Intelligent distribution substation improves power quality
Download
Report
Transcript Intelligent distribution substation improves power quality
Frankfurt (Germany), 6-9 June 2011
Intelligent Distribution Substation
improves power quality
Irina Melnik – the Netherlands – Session S2 – 0665
Frankfurt (Germany), 6-9 June 2011
Need for new technologies
MV
LV
Load
Power
MV
Generation
Micro
CHP
Micro
CHP
Micro
CHP
Load
Power
PV
Fluctuating loads
Distributed generation
Changes in power flows
Larger voltage variations
Uncertainty for planning
Complex grid operation
LV
PV
Monitoring and control
New technologies
Frankfurt (Germany), 6-9 June 2011
Intelligent distribution substation (IntDS)
Developed by a consortium of Dutch industries
Installed and tested in the grid of DSO Alliander
Additional functions of the IntDS:
Monitoring
Control
Improving Power Quality
Frankfurt (Germany), 6-9 June 2011
“Intelligent” components of IntDS
Smart
Transformer
Electricity storage system
with bidirectional inverter
Measurement system
Frankfurt (Germany), 6-9 June 2011
IntDS implementation
District with large amount of
micro Combined Heat Power
at customers
Frankfurt (Germany), 6-9 June 2011
Test program
Power Quality improvement by the IntDS:
Voltage control
Reduction of harmonic distortion
Reduction of flicker
Mitigation of voltage dips
Frankfurt (Germany), 6-9 June 2011
Voltage control
Performed by Smart Transformer:
Electronic tap changer ensures
a constant voltage level on the LV rail
of the IntDS.
The voltage control set-point
has to be determined to achieve
the optimal voltage level on PCC’s
of all LV customers.
Smart
Transformer
Frankfurt (Germany), 6-9 June 2011
Voltage control – test results
LV bus-bar
control
U avg
U max
U min
no control
LV customer
1
2
control
3
1
2
3
no control
Frankfurt (Germany), 6-9 June 2011
Harmonic distortion reduction
Performed by ESI
(Electricity storage inverter) :
Resistive harmonic damping
Passive harmonic damping
The filter capacitors of the ESI take
part in the filtering of harmonics.
Electricity storage system
with bidirectional inverter
Frankfurt (Germany), 6-9 June 2011
Harmonic distortion reduction – test results
LV bus-bar
no control
control
H03 max
H05 max
H07 max
THD max
no
LV customer
no control
control
no
Frankfurt (Germany), 6-9 June 2011
Voltage dips mitigation
Can be performed by:
the Smart Transformer
the ESI (Electricity storage inverter)
Voltage dips occur only a few times per year
on an LV bus-bar of Dutch distribution substations.
That’s why this functionality is not actively tested.
Frankfurt (Germany), 6-9 June 2011
Flicker reduction (LV side)
Performed by:
The electronic tap changer of the Smart Transformer
The flicker reduction control of the bidirectional inverter (ESI)
of the storage system.
Frankfurt (Germany), 6-9 June 2011
Flicker reduction – test results
Plt avg
Pst avg
Plt max
Pst max
LV bus-bar
no
control
LV customer
no
control
Frankfurt (Germany), 6-9 June 2011
Conclusions
The Intelligent substation has proved to be safe in operation.
The first field test results demonstrate a significant reduction
of voltage variations, harmonic and THD levels both at the
LV bus-bar of the IntDS and at the LV customers.
Further metering and test programs will be performed to set
optimal set-points for control equipments.
The proved principles can be used for area’s with high levels
of PQ distortions.
Irina Melnik – the Netherlands – Session S2 – 0665