UR_710_Sales_PPT_v1_May_2013

Download Report

Transcript UR_710_Sales_PPT_v1_May_2013

GE Digital Energy
UR version 7.10 and URPlus version
1.90 Firmware release
Sales Presentation
May , 2013
By: Jose Mendez & JC Theron – Product Managers
V1.0
Content
• UR & URPlus Family Preview
• What is UR v710 and URPlus 1.90?
• Application Examples
• Key Market Drivers
• Ordering
• Q&A
UR Family Preview
Continuing to drive the protection and control
• Complete Platform supporting all
major protection applications
industry
• Modular platform: Reduce spare part cost and handling, swap modules among different
relay models, upgrade and expand hardware seamlessly, drastically reduce the impact of
hardware updates, common software tools for configuration, monitoring, diagnostics.
• Advanced Communications as a backbone of the platform with unique integration
flexibility
• Continued development in Ease of Use functionality
• IEC61850 on the entire family including Process Bus (Hardfiber)
• Diagnostics and Recording meeting international
requirements
• Security providing the tools for NERC CIP compliance
• 15 years of experience in the market
• More than 140000 units sold (2012)
• GE Multilin Committed to market and Customers
Proven State of the Art Protection and Control Systems
URPlus Family Preview
Completely Packaged Cost-Effective Solution for Protection, Control &
Automation
Plus
• D90
: Sub-cycle protection . . . Improved network stability & power system performance
• C90Plus: Bay Monitoring/control, SSOD, F/V, dF/dt and Fast Load Shed. . . easy to
design, expand
• B95Plus: Distributed Bus Protection . . . Up to 24 three-phase ccts with BF, reconfigurable
busses
• Powerful automation flexlogic & math engine . . .Improved substation automation capability in
terms of performance, cost & redundancy
• Color HMI & annunciator . . . very intuitive and easy-to-use visual tool to monitor & control the
bay/bus
. . . Soft labels, descriptive messages - eliminate LEDs and annunciator in
panels – 288 Alarms
• Powerful DFR capability . . . Eliminate the need for standalone DFRs and meet NERC requirement
• Enhanced metering functionality . . . Enhanced data logger and Synchrophasors as per IEEE
C37.118
• Outstanding communication capability . . . IEC61850, Dual IP redundancy, PRP . . .
• Pre-configured to use for 12 different configurations . . . ready to use
Covering All Major Protection and Control
Applications
Generation
Transmission
Distribution
Network & Control
Industrial
G60 – Generator
L90 - Line Differential
F60 – Complete Feeder
C30 – Controller
M60 – Motor
G30 – Generator &
Transformer
L60 - Phase Comparison
F35 - Multiple Feeder
N60 – Network Stability
and Synchrophasors
C90Plus – Fast Load
Shedding
L30 - Line Differential
T60 – Complete
Transformer
C60 – Breaker Controller
T35 - Transformer
C70 - Capacitor Bank
D90Plus – Sub-Cycle Distance
D60 - Line Distance
D30 - Backup Distance
B30 – Low Impedance Bus
B90 – Low Impedance Bus
B95Plus – Distributed Bus Bar
C90Plus – Bay Controller
and Small Signal
Oscillation
What is UR 7.10?
What is URPlus 1.90?
MDS WiYZTM
Product Summary UR
Multilin UR FW release v7.10
What is it?
UR FW version 7.10 release introduces specific new
communication and P&C capabilities to The UR Family
of devices.
New Communication functionality
- New network redundancy method as per the IEC
62439-3 PRP standard.
- Updated KEMA certification on the IEC61850 protocol
New P&C Functionalities
- In-zone transformer capabilities added to the L90 Line
Protection System
- CyberSentryTM UR Lvl 1 new settings for password
bypass
Value Proposition of UR FW version 7.10
• Increases network availability by enabling
independent failure mode and reducing failover
time to zero through implementation of IEC62439-3
“PRP”
• In-zone transformer capability in the L90 enables
decreasing the number of required CT banks by 1/3
and dedicated transformer relay for line differential
schemes with a power transformer in between
• New settings fields for bypassing user
authentication may speed up relays commissioning
and testing by 10% while keeping NERC/CIP
compliance
MDS WiYZTM
Product Summary URPlus
Multilin URPlus FW release v1.90
What is it?
URPlus FW version 1.90 release introduces specific new
communication and enhanced P&C capabilities to The
URPlus platform, excluding the B95Plus.
New Communication functionality
- New network redundancy method as per the IEC
62439-3 PRP standard.
- Updated KEMA certification on the IEC61850 protocol
Enhanced P&C Functionalities (C90Plus)
- Small Signal Oscillation Detection range is expanded
to cover a wider range of 0.08 to 1Hz with step
increments of 0.02Hz.
Value Proposition of URPlus FW version
1.90
• Increases network availability by enabling
independent failure mode and reducing failover time
to zero through implementation of IEC62439-3 “PRP”
• The SSOD (Small Signal Oscillation Detection)
range is expanded and refined to ensure a larger
area of system oscillations can be detected
Application Examples
Applications 1 – PRP (UR & URPlus)
MDS WiYZTM
•
Bumpless recovery of
communications
•
UR / URPlus
•
2 networks
•
2 ports
•
1 MAC address/IP
address
UR receives frames from
both networks
•
Discards 2nd frame
Transparent to switches
•
•
Increased network availability that reduces failover time to zero through
implementation of IEC62439-3 “PRP”
Application Example 1b – Complete Network
Redundancy (UR & URPlus)
LAN B –
Tree mode
LAN A –
Ring mode
SAN: Single
access node
DANP: Double
access node PRP
UR v6.xx or older
SAN
UR v7.10 or
higher
DANP
• Increased network availability (Independent failure mode)
• Chosen redundancy method for S/S automation networks based on 61850 (Ed. 2)
Application Example 1c – Programmable
Redundancy (UR)
Programmable Redundancy
- Eth Ports 2 & 3: Independent,
Failover or PRP redundancy
- Port 2 shares IP and MAC
addresses with Port 3
Eth Port 1
Eth Port 2
Eth Port 3
Applications 2 – L90 With In-zone Transformer
(UR)
MDS WiYZTM
In-zone Power Transformer Functionality
• Compensates remote terminal side phase shift
• Suitable for two and three line terminals
• Several Inrush Inhibit modes
Reduces the number of required CT banks by 1/3 and dedicated transformer relay for
line differential schemes with a power transformer in between
Applications 3 – CyberSentryTM (UR)
MDS WiYZTM
Standard Security UR
Standard
• Exceeds NERC CIP Password requirements (6
digits, alpha-numeric and special characters;
UR – 20 Digits, Alpha-numeric, special, capital
and small case characters)
• Access Level for Settings
• Access Level for Commands
• Dual Access control
• Remote Password, Local Password
• Security Audit Trial (6.0x)
FW 7.0x
CyberSentryTM UR
CyberSentryTM UR Level 1
• Exceeds NERC CIP Password requirements (6
digits, alpha-numeric and special characters;
UR – 20 Digits, Alpha-numeric, special, capital
and small case characters)
• RBAC with Five Roles
•Administrator
•Supervisor
•Engineer
•Operator
•Observer
• Enterprise authentication - Radius
•Enhanced Security Audit Trial plus Syslog
support
•Requires software option
Applications 3b – Password Bypass (UR)
Relay Commissioning and Testing
• Takes hours and requires frequent settings
change (at least once per tested element)
• Each setting change requires password
clearance
Remote Password
Bypass
Ethernet
• Submitting password may be slow depending
on the interface (front panel)
• Disabling passwords compromises final
settings
• Bypass requires
Administrator privileges
Local Password
Bypass
Front Panel, RS232
& RS485
User Activities FP
See and write independent
settings
See independent records
No access to CyberSentry
settings
User Activities Comms
Read and write settings files
Read record files
Write independent settings
FW upgrade
CybersSentry settings
Master/client Comm
Speeds up relays commissioning and testing by about 10% while keeping
NERC/CIP compliance
Applications 4 – Small Signal Oscillation
Detection (URPlus)
MDS WiYZTM
SSOD Settings Range Expanded in C90Plus
• Measure up to 6 analog inputs either local or remote signals at a fixed
measurement rate of 100 ms, and monitor for small power system oscillations
(Power or Frequency) Alarm and Trip stage
• Settings range expanded: 0.08 to 1 Hz with 0.02 Hz frequency step
Increases large power system stability by monitoring 6 inputs and allow system
separations upon detected instability
Multilin UR &10 Key Feature Descriptions
Key Feature
What it Means…
IEC62439-3 (PRP)
IEC 62439-3 is a standard that re-defines traditional Ethernet LAN redundancy by introducing
two redundancy methods: the Parallel Redundancy Protocol (PRP) and the High-Availability
Seamless Redundancy (HSR). UR and URplus devices support both PRP. When PRP is
implemented, both main and redundant Ethernet LANs become active, data packets from
UR/URPlus devices are tagged and transmitted over both LANs simultaneously. The device
receiving that data, will use the packet that comes in first and drop the second one. As a benefit,
if one LAN fails, there is no failover time causing delays. UR and URPlus implementation is based
on the latest version of the IEC62439-3 standard, which is dated Jul-2012.
“In-zone Transformer” for
line differential protection
The “In-zone transformer protection” functionality refers to the capability that GE’s Line
Differential Protection Systems, L30 and L90, have to accommodate a power transformer
between the line terminals so the current differential scheme looks over both, Line and power
transformer, without compromising protection performance. Magnitude and phase
compensation as well as second harmonic inhibit during transformer magnetizing inrush are
provided. This reduces the current differential scheme hardware requirements.
CyberSentryTM
This is a new GE’s Trade Mark that refers to all cyber security products an functionality
developed by GE Grid Automation. The “CyberSentry TM UR” is related to the set of features
inside UR devices. The UR v700 release introduced the first level of cyber security functionality,
called “CyberSentry UR Level 1”. This software option brings Radius (for remote authentication
and access management) and Syslog (standard data format for cyber security event reporting),
which are standard tools used by IT teams for Cyber Security applications. At the date of the
v7.00 release (Dec-2012) UR relays were the only one commercially-available P&C device with
this capabilities.
Market Drivers
Market Drivers
• IEC 62439-3 Standard on Industrial Network Redundancy
Industrial communication networks – High availability automation networks – Part
3: Parallel Redundancy Protocol (PRP) and High-availability Seamless
Redundancy (HSR)
First edition of the standard “1.0” is dated Feb-2010. A second edition “2.0” came up in
Jul-2012. The Ed. 2 PRP is not backward compatible with Ed. 1 PRP. This was the tradeoff to enable multi protocol nodes, which are nodes that can be work on both PRP and
HSR networks.
The standard has been highly promoted by ABB and Siemens as they hold patents on it.
PRP has been adopted by a small number of companies so far. However, we see how
the rapidly-growing interest on this protocol can make an important market driver in the
short term.
• North American Electric Reliability Corporation Critical
Infrastructure Protection (NERC CIP)
This term has become standard matter for all utility companies in North America as they
collaborate with the US Department of Energy (DOE) and the US Department of
Homeland Security (DHS).
“The DOE designated NERC as the electricity sector coordinator for critical infrastructure
protection. NERC serves as the Information Sharing and Analysis Center for the
electricity sector. NERC also works closely with the DHS and Public Safety Canada to
ensure the critical infrastructure protection functions are coordinated with the
governments of the United States and Canada”
http://www.nerc.com/
Ordering
CPU v710 – New Software Options
MDS WiYZTM
UR Soft Options
Description
List Price level
24
In-zone Transformer (L90)
$ 850.00
C0
PRP
$ 500.00
E0
IEEE 1588 + PRP
$ 750.00
F0
G0
PRP + CyberSentry UR Lvl
1
IEEE1588 + PRP +
CyberSentry UR Lvl 1
$ 1,475.00
$ 1,725.00
Qty of New Software Options
UR
172
B90
48
URPlus Soft
Options
Description
List Price level
A2
PRP
$ 500.00
Qty of New Software Options
UR
3
UR v710 Order Code – L90 Device
MDS WiYZTM
v710 Order Code – L90 Device cont.
MDS WiYZTM
URPlus v190 Order Code C90Plus Device
MDS WiYZTM
C90Plus Order Code
Interface
Front Panel
C90P- * * - * *
| |
| |
| |
| |
A |
| |
H |
| |
| |
|
** * * * - * * *
* * * * * ** *
Description
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Annunciator (standard)
| + HMI
|
| English (Standard)
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
X
P
O
|
|
|
|
|
S
E
L
C
A
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
01
02
03
04
A2
A3
A4
|
|
|
|
|
|
|
|
D
S
P
L
U
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S
D
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
X
S
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Hardware
|
|
|
|
|
|
|
|
|
|
Harsh Environment Coating
| |
X |
C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| None (Standard)
| Harsh Environment Conformal Coating
Language
E
Features
Protection
(AC module must for this option)
Automation
(protection or/ and automation)
Communications
(Option 02, 03 & 04 require communication module)
(Option A2, A3 & A4 require communication module)
Metering
DFR
Equipment Manager
None (standard)
Basic Protection + Protection Flexlogic
+ Small Signal Oscillation
Breaker Control + Synccheck
Breaker Control + Synccheck + Automation Controller (standard)
+ Basic Load Shedding elements
Fast Load Shedding Element (Controller) - Does not support AC, I/ O card optional, needs IEC61850
Fast Load Shedding Element (Aggregator) - Does not require AC or I/ O card, needs IEC61850
ModBus TCP/ IP + DNP 3.0 Serial + ModBus Serial (Standard)
+ IEC61850
+ IEC61850 + DNP 3.0 TCP/ IP
+ IEC61850 + IEC 60870-5-104
+ IEC61850 + PRP
+ IEC61850 + DNP 3.0 TCP/ IP + PRP
+ IEC61850 + IEC 60870-5-104 + PRP
No AC metering; data logger for non-metering data
Basic Metering (Standard)
+ Synchrophasors
+ Data Logger
+ Data Logger + Synchrophasors
Transient Recorder + Sequence Of Events (Standard)
+ Disturbance Recorder
No Equipment Manager
Circuit Breaker/ Communication Statistics + Battery Monitor (Standard)
Questions & Answers