Transcript Document

Asbestos Issue Prevents Fire Safety Upgrade
Kevin Thomas, Peter O’Connell, Peter Lewis, Steve Paskell, Martyn Walley
Jan’15
Introduction
• Fire Safety Audit
– Review to upgrade Historical Fire System within Supported
Living Accommodation
– None Compliance / Original Installation >30 Years
• Costing & Design Required for Replacement Hardwire
System
• Tender Completed & Contractor Appointed
• Full Asbestos Survey conducted on Property
– Start Delay due to Historical Issue Asbestos on site
• Solutions now required to be sought to maintain Fire Safety
at property should system fail
• Aico consulted for possible solutions due to previous
projects completed with Tai Calon
Solution
• Wireless / RF System
• Cost effective solution minimising site disruption
• Meet requirements of both Audit & H&S Report
• System Specification Design Drafted utilising new product providing
Integration
• In House Electrical Team – Quick, Cost Effective Solution, PPM
• Maintaining Coverage of New & Existing System
• Enforcing Stay Put Policy with Visual Aid within Property
• Futureproofing System
• DDA Compliance
• Warden Call Integration
• Duplex Communication with House Fire Panel
• Presentation conducted with Tai Calon & South Wales Fire & Rescue
Service Nov’14
• Internal & External buy in gained for System Installation
Ground Floor East
Zone 2
Zone 1
4 x Ei414
1 x Ei603TYCRF
3 x Ei605TYWRF
8 x SAB300R
8 x Ei428
First Floor West
Zone 3
1 x Ei603TYCRF
7 x Ei605TYWRF
8 x SAB300R
8 x Ei428
Product Requirements
Quantity
Product Code
Device
3
Ei603TYCRF
10Year Battery RadioLINK Optical Alarm
25
Ei605TYWRF
10Year Battery RadioLINK Heat Alarm
4
Ei414
Fire / CO Alarm Interface
1
Ei208WRF
RadioLINK CO Alarm
31
Ei428
RadioLINK Relay Module
31
SAB300
Strobe Light Red
Ei 414 – Integration with
Part 1 Panel
C
N/O
N/C
E
O
L
Either ‘+’ &’-’ from sounder
cct
Or volt free change over op
driven from Fire Panel
470
ohm
C
N/O
N/C
C
N/O
N/C
Zone 1 - 4
INSTALLATION NOTES;
- Each Ei414 to be wired as above per Zone
- Due to Limited Zone availability on the Panel, CO will sound
the Same Circuit as the Fire Notification
- Fire Alarm Trigger to the Ei414 can be either a Volt-free
change over or triggered from the Sounder Circuit
- Power Supply for the Ei414 can be either 230VAC or fed from
the Fire Panel
- The EOL resistor if not local can be substituted for the
outgoing circuitry
- The Fault Resistor 470 Ohm is indicative only as you will need
to verify this from the existing panel on site
4 x Ei414 units cabled individually to 4 Zone from the respective fire Panel
} 10-30VDC
Or
} 230VAC
Ei 414 – External
Functions
Functional
Keyswitch
Fire LED
Indicator
Service LED
Indicator
CO LED
Indicator
Power LED
Indicator
RF LED
Indicator
House Code
Button
Underside
Ei 414 – Key Switch
Function’s
OFF
ON
TEST
In the ‘OFF’ Position; all functions from the Ei414
are disabled – No Functional Relays will Operate
In the ‘ON’ Position; all functions from the Ei414
are enabled – Any activation via actual Smoke,
CO, Service or other optional Input will operate
the appropriate Relay and LED – Any manual
operation of a ‘Test’ button from a coded device
will NOT activate the relays or follow on
functions.
In the ‘TEST’ Position; all functions from the
Ei414 are enabled – Any activation via actual
Smoke, CO, Service or other optional Input will
operate the appropriate Relay and LED – Any
manual operation of a ‘Test’ button from a coded
device will also activate the relays or follow on
functions.
NOTE: The system MUST be house coded to differentiate between a Fire & CO RF Signal Type’s
Ei414 Live Schemes
• City of Swansea County Council
– Newly Specified Scheme for refit – currently out to
Tender
• Carmarthenshire County Council
– 3 Schemes – currently out to Tender
• Integration with Main Fire Panel & Deaf Alert Equipment
• Hafod HA / Hendre HA
– 5 New Schemes
• TAFF HA
– Red Sea House Warden Call Integration – Installed
Maintenance
• Daily Checks
– Scheme Manager Visual Inspection
• Weekly Checks
– Completed by Scheme Manager
• Sample Test on Fire Alarm Devices
• Log Book Completed
• Any Faults Recorded and reported to Tai Calon
• Monthly Checks
–
–
–
–
–
Tai Calon Competent Person Attendance
Fire Alarm Test
Emergency Lighting Test
Log Book & Work Sheets Completed
Any Faults Reported & Rectified Immediately
• Essential Stocks Held in house