ups technology update

Download Report

Transcript ups technology update

Consult + Engineer + Commission
“UNINTERRUPTIBLE POWER SYSTEM
(UPS) TECHNOLOGY UPDATE”
IEEE Industry Applications Society
Atlanta Chapter
January 18, 2011
Creating Exceptional Environments
© All Rights Reserved
www.syska.com
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
TYPES OF UPS TECHNOLOGIES
•STATIC, DOUBLE CONVERSION
•STATIC, LINE INTERACTIVE
•FLYWHEEL-BASED
•ROTARY
•OFF-LINE
© All Rights Reserved
2
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
STATIC, DOUBLE CONVERSION UPS TOPOLOGY
•NORMAL POWER PATH: INPUT-RECTIFIER-DC BUSINVERTER-OUTPUT
•BYPASS POWER PATH: INPUT-STATIC SWITCH-OUTPUT
•STORED POWER PATH: BATTERY/FLYWHEEL-DC BUSINVERTER-OUTPUT
•MAJOR MANUFACTURERS: GE, LIEBERT, MGE,
MITSUBISHI, POWERWARE, TOSHIBA
© All Rights Reserved
3
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
© All Rights Reserved
4
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
STATIC, DOUBLE CONVERSION UPS CHANGES FOR
INCREASED OPERATING EFFICIENCY
•PWM IGBT RECTIFIERS INSTEAD OF SCRS
•PWM IGBT INVERTERS
•ELIMINATE INPUT AND OUTPUT TRANSFORMERS
•USER-SELECTABLE OFFLINE OPERATION
•USER-SELECTABLE CAPACITY CONTROL
•DISTRIBUTED OR SYSTEM STATIC BYPASS SWITCH
© All Rights Reserved
5
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
STATIC, DOUBLE CONVERSION UPS OPERATING
EFFICIENCY
•TYPICALLY 91%-96% AT FULL LOAD AND 90%- 94%
AT HALF LOAD
•USER-SELECTABLE OFFLINE 98%
•USER-SELECTABLE CAPACITY CONTROL CAN
IMPROVE % AT LOW LOADS
© All Rights Reserved
6
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
THE FLEAS THAT COME WITH THE DOG, PART 1
•ELIMINATING TRANSFORMERS REDUCES DC BUS
SAFETY
•INDUSTRY TREND IS TO ELIMINATE TRANSFORMERS
•ELIMINATING THE OUTPUT TRANSFORMER MAY
ELIMINATE A WYE-CONNECTED OUTPUT
•INDUSTRY TREND IS TO PROVIDE DISTRIBUTED
STATIC BYPASS SWITCHES
•IN USER-SELECTABLE OFFLINE MODE, SOME
TRANSIENTS COULD GET THROUGH BEFORE
THE UPS CAN REACT
© All Rights Reserved
7
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
STATIC, LINE-INTERACTIVE UPS TOPOLOGY
•NORMAL POWER PATH: INPUT-MAIN STATIC
SWITCH-OUTPUT
•BYPASS POWER PATH: INPUT-ALTERNATE STATIC
SWITCH-OUTPUT
•STORED POWER PATH: BATTERY-DC BUS-INVERTEROUTPUT
•MANUFACTURER: APC (SYMMETRA MW)
© All Rights Reserved
8
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
© All Rights Reserved
9
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
STATIC, LINE INTERACTIVE UPS CHANGES FOR
INCREASED OPERATING EFFICIENCY
•IMPROVED FIRMWARE CONTROL
STATIC, LINE INTERACTIVE UPS OPERATING
EFFICIENCY
•TYPICALLY 97% AT FULL LOAD, 96% AT HALF LOAD
AND 94% AT QUARTER LOAD
© All Rights Reserved
10
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
THE FLEAS THAT COME WITH THE DOG, PART 2
•REDUCED DC BUS SAFETY
•SOME TRANSIENTS COULD GET THROUGH
BEFORE THE UPS CAN REACT
© All Rights Reserved
11
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
FLYWHEEL-BASED UPS TOPOLOGY
•NORMAL POWER PATH: INPUT-MAIN STATIC
SWITCH-INDUCTOR-OUTPUT
•BYPASS POWER PATH: INPUT-ALTERNATE STATIC
SWITCH-OUTPUT
•STORED POWER PATH: FLYWHEEL-CONVERTERINDUCTOR-OUTPUT
•MANUFACTURER: ACTIVE POWER
© All Rights Reserved
12
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
© All Rights Reserved
13
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
FLYWHEEL-BASED UPS CHANGES FOR INCREASED
OPERATING EFFICIENCY
•IMPROVED FIRMWARE CONTROL
STATIC, LINE INTERACTIVE UPS OPERATING
EFFICIENCY
•TYPICALLY 98% AT FULL LOAD AND 96% AT HALF
LOAD
© All Rights Reserved
14
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
THE FLEAS THAT COME WITH THE DOG, PART 3
•LIMITED ENERGY STORAGE – 14 SECONDS
•SYSTEM CAPACITY LIMITED BY THE CAPACITY OF
ONE STANDBY GENERATOR
© All Rights Reserved
15
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
BASIC ROTARY UPS TOPOLOGY
•NORMAL POWER PATH: INPUT-RECTIFIERINVERTER-SYNCHRONOUS MACHINE-OUTPUT
•BYPASS POWER PATH: INPUT-STATIC SWITCH SYNCHRONOUS MACHINE –OUTPUT
•STORED POWER PATH: BATTERY-DC BUS-INVERTERSYNCHRONOUS MACHINE-OUTPUT
•MANUFACTURER: PILLER
© All Rights Reserved
16
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
© All Rights Reserved
17
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
VARIATION ON ROTARY UPS TECHNOLOGY,
AKA DYNAMIC ROTARY UPS (DRUPS)
•NORMAL POWER PATH: INPUT-RECTIFIER-COUPLING
CHOKE-OUTPUT
•BYPASS POWER PATH: INPUT-BYPASS SWITCH OUTPUT
•STORED POWER PATH: ENGINE-COUPLING-ENERGY
ACCUMULATOR-SYNCHRONOUS MACHINECOUPLING CHOKE-OUTPUT
•CAN OPERATE AT LOW VOLTAGE OR MEDIUM
VOLTAGE
•MANUFACTURERS: EURO-DIESEL, HITEC, PILLER
© All Rights Reserved
18
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
© All Rights Reserved
19
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
ROTARY UPS CHANGES FOR INCREASED OPERATING
EFFICIENCY
•IMPROVED FIRMWARE CONTROL
•USER-SELECTABLE OFFLINE OPERATION
ROTARY UPS OPERATING EFFICIENCY
•TYPICALLY 92% AT FULL LOAD AND 88% AT HALF
LOAD (BASIC)
•TYPICALLY 96% AT FULL LOAD AND 48% AT HALF
LOAD (VARIATION)
© All Rights Reserved
20
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
THE FLEAS THAT COME WITH THE DOG, PART 4
•VARIATION IS THE MOST UPS CAPACITY/SQUARE
FOOT OF BUILDING AREA
•VARIATION HAS CONSTANT LOSSES, REGARDLESS
OF LOAD
•VARIATION CAN SUPPLY LARGE MEDIUM
VOLTAGE SYSTEMS (VOLTAGE VARIES BY
MANUFACTURER)
© All Rights Reserved
21
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
OFFLINE UPS TOPOLOGY
•NORMAL POWER PATH: INPUT-STATIC SWITCHOUTPUT
•BYPASS POWER PATH: INPUT-BYPASS SWITCHOUTPUT
•STORED POWER PATH: BATTERY-INVERTER-STEPUP
TRANSFORMER-OUTPUT
•CAN OPERATE AT LOW OR MEDIUM VOLTAGE (UP
TO 25KV)
•MANUFACTURER: S&C
© All Rights Reserved
22
Consult + Engineer + Commission
© All Rights Reserved
23
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
OFFLINE UPS CHANGES FOR INCREASED OPERATING
EFFICIENCY
•CAPACITY UP TO 16MW PER SYSTEM
•IMPROVED FIRMWARE
•CAN ACCOMMODATE WET CELL OR VRLA BATTERIES
•CAN ACCOMMODATE UP TO 20 MINUTES BATTERY
OPERATION AT FULL LOAD
•CAN BE INSTALLED INDOORS OR OUT DOORS
•CAN UTILIZE METAL-ENCLOSED OR METAL-CLAD
SWITCHGEAR
•DISTRIBUTED OR SYSTEM STATIC BYPASS SWITCH
© All Rights Reserved
24
Consult + Engineer + Commission
OFFLINE UPS OPERATING EFFICIENCY
•TYPICALLY 98%-99% AT ALL LOADS
THE FLEAS THAT COME WITH THE DOG, PART 5
•SOME TRANSIENTS COULD GET THROUGH BEFORE THE
UPS CAN REACT
© All Rights Reserved
25
Consult + Engineer + Commission
Thank You!
Comments and Questions?
Creating Exceptional Environments
© All Rights Reserved
www.syska.com