OPERATIONS - DB
Burners Technical Training
CONTROL BOX RMG88.620
All information here reported have been made for teaching purposes. To operate on Riello Burners the official manual instruction must be considered.
This document contains confidential and proprietary information of Riello SpA. Unless authorised, these information shall not be divulged, nor duplicated in whole or in part.
OPERATIONS - DB
Burners Technical Training
Dedicated to:
Gas burners
GS SERIES
ONE STAGE
TWO STAGE
GAS SERIES
ONE STAGE
TWO STAGE
RS SERIES
ONE STAGE
TWO STAGE
All information here reported have been made for teaching purposes. To operate on Riello Burners the official manual instruction must be considered.
This document contains confidential and proprietary information of Riello SpA. Unless authorised, these information shall not be divulged, nor duplicated in whole or in part.
OPERATIONS - DB
Burners Technical Training
FEATURES
MODELS
RMG88.620A2RL
RMG88.620A1RL
Mode operation………….…... Intermittent
Intermittent
Main voltage…………….…... AC 220-240 V +10% -15%
AC 100-120 V +10% -15%
Frequency…………….…...
50-60 Hz +/-6%
50-60 Hz +/-6%
Under Voltage protection…...
Approx. AC 170 V
Approx. AC 70 V
Primary fuse…………….…...
Max 16 A
Max 16 A
Power consumption……..…... 20 VA
20 VA
Internal fuse…….……..…...
T6.3
T6.3H250V (IEC 127-215)
Polarity...………….……..…... Must be observed (checked)
Must be observed (checked)
Voltage at ionization probe.…. AC 115-230 V
AC 50-120 V
Flame signal (current ioniz.)…. 1.5 A (pre-purge)
3 A (operation)
1.5 A (pre-purge)
3 A (operation)
All information here reported have been made for teaching purposes. To operate on Riello Burners the official manual instruction must be considered.
This document contains confidential and proprietary information of Riello SpA. Unless authorised, these information shall not be divulged, nor duplicated in whole or in part.
OPERATIONS - DB
Burners Technical Training
Timings of cycle
Waiting time………….…...
RMG88.620A2RL
RMG88.620A1RL
NOTES
2 sec………………………….. Beginning when both
# 4 & # 9 are energised.
If not input to # 4 within
60 sec since # 9 is
energised lock out
Checked Pre-purge time (min).. 40 sec (55sec on A1RL type)... Time between no voltage
at # 4 (P.switch at working
position) and both # 12
and # 13 outputs
Max time for the
air P.Switch to change……... 10 sec
Post-ignition time……….…...
2 sec
Ignition safety time……..…...
3 sec
Interval 1st 2nd stage..…...
10 sec…………………………. Interval between # 12
# 14 outputs
Voltage at # 3 …….………. .
25 sec…………………………...to manage a servomotor
All information here reported have been made for teaching purposes. To operate on Riello Burners the official manual instruction must be considered.
This document contains confidential and proprietary information of Riello SpA. Unless authorised, these information shall not be divulged, nor duplicated in whole or in part.
OPERATIONS - DB
Burners Technical Training
CONTROL PROGRAM IN EVENT OF FAULT
Cause
Reponse
Mains failure
Restart with program sequence
Voltage dropped below
undervoltage threshold
Premature flame signal
Restart with program sequence
Lock-out
Burner does not ignite within
Lock-out
safety time
Loss of flame during operation Immediate lock out
Air pressure switch welded in
indle position
Air pressure switch in working
position at beginning
Air pressure failure within prepurge
Air pressure failure at
oparation
Lock-out 10 secs after the motor start
Prevention of start-up and about 1 min
after, lock-out
4 new starts, then lock-out
Immediate lock-out
All information here reported have been made for teaching purposes. To operate on Riello Burners the official manual instruction must be considered.
This document contains confidential and proprietary information of Riello SpA. Unless authorised, these information shall not be divulged, nor duplicated in whole or in part.
OPERATIONS - DB
Burners Technical Training
INDICATION OF OPERATION
Color code table
Stand-by and waiting statuses
Pre-purging
Ignition phase, ignition controlled
Operation, flame OK
Operation, poor flame
Undervoltage, built-in fuse
Fault, alarm
Extraneous light
Error code output (e.g. 2 blinks)
All information here reported have been made for teaching purposes. To operate on Riello Burners the official manual instruction must be considered.
This document contains confidential and proprietary information of Riello SpA. Unless authorised, these information shall not be divulged, nor duplicated in whole or in part.
OPERATIONS - DB
Burners Technical Training
SELF-DIAGNOSTIC
Operating concept
Burner control has initiated lockout
Red fault LED on
Reset
Press lockout reset button for about 1 s
Diagnosis of cause of fault
– Press lockout reset button for > 3 s
– Press again lockout reset button for > 3 s
– Read blink code of red fault LED
«Error code table A»
All information here reported have been made for teaching purposes. To operate on Riello Burners the official manual instruction must be considered.
This document contains confidential and proprietary information of Riello SpA. Unless authorised, these information shall not be divulged, nor duplicated in whole or in part.
OPERATIONS - DB
Burners Technical Training
Error code table A
Blink code
Possible cause
2 x
No establishment of flame at the end of «TSA»
– Faulty or soiled detector electrode
– Faulty or soiled fuel valves
– Poor adjustment of burner
– Faulty ignition equipment
3 x
Faulty air pressure monitor
– «LP» faulty
– «LP» incorrectly adjusted
– Fan motor does not run
4 x
extraneous light on burner startup
7 x
Loss of flame during operation
– Poor adjustment of burner
– Faulty or soiled fuel valves
– Short-circuit between detector electrode and ground
10 x
Wiring error or internal fault, output contact, unidentifiable
fault, e.g. faults that occurred simultaneously