Serial / Ethernet Converter
Download
Report
Transcript Serial / Ethernet Converter
Introduction to Weidmüller
Serial/Ethernet Converter
► IE-CS-2TX-1RS232/485
► IE-CS-2TX-2RS232/485
Serial / Ethernet Converter - IE-CS-2TX-XRS232/485
IE-CS-2TX-1RS232/485 and IE-CS-2TX-2RS232/485
Model 1: Serial/Ethernet Converter with two Ethernet ports and one serial
interface
Model 2: Serial/Ethernet Converter with two Ethernet ports and two serial
interfaces
Allow the access (e.g. PC’s) to components with serial interfaces over an
Ethernet network
Connect remote components with serial interface over an Ethernet network
Available mid of may 2011
List price in Germany
IE-CS-2TX-1RS232/485 298 €
IE-CS-2TX-2RS232/485 362 €
Page 2
Introduction to Weidmüller Serial/Ethernet Converter
Specifications and Features
Robust industrial design in a high-quality metal housing (IP30)
IE-CS-2TX-1RS232/485
2 Fast Ethernet ports (unmanaged 2-Port-Switch)
Transfer rates for serial ports from 50 to 921.6 kBit/s
Redundant power input 12 - 48 VDC
Operating temperature 0°C – 60°C (Model with extended temperature
range -40°C to +75°C available in Q3 / 2011)
Increased surge protection (Serial Ports: 1 kV, Ethernet Interfaces: 1kV
and Power Input: 2 kV)
Integrated Watchdog timer and alarm buzzer
Warning by eMail or relay output
DIP switches for termination of RS485 connections
Configuration by
Windows Management Software
Web-Interface
Telnet or RS232 Console
Software drivers for all versions of Windows (Virtual COM port)
Approvals: CE, FCC, UL (Pending: Class 1 Div.2 / Atex)
Page 3
Introduction to Weidmüller Serial/Ethernet Converter
IE-CS-2TX-2RS232/485
Overview Serial/Ethernet Converter functions
Converter functions
RealCOM mode
TCP-Server mode
TCP-Client mode
Pair Connection mode
UDP mode
COM grouping
COM Grouping function is designed to simulate the serial RS-485 multi-drop
behavior over an Ethernet network
Introduction to Weidmüller Serial/Ethernet Converter
Page 4
S/E-Converter functions RealCOM Mode
PC connection to serial devices over Ethernet
Communication with serial devices via Virtual COM port
Virtual COM port is set up via software drivers (Serial/Ethernet Converter
Software "SE-Administration Tool")
Each virtual COM port is assigned an IP-address/ port number combination
that points to a real Serial Ethernet Converter inside the network
PC application "thinks" that it communicates with an actual COM port
Sample application:
Configuration and data retrieval of an intelligent smart meter with a
serial interface
IP = 192.168.1.140
Ethernet
PC with „Smart-Meter“
software application
using COM3
Ethernet
TCP/IP
Ethernet
Network
Ethernet
RS232 /
RS485
Switch
Intelligent
smart meter
COM3 = IP:port = 192.168.1.140:4001
Introduction to Weidmüller Serial/Ethernet Converter
Page 5
S/E-Converter functions TCP-Server Mode
Serial/Ethernet Converter waits passively for host computer to establish a connection
Supports up to 8 simultaneous connections, allowing multiple hosts to collect data from the
same serial device at the same time
PC application which actively
retrieves the data (Mode
TCP/IP-Client)
Ethernet
TCP/IP
Ethernet
Intelligent
sensor
Ethernet
RS232 /
max. 8 connections
at the same time
RS485
Waits passively for data
requests
PLC application which actively
retrieves the data (Mode
TCP/IP-Client)
Introduction to Weidmüller Serial/Ethernet Converter
(Mode TCP/IP-Server)
Page 6
S/E-Converter functions TCP-Client Mode
Serial/Ethernet Converter establishes a connection to a specified host computer
SE-Converter closes the connection after data has been transferred
Supports up to 4 simultaneous connections, allowing multiple hosts to collect data from the
same serial device at the same time
PC application which waits for
retrieving the data (Mode
TCP/IP-Server)
Ethernet
max. 4
connections at
the same time
TCP/IP
Ethernet
Intelligent
sensor
Ethernet
RS232 /
RS485
PLC application which waits for
retrieving the data (Mode
TCP/IP-Server)
Introduction to Weidmüller Serial/Ethernet Converter
SE-Converter can actively send the sensor
data to 4 IP addresses at the same time
(Mode TCP/IP-Client)
Page 7
S/E-Converter functions Pair Connection Mode
Connecting two remote serial devices over an Ethernet network
Transparent data transfer for the serial devices
Allows communication between serial devices over long distances (only dependent from the
Ethernet network, RS232 direct connection max. 15 m)
Very simple Web configuration (One device as Pair Connection master, the other device as
Pair Connection slave)
Sample application: Showing the data of a sensor with a serial interface on a
remote control display
RS232 /
Ethernet
RS485
Display for sensor
data
Mode “Pair Connection
Slave”
Introduction to Weidmüller Serial/Ethernet Converter
TCP/IP
Ethernet
Intelligent
Sensor
Ethernet
RS232 /
RS485
Mode “Pair Connection
Master”
Page 8
Cascading of several Serial/Ethernet-Converter
Connecting several Serial/Ethernet Converter in a line structure
Saving of additional switches due to integrated unmanaged 2-port switch
Ethernet
Ethernet
Switch
PC's with software applications for
serial devices
Introduction to Weidmüller Serial/Ethernet Converter
Ethernet
Ethernet
Serial Connections RS232/ RS485
Controls/PLC‘s
Barcode
scanner
Measuring
instruments
Page 9
Intelligent
sensors
Accessing and Configuring
Configuration by
WEB Interface
Weidmüller S/E-
Converter
Administration
Tool
Introduction to Weidmüller Serial/Ethernet Converter
Page 10
WEB Interface „Quick Setup = 3-Step Easy Configuration“
Page 11
Introduction to Weidmüller Serial/Ethernet Converter
WEB Interface „Basic Settings“
Page 12
Introduction to Weidmüller Serial/Ethernet Converter
WEB Interface „Network Settings“
Page 13
Introduction to Weidmüller Serial/Ethernet Converter
WEB Interface „Serial Settings Port1 / Port 2“
Page 14
Introduction to Weidmüller Serial/Ethernet Converter
WEB Interface „Operating Mode Selection “
Page 15
Introduction to Weidmüller Serial/Ethernet Converter
WEB Interface „Operating Modes RealCOM and TCP Server “
Page 16
Introduction to Weidmüller Serial/Ethernet Converter
WEB Interface „Operating Modes TCP Client and UDP“
Page 17
Introduction to Weidmüller Serial/Ethernet Converter
WEB Interface „Operating Mode Pair Connection“
Page 18
Introduction to Weidmüller Serial/Ethernet Converter
WEB Interface „Event Type Settings“
Page 19
Introduction to Weidmüller Serial/Ethernet Converter
WEB Interface „Mail and SNMP Trap Settings“
Page 20
Introduction to Weidmüller Serial/Ethernet Converter
Thank you for your attention.
Questions?
Page 21
Introduction to Weidmüller Serial/Ethernet Converter