power transfer ratings, system voltage profiles, operational effects on the network, equipment
configurations, etc.
A - Load flow studies will be performed to establish steady-state ratings, and identify the appropriate
locations for connection of alternative compensation devices. Load flow studies will be used to address
the following:
•System Criteria (maximum steady-state power transfers, short-term operating limits, etc.)
•Controller Enhancements (controller types, ratings, sensitivities, etc.)
•Controller Losses (based on operating points and duration)
•System Losses (system losses base on controller operating point and duration)
•Overvoltsages ((steady-state and short-term voltage insulation requirements)
•Compare technical and economic benefits of alternatives
•Identify interconnection points
•Identify critical system contingencies
•Establish power transfer capability of the transmission system
•Confirm that reliability criteria can be met
•Identify the cost of capital of equipment and losses
•Identify steady-state and dynamic characteristics of FACTS controllers
Stability Studies
P. Ribeiro
IEEE
June, 2002
18
Identify
Transmission
Systems Provide System
data and
Configuration
System Studies
Outages
and load
transfer
System data
and
configuration
Outages
and load
transfer
System
operat.
limits
Load Flow
(P,Q, V, q)
Generato
r data
Voltage
Reg.
Data
(AVR)
Governor
data
Relay
data
IEEE
P. Ribeiro
Induction
motor
data
Fault
data
Transient
Stability
(P,Q, V, q, time)
Perform Load
Flow
(P,Q, V, q)
System
operat.
limits
Identify and Size
Transfer
Enhancement
Solutions
Devices
Perform
Economic
Analysis
System
changes
Load
Shedding
Dynamic
Stability
(P,Q, V, q, w,
time)
June, 2002
19
AC Transmission Fundamentals
E1 / 1
E2 / 2
P&Q
I
X
E2 . sin()
(E1 - E2 . cos()
P1 = E1 . Ip1
E1
E1 - E2
E2 . cos()
E1 . sin ()
Ip1 = E2 sin() / X
I
E1 . Cos ()
Iq1 = (E1 - E2 . cos() / X
P. Ribeiro
E2
(E2 - E1 . cos()
June, 2002
20
AC Transmission Fundamentals
Active component of the current flow at E1
Ip1 = (E2 . sin ()) / X
Reactive component of the current flow at E1
Iq1 = (E1 - E2 . cos ())/X
Active Power at the E1 end
P1 = E1 (E2 . sin ())/X
Reactive Power at the E1 end
Q1 = E1(E1 - E2 . cos ()) / X
P. Ribeiro
June, 2002
21
AC Transmission Fundamentals (Voltage - Shunt Control)
E1 / 1
E2 / 2
P&Q
I
X
P1 = k1.E1 (E2 . sin (/k2))/X
Q/V
E1
P1 = E1 (E2 . sin ())/X
E1 - E2
I
E2
Regulating end bus voltage mostly change reactive power - Compensating at an intermediate
point between buses can significantly impact power flow
P. Ribeiro
June, 2002
22
AC Transmission Fundamentals (Voltage-Series Injection)
E1 / 1
E2 / 2
P&Q
I
X
Vinj
Injected Voltage
E1
P1 = E1 . E2 . sin () / (X - Vinj / I)
E1 - E2
I
E2
Injecting Voltage in series with the line mostly change real power
P. Ribeiro
June, 2002
23
AC Transmission Fundamentals (Series Compensation)
E1 / 1
E2 / 2
P&Q
I
X
Changes in X will increase or decrease real power flow for a fixed angle or change angle for a fixed power flow.
Alternatively, the reactive power flow will change with the change of X. Adjustments on the bus voltage have
little impact on the real power flow.
Vc
Vx
I
P1 = E1 . E2 . sin () / (X - Xc)
Vs
Real Power Angle Curve
2
Vseff = Vs + Vc
Vr
Xeff = X - Xc
Vx
2
Vc
P1( x delta V1)
Vxo
1
Vs
Vseff
0
0
0
0
0.5
1
1.5
2
delta
2.5
3
Vr
I
3.5
3.14
Phase Angle
P. Ribeiro
June, 2002
24
AC Transmission Fundamentals (Voltage-Series and Shunt Comp.)
E1 / 1
P&Q
E2 / 2
I
X
P
Injected Voltage
E1
E1 - E2
I
E2
Integrated voltage series injection and bus voltage regulation (unified) will
directly increase or decrease real and reactive power flow.
P. Ribeiro
June, 2002
25
AC Transmission Fundamentals (Stability Margin)
Improvement of Transient Stability With FACTS Compensation
Equal Area Criteria
Q/V
with VAR compensation (ideal midpoint)
Amargin
A2
no compensation
A1
A1 = Acceleration Energy
1
2
3
A2 = Deceleration Energy
Therefore, FACTS compensation can increase
1 - prior to fault
crit
power transfer without reducing the stability margin
P. Ribeiro
June, 2002
Phase Angle 2 - fault cleared
3 - equal area
3 >crit - loss of synchronism
26
Voltage Source Vs. Current Source Converters
CSC
Adv/Dis
VSC
Adv/Dis
Device Type
Thyristor
Self-Commutation
Thyristor
Self-Commutation
Device
Characteristic
Symmetry
Symmetrical
Asymmetrical
Short-Circuit
Current
Lower
+
Higher
Rate of Rise of
Fault Current
Limited by DC Reactor
+
Fast Rise (Due to
capacitor discharge)
Losses
Higher
-
Lower
+
AC Capacitors
Required
Not Required
+
DC Capacitors
Not Required
+
Required
Valves dv/dt
Lower
(AC Capacitors)
More Complex
+
Higher
Interface with AC
System
Reactive Power
Generation
Depends on Current
Flowing through
Energy Storage
+
Less Complex
+
Independent of
Energy Storage
+
Performance
Harmonics
P. Ribeiro
AC capacitors may
produce resonances
near the characteristic
harmonics – may cause
overvoltages on valves
and transformer.
-
June, 2002
27
Voltage Source Converters
S hun tC om p en sa toi n
S e r ies C om p en sa toi n
V
S ys etm bu s
V
S ys etm bu s
V
C oup lni g
T ran s of m
r er
C oup lni g
T ran s of m
r er
I
X
I
T ran s of m
r e r el a kage
ni du c at n ce
X
Vo
Vo
DC A
-C
Sw itch ni g
C on ve r te r
DC A
-C
Sw itch ni g
C on ve r te r
Cs
P. Ribeiro
T ran s of m
r e r el a kage
ni du c at n ce
Cs
+
+
V dc
V dc
June, 2002
28
Voltage Source Converters
Basic 6-Pulse, 2-level, Voltage-Source Converter
di c
ea
eb
ec
ai
Ta1
D a1 Tb1
D b1 T c1
bi
D c1
V dc
+
Cs
V dc
ci
2
H y po h
t e tci a l
neu tra lpo ni t
V dc
Ta2
D a2 Tb2
D b2 T c2
D c2
2
ea
Vdc
eb
Vdc
ec
Vdc
eab
[a ]
ebc
eca
P. Ribeiro
ia
ib
ic
D
Ta 1
a1
Ta2
D
a2
D
b1
Tb1
D
Tb2
D
c1 b2
June, 2002
Tc2
29
[b ]
Voltage Source Converters
2, 3, 5-level, VSC Waveforms
vd c
2
vd c
2
+
e ou t
vd c
2
v dc
+
vd c
2
v dc
+
2 v dc
v dc
N eu tra l
m
( di -) po ni t
vd c
e ou t
+
1
v dc
+
2
+ v dc
N e u tra l
m
( di -) p o ni t
e ou t
vd c
P. Ribeiro
+
- v dc
v dc
June, 2002
+
30
Voltage Source Converters
Voltage-Source Converter Bridges
C
voa
voavobvo c
vdc
vdc
C
voavobvo c
Vdc
C
S ni g el -pha se ,
T h ree -pha se , w
t o -el ve l
w
t o -el ve lH -b rdi ge
s xi -pu sl e b rdi ge
P. Ribeiro
June, 2002
C /2
Vdc
C /2
T h ree -pha se , h
t ree -el ve l
12 -pu sl e b rdi ge
31
Voltage Source Converters
Output voltage control of a two-level VSC
v =V 0
iwt
v= V s n
io
v o= V o ( )
wt
*
wt
= *
v o ( )
v o ( )
v oF ( )= V (+ ) s n
i w tw t
(v+ v )d c
v d c nom ni a l
(v - v )d c
wt
C
idc
v d c= 1 i d c d t
C
i d c = f
v oF ( )= V (+ ) s n
iwt
P. Ribeiro
vdc
June, 2002
32
Voltage Source Converters
Output voltage control of a three-level VSC
iwt
v= V s n
v =V 0
io
v o= V o ( )
wt
*
= *
wt
wt
(< < )
v om ax
vo
v oF = f ( , )= s n
i (w t - )
V d c= con s t
wt
m ax = 2
3
P. Ribeiro
June, 2002
V dc
C /2
V dc
C /2
33
Voltage Source Converters
S ys etm B u sb a r
Multi-pulse VSC with
wave-forming magnetic circuits
C o u p lni g
T ra n s of m
r er
M agne tci s truc tu re
fo rm u lt i-pu sl e w a ve fo m
r syn the s si
C on ve r te r 1
C on ve r te r 2
C on ve r te r n
138 kV B u s
C oup ln
ig
T ran s fo m
r er
In te r fa ceM agne t c
is
P. Ribeiro
June, 2002
34
FACTS Technology - Possible Benefits
• Control of power flow as ordered. Increase the loading capability of lines to their
thermal capabilities, including short term and seasonal.
• Increase the system security through raising the transient stability limit, limiting
short-circuit currents and overloads, managing cascading blackouts and
damping electromechanical oscillations of power systems and machines.
• Provide secure tie lines connections to neighboring utilities and regions thereby
decreasing overall generation reserve requirements on both sides.
• Provide greater flexibility in siting new generation.
• Reduce reactive power flows, thus allowing the lines to carry more active power.
• Reduce loop flows.
• Increase utilization of lowest cost generation.
P. Ribeiro
June, 2002
35
FACTS and HVDC: Complimentary Solutions
HVDC
Independent frequency and control
Lower line costs
Power control, voltage control,
stability control
FACTS
Power control, voltage control,
stability control
Installed Costs (millions of dollars)
Throughput MW
HVDC 2 Terminals
FACTS
2000 MW
500 MW
1000 MW
2000 MW
$ 40-50 M
$ 75-100M
$120-170M
$200-300M
$ 5-10 M
$ 10-20M
$ 20-30M
$ 30-50M
(*)Hingorani/Gyugyi
P. Ribeiro
June, 2002
36
FACTS and HVDC: Complimentary Solutions
HVDC Projects: Applications
Submarine cable
Long distance overhead transmission
Underground Transmission
Connecting AC systems of different or incompatible frequencies
Large market potential for FACTS is within the ac system on a value-added basis, where:
• The existing steady-state phase angle between bus nodes is reasonable
• The cost of a FACTS device solution is lower than HVDC or other alternatives
• The required FACTS controller capacity is less than 100% of the transmission throughput rating
P. Ribeiro
June, 2002
37
FACTS Attributes for Different Controllers
FACTS Controller
Static Synchronous Compensator
(STATCOM without storage)
Static Synchronous Compensator
(STATCOM with storage, BESS, SMES,
large dc capacitor)
Static VAR Compensator (SVC, TCR,
TCS, TRS
Thyristor-Controlled Braking Resistor
(TCBR)
Static Synchronous Series Compensator
(SSSC without storage)
Static Synchronous Series Compensator
(SSSC with storage)
Thrystor-Controlled Series Capacitor
(TCSC, TSSC)
Thyristor-Controlled Series Reactor
(TCSR, TSSR)
Thyristor-Controlled Phase-Shifting
Transformer (TCPST or TCPR)
Unified Power Flow Controller (UPFC)
Thyristor-Controlled Voltage Limiter
(TCVL)
Thyristor-Controlled Voltage Regulator
(TCVR)
Interline Power Flow Controller (IPFC)
P. Ribeiro
Control Attributes
Voltage control, VAR compensation, damping oscillations, voltage
stability
Voltage control, VAR compensation, damping oscillations, transient
and dynamic stability, voltage stability, AGC
Voltage control, VAR compensation, damping oscillations, transient
and dynamic stability, voltage stability
Damping oscillations, transient and dynamic stability
Current control, damping oscillations, transient and dynamic stability,
voltage stability, fault current limiting
Current control, damping oscillations, transient and dynamic stability,
voltage stability
Current control, damping oscillations, transient and dynamic stability,
voltage stability, fault current limiting
Current control, damping oscillations, transient and dynamic stability,
voltage stability, fault current limiting
Active power control, damping oscillations, transient and dynamic
stability, voltage stability
Active and reactive power control, voltage control, VAR
compensation, damping oscillations, transient and dynamic stability,
voltage stability, fault current limiting
Transient and dynamic voltage limit
Reactive power control, voltage control, damping oscillations,
transient and dynamic stability, voltage stability
Reactive power control, voltage control, damping oscillations,
transient and dynamic stability, voltage stability
June, 2002
38
FACTS Implementation - STATCOM
P&Q
E1 / 1 I
E2 / 2
X
Regulating Bus Voltage
Can Affect Power Flow Indirectly / Dynamically
P1 = E1 (E2 . sin ())/X
P. Ribeiro
June, 2002
39
FACTS Implementation - TCSC
E1 / 1
P&Q
E2 / 2
X
Line Impedance Compensation
Can Control Power Flow Continuously
P1 = E1 (E2 . sin ()) / Xeff
Xeff = X- Xc
The alternative solutions need to be distributed; often series compensation has to be installed in several places along a line but many of the
other alternatives would put both voltage support and power flow control in the same location. This may not be useful. For instance, if
voltage support were needed at the midpoint of a line, an IPFC would not be very useful at that spot. TCSC for damping oscillations ...
P. Ribeiro
June, 2002
40
FACTS Implementation - TCSC
Breaker
X
MOV
TCSC
TCSC
TCSC
TCSC
TCSC
#2
#3
#4
#5
#6
TCSC module #1
Slatt TCSC
P. Ribeiro
June, 2002
41
FACTS Implementation - TCSC
Damping
Circuit
Damping
Circuit
Breaker
X
X
Breaker
MOV
MOV
MOV
40 Ω
55 Ω
TCSC 15 to 60 Ω
Kayenta TCSC
P. Ribeiro
June, 2002
42
FACTS Implementation - SSSC
E1 / 1
P&Q
E2 / 2
I
X
P1 = E1 (E2 . sin ()) / Xeff
Xeff = X - Vinj/I
P. Ribeiro
June, 2002
43
FACTS Implementation - UPFC
E1 / 1
P&Q
E2 / 2
I
X
Regulating Bus Voltage and Injecting Voltage
In Series With the Line
Can Control Power Flow
P1 = E1 (E2 . sin ()) / Xeff
Xeff = X - Vinj / I
Q1 = E1(E2 - E2 . cos ()) / X
P. Ribeiro
June, 2002
44
FACTS Implementation - UPFC
Series Transformer
Shunt Inverter
Series
Inverter
Shunt
Transforme
r
Unified Power Flow Controller
P. Ribeiro
June, 2002
45
FACTS Implementation - STATCOM + Energy Storage
E1 / 1
I
P&Q
E2 / 2
X
Regulating Bus Voltage Plus Energy Storage
Can Affect Power Flow Directly / Dynamically
Plus Energy Storage
P. Ribeiro
June, 2002
46
FACTS Implementation - SSSC + Energy Storage
E1 / 1
P&Q
E2 / 2
I
X
Voltage Injection in Series Plus Energy Storage
Can Affect Power Flow Directly / Dynamically
and sustain operation under fault conditions
Plus Energy Storage
P. Ribeiro
June, 2002
47
FACTS Implementation - UPFC + Energy Storage
E2 / 2
P&Q
E1 / 1
I
X
Plus Energy Storage
P. Ribeiro
Regulating Bus Voltage + Injected
Voltage + Energy Storage
Can Control Power Flow Continuously,
and Support Operation Under Severe
Fault Conditions (enhanced performance)
June, 2002
48
FACTS Implementation - UPFC + Energy Storage
Series
Inverter
Shunt
Inverter
1000μ
F
1000μ
F
1000μ
F
1000μ
F
SMES Chopper
and Coil
Unified Power Flow Controller - SMES Interface
P. Ribeiro
June, 2002
49
FACTS Implementation - UPFC + Energy Storage
MOV
UPFC
Grounding
SMES Chopper and Coil - Overvoltage Protection
P. Ribeiro
June, 2002
50
FACTS Implementation - TCSC + STACOM + Energy Storage
$
Regulating Bus Voltage + Energy
Storage + Line Impedance Compensation
Can Control Power Flow Continuously,
and Support Operation Under Severe
Fault Conditions (enhanced performance)
P. Ribeiro
June, 2002
51
FACTS Implementation - IPFC
E3 / 3
E1 / 1
E2 / 2
P12 = E1 (E2 . sin (1- 2)) / X
P13 = E1 (E2 . sin (1- 3)) / X
P. Ribeiro
June, 2002
52
FACTS Implementation - IPFC
Series Transformer, Line 1
Series Transformer, Line 2
Series Inverter #1
Series Inverter #2
Interline Power Flow Controller
P. Ribeiro
June, 2002
53
Enhanced Power Transfer and Stability:
Technologies’ Perspective
Compensation
Devices
FACTS Devices
Energy Storage
Fast
SMES Real Power Injection
and Absorption
P
P
TSSC
SSSC
UPFC
Electric Grid
Q
STATCOM
Q
2
Acceleration
Area
1.5
STATCOM
Fast
Reactive Power Injection and
Absorption
June, 2002
Increased Power
Transfer
Additio
nal
Stabilit
y
Margin
Electric Grid
Fast
Reactive Power Injection
and Absorption
P. Ribeiro
P
Power Transfer
TSSC
SSSC
UPFC
Deceleration
Area
Stability
Margin
1
0.5
0
0
0.5
1
1.5
2
2.5
3
Phase Angle
54
FACTS + Energy Storage
Q
The Role of Energy Storage: real
power compensation can
increase operating control and
reduce capital costs
STATCOM
Reactive Power Only
Operates in the
vertical axis only
P
MVA Reduction
The Combination or Real
and Reactive Power will
typically reduce the Rating of
the Power Electronics front
end interface.
Real Power takes care of
power oscillation, whereas
reactive power controls
voltage.
P. Ribeiro
P - Active Power
Q - Reactive Power
STATCOM + SMES
Real and Reactive Power
Operates anywhere within the
PQ Plane / Circle (4-Quadrant)
June, 2002
55
FACTS + Energy Storage - Location Sensitivity
Additional Power Transfer(MW)
Closer to generation
Closer to load centers
SMES Power (MW)
P. Ribeiro
June, 2002
56
Enhanced Power Transfer and Stability:
Location and Configuration Type Sensitivity
No Compensation
60.
8
59.
2
time (sec)
2 STATCOMs
1 STATCOM + SMES
60.
8
60.
8
59.
2
59.
2
time (sec)
time (sec)
Enhanced Voltage and Stability Control
Voltage and Stability Control
(2 x 80 MVA Inverters)
P. Ribeiro
( 80 MVA Inverter + 100Mjs SMES)
June, 2002
57
FACTS For Optimizing Grid Investments
FACTS Devices Can Delay Transmission Lines Construction
By considering series compensation from the very beginning, power transmission between regions can be
planned with a minimum of transmission circuits, thus minimizing costs as well as environmental impact
from the start.
The Way to Proceed
· Planners, investors and financiers should issue functional specifications for the transmission system
to qualified contractors, as opposed to the practice of issuing technical specifications, which are
often inflexible, and many times include older technologies and techniques) while inviting bids for a
transmission system.
· Functional specifications could lay down the power capacity, distance, availability and reliability
requirements; and last but not least, the environmental conditions.
· Manufacturers should be allowed to bid either a FACTS solution or a solution involving the
building of (a) new line(s) and/or generation; and the best option chosen.
P. Ribeiro
June, 2002
58
Specifications
(Functional rather than Technical )
Transformer Connections
Higher-Pulse Operation
Higher-Level Operation
PWM Converter
Pay Attention to Interface Issues and Controls
Converter
Increase Pulse Number
Higher Level
Double the Number of Phase-Legs and Connect them in Parallel
Connect Converter Groups in Parallel
Use A Combination of several options listed to achieve required rating and performance
P. Ribeiro
June, 2002
59
Cost Considerations
Technology
Reconductor lines
Fixed or Switched Shunt
Reactors
Fixed or Switched Shunt
Capacitors
Fixed or Switched Series
Capacitors
Static VAR Compensators
Thyristor Controlled Series
Compensation (TCSC)
STATCOM
STATCOM w/SMES
Transmission Line
Transfer Enhancement
Increase thermal capacity
Voltage reduction – Light
Load Management
Voltage support and
stability
Power flow control,
Voltage support and
Stability
Voltage support and
stability
Power flow control,
Voltage support and
stability
Voltage support and
stability
Voltage support and
stability
Cost Range
$50K to $200K per
mile
$8-$12 kVAR
$8-$10 kVAR
$12-$16 kVAR
$20-$45 kVAR
$25-$50 kVAR
$80-$100 kVAR
$150-$300 kW
Unified Power Flow
Controller (UPFC)
Operating principle
Increases thermal limit for line
Procurement
Availability
Competitive
Compensates for capacitive varload
Compensates for inductive varload
Reduces inductive line
impedance
Competitive
Compensates for inductive
and/or capacitive var-load
Reduces or increases inductive
line impedance
Competitive
Compensates for inductive and
capacitive var-load
Compensates for inductive
and/or capacitive var-load plus
energy storage for active power
SVC and TCSC functions plus
phase angle control
Limited
competition
Limited
Competitive
Competitive
Limited
competition
Power flow control,
$150-$200 kW
Sole source
Voltage support, and
Stability
Unified Power Flow
Power flow control
$250-$350 kW
SVC and TCSC functions plus
Sole source
Controller (UPFC) w/SMES Voltage support and
voltage regulator, phase angle
Stability,
controller and energy storage
Shaded area indicates technologies that are either permanently connected or switched on or off with mechanical switches. (i.e. these are
not continuously controllable)
P. Ribeiro
June, 2002
60
Cost Considerations
Hardware
Eng & Project Mgmt.
Installation
Civil Works
Commissioning
Insurance
Cost structure
The cost of a FACTS installation depends on many factors, such as power rating, type of device, system
voltage,
system requirements, environmental conditions, regulatory requirements etc. On top of this, the variety of
options available for optimum design renders it impossible to give a cost figure for a FACTS installation.
It is strongly recommended that contact is taken with a manufacturer in order to get a first idea of costs and
alternatives. The manufacturers should be able to give a budgetary price based on a brief description of the
transmission system along with the problem(s) needing to be solved and the improvement(s) needing to be
attained.
(*) Joint World Bank / ABB Power Systems Paper
Improving the efficiency and quality of AC transmission systems
P. Ribeiro
June, 2002
61
Technology & Cost Trends
$
I
$$$
$
I
additional cost savings possible
P. Ribeiro
June, 2002
62
Concerns About FACTS
Cost
Losses
Reliability
P. Ribeiro
June, 2002
63
Economics of Power Electronics
Sometimes a mix of conventional and FACTS systems has the lowest cost
Losses will increase with higher loading and FACTS equipment more lossy than conventional ones
Reliability and security issues - when system loaded beyond the limits of experience
Demonstration projects required
100% Power
Electronics
Delta-P4
Delta-P2
Delta-P3
Delta-P1
100%
Conventional
Cost of System
P. Ribeiro
Stig Nilson’s paper
June, 2002
64
Operation and Maintenance
Operation of FACTS in power systems is coordinated with operation of other items in the
same system, for smooth and optimum function of the system. This is achieved in a
natural way through the Central Power System Control, with which the FACTS device(s)
is (are) communicating via system SCADA. This means that each FACTS device in the
system can be operated from a central control point in the grid, where the operator will
have skilled human resources available for the task. The FACTS device itself is normally
unmanned, and there is normally no need for local presence in conjunction with FACTS
operation, although the device itself may be located far out in the grid.
Maintenance is usually done in conjunction with regular system maintenance, i.e.
normally once a year. It will require a planned standstill of typically a couple of days.
Tasks normally to be done are cleaning of structures and porcelains, exchanging of
mechanical seals in pump motors, checking through of capacitors, checking of control and
protective settings, and similar. It can normally be done by a crew of 2-3 people with
engineer´s skill.
Joint World Bank / ABB Power Systems Paper
Improving the efficiency and quality of AC transmission systems
P. Ribeiro
June, 2002
65
Impact of FACTS in interconnected networks
The benefits of power system interconnection are well established. It enables the participating parties to
share the benefits of large power systems, such as optimization of power generation, utilization of
differences in load profiles and pooling of reserve capacity. From this follows not only technical and
economical benefits, but also environmental, when for example surplus of clean hydro resources from one
region can help to replace polluting fossil-fuelled generation in another.
For interconnections to serve their purpose, however, available transmission links must be powerful
enough to safely transmit the amounts of power intended. If this is not the case, from a purely technical
point of view it can always be remedied by building additional lines in parallel with the existing, or by
uprating the existing system(s) to a higher voltage. This, however, is expensive, time-consuming, and calls
for elaborate procedures for gaining the necessary permits. Also, in many cases, environmental
considerations, popular opinion or other impediments will render the building of new lines as well as
uprating to ultrahigh system voltages impossible in
practice. This is where FACTS comes in.
Examples of successful implementation of FACTS for power system interconnection can be found among
others between the Nordic Countries, and between Canada and the United States. In such cases, FACTS
helps to enable mutually beneficial trade of electric energy between the countries.
Other regions in the world where FACTS is emerging as a means for AC bulk power interchange between
regions can be found in South Asia as well as in Africa and Latin America. In fact, AC power corridors
equipped with SVC and/or SC transmitting bulk power over distances of more than 1.000 km are a reality
today.
P. Ribeiro
Joint World
Bank / ABB Power Systems Paper
Improving the efficiency and quality of AC transmission systems
June, 2002
66
Power Quality Issues
1 – Background (Power Quality – Trade Mark)
2 – The Need For An Integrated Perspective of PQ
3 – Harmonics
4 – Imbalance
5 – Voltage Fluctuations
6 – Voltage Sags
7 – Standards, Limits, Diagnostics, and Recommendations
Flexibility, Compatibility, Probabilistic Nature, Alternative Indices
8 – Combined effects
9 – Power Quality Economics
10 – Measurement Protocols
11 – Probabilistic Approach
12 – Modeling & Simulation
13 – Advanced Techniques
(Wavelet, Fuzzy Logic, Neural Net, Genetic Algorithms)
14 – Power Quality Programs
P. Ribeiro
June, 2002
67
Compatibility: The Key Approach
P. Ribeiro
June, 2002
68
Relative Trespass Level (RTL)
U k Uref k
RTL k max 0,
Uref k
Uk - measured or calculated harmonic voltage
Uref - harmonic voltage limit (standard or particular equipment)
k - harmonic order
8
8
8
6
6
RT Lk
RT Lk
4
0
0
2
2
P. Ribeiro
4
2
2
0
8
4
6
8
k
10
12
14
13
June, 2002
0
0
0.05
0.1
0
Uk
.1
69
Harmonic Distortion Diagnostic Index Applying Fuzzy Logic
Comparisons
Alternative Approach
Individual Harmonics (Vh)
Equipment Malfunction
Fuzzy - Color Code Criteria
No Problem
b
c
Below
NormalOver
Below
Normal
Heating
Normal
a
Caution
Possible Problems
Very
Hot
d
Imminent Problems
e
1
Normal
Levels
0
P. Ribeiro
A
B
Caution Possible Severe Dangerous
Problems Distortions Levels
C
June, 2002
D
E
F
G
RTL
70
Harmonics
Definition of harmonics
Sources of harmonics
Effects of harmonics
Mitigation methods
Considerations on the extra costs due to harmonic pollution
Measurement results
Voltage fluctuations/Flicker
Definitions
Sources of voltage fluctuations/flicker
Effects of voltage fluctuations/flicker
Mitigation methods
Measurement results
P. Ribeiro
June, 2002
71
Voltage Dips
Definition
Sources of voltage dips
Effects of voltage dips
Mitigation methods
Measurement results
Conclusions
Unbalance
Definition
Sources of unbalance
Effects of unbalance
Mitigation methods
Measurement results
Transient Overvoltages
P. Ribeiro
June, 2002
72
How To Interpret This?
P. Ribeiro
June, 2002
73
How To Interpret This?
P. Ribeiro
June, 2002
74
How To Interpret This?
P. Ribeiro
June, 2002
75
The Total Quality Environment
Power System Value Chain
Environmental
Maintainability
Availability
Safety
Efficiency
Reliability
Performance
Price
Power Quality
Energy
INPUTS
Generation
Delivery
Conversion
Power
Processing
Communication
OUTPUTS
Light / Motion
Central
Station
T&D
AC-AC
Supplies
Motion
SMES
Batteries
FACTS
SMES
PQ Parks
UPS
Appliances
Power Electronics Systems and Components
User
Utility
P. Ribeiro
June, 2002
76
Benefits of a Power Quality Program
Offer options to customers with PQ concerns
Attract new business to area (regional development)
Facilitate load retention of current customers
Meet changing needs of customer's new technology
Discourage co-generation or self-generation as solutions of
PQ Problems
Enhance and public image - as customers hold utility accountable
for both PQ and reliability
Add value to service
Serve customers' best interests and save customers money
Support utility mission
P. Ribeiro
June, 2002
77
Suggested Topics for Investigation
FACTS
Inclusion of Energy Storage
Topology Combination
Power Quality
Effects of Power Quality on Relaying Equipment
Cost/Benefit Analysis of PQ
Application of Advanced Techniques
P. Ribeiro
June, 2002
78
Conclusions
•
•
•
•
•
•
•
•
P. Ribeiro
Future systems can be expected to operate at higher stress levels
FACTS could provide means to control and alleviate stress
Reliability of the existing systems minimize risks (but not risk-free)
Interaction between FACTS devices needs to be studied
Existing Projects - Met Expectations
More Demonstrations Needed
R&D needed on avoiding security problems (with and w/o FACTS)
Energy storage can significantly enhance FACTS controllers performance
June, 2002
79
Conclusions
Power supply industry is undergoing dramatic change as a result of deregulation and
political and economical maneuvers. This new market environment puts demands for
flexibility and power quality into focus. Also, trade between companies and countries
of electric power is gaining momentum, to the benefit of all involved. This calls for the
right solutions as far as power transmission facilities between countries as well as
between regions within countries are concerned.
FACTS Benefits included:
-An increase of synchronous stability of the grid;
-An increased voltage stability in the grid;
-Decreased power wheeling between different power systems;
-Improved load sharing between parallel circuits;
-Decreased overall system transmission losses;
-Improved power quality in grids.
•The choice of FACTS device is simple and needs to be made the subject of detailed
system studies, taking all relevant requirements and prerequisites of the system into
consideration, so as to arrive at the optimum technical and economical solution. In
fact, the best solution may often be lying in a combination of devices.
P. Ribeiro
June, 2002
80
Conclusions
From an economical point of view, more power can be transmitted over existing or
new transmission grids with unimpeded availability at an investment cost and
time expenditure lower, or in cases even far lower than it would cost to achieve the
same with more extensive grids. Also, in many cases, money can be saved on a
decrease of
power transmission losses.
From an environmental point of view, FACTS enables the transmission of power
over vast distances with less or much less right-of-way impact than would
otherwise be possible. Furthermore, the saving in transmission losses may well
bring a corresponding decrease in need for generation, with so much less toll on
the environment.
All these things help to enable active, useful power to reach out in growing
quantities to growing populations under safe and favorable conditions all over the
world. Also, individual countries´ own border lines no longer constitute any limit
to power industry. With FACTS, power trade to the benefit of many can be
established to a growing extent across June,
borders,
by making more efficient use of
P. Ribeiro
2002
interconnections between countries, new as well as existing.
81
Conclusions
A Balanced and Cautious Application
The acceptance of the new tools and technologies will take time, due to the
computational requirements and educational barriers.
The flexibility and adaptability of these new techniques indicate that they
will become part of the tools for solving power quality problems in this
increasingly complex electrical environment.
The implementation and use of these advanced techniques needs to be done
with much care and sensitivity. They should not replace the engineering
understanding of the electromagnetic nature of the problems that need to
be solved.
P. Ribeiro
June, 2002
82