Transcript Slide 1
New Control Box
(Cleaner) Design
RTU-MP
Controller
(Opt)
Command Center
Terminal Board
Gas Controller
Controls: Cooling
• High Pressure Switch
• Low Pressure Switch
• Indoor Fan Motor Overloads:
Linebreak
Thermik (pilot-circuit)
External circuit-breaker
Controls: Cooling
Control Transformer
75 va
3.2-A circuit breaker on transformer housing
CLO -- Accy or FIOP
CLO Connections
Controls: Heating
Integrated Gas Controller (IGC)
• IGC Inputs
• IGC Outputs
Diagnostic LED
Flame Sensor
Inducer Motor (CM)
Hall Effect
Indoor Blower (BM)
W1 Demand
Speed Sensor
IFO signal
Rollout Switch
Gas Valve
24-v Limit Switch
Sparker
Hall Effect
Ref: Honeywell
Hall Effect Sensor
Includes:
Current field
Integrated circuit
Transistor
Amplifier circuit
Hall Effect:
Pulse Output Signal
Speed Sensor Logic Criteria
Speed > 2400 RPM: Inducer Motor OK
Speed < 2000 RPM: Combustion Terminated
IGC Alarms
IGC Troubleshooting
IGC Error Codes:
From NSMM 2003 (SPP PPT) in HVACPartners
• Fault 2 – Limit Switch Open
If limit opens:
•
•
•
•
Gas valve and ignitor will be disable
Indoor blower will immediately energized.
Inducer shall remain energized
The indoor blower will turn off after the fan off
delay if “W” goes away.
• If limit closes again the fault will clear. If you
still have “W”, the gas valve still open and
re-igniton will occur.
IGC Service Reference Material
• NSMM 2003 SPP PPT IGC Alarms
• Technical Base / Hall Effect
• Service Training GT54-01
Heat Pump Defrost Board
New PN: HK32EA005
Thermostat demands for
1 or 2 stage Cooling
2 stage Heating
Emergency Heating
Defrost Control in Heating Mode
Based on RES HK32EA003
Controls: Heat Pump
• HPS High Pressure Switch
Opens 660PSI. Close 505PSI
• LPS Low Pressure Switch (A/C’s)
Opens 54PSI. Close 117PSI
• Liquid Line Loss-of-Charge (HP’s)
Opens 27PSI. Close 44PSI
• Freeze Protection Thermostat (FPS)
Opens 30F. Close 45F
Connects to new defrost board
Reversing Valve Operation
• No O or B signal required
• Energized in Cooling
• Reversing Valve does not shift mode in
Off cycle (No Dump)
Heat Pump Compressor Seq
Cooling Stage 1:
Reversing Valve 1 + Compressor
Cooling Stage 2: (2-comp models only)
Rev Valves 1+2 + Compressors 1+2
Heating Stage 1:
Compressor(s), No Reversing Valve
Heat Pump Electric Heat
Heating Stage 2
Concurrent with compressor(s)
Emergency Heat
Electric Heat WITHOUT compressors
Defrost Tempering
Heat Pump Defrost
Time-Temperature Sequence
1. Heat Run Time (30,60,90 or
120 mins) Factory 60 mins
2. Initiate if tube temperature
(DFT) low
3. Terminate when tube
temperature (DFT) rises or
defrost run period reaches
10 min
HH18SA261DFT Settings:
Open: 30F
Close: 80F
Defrost Speed-Up
• JMP17-JMP18
(flat/slot screwdriver)
• 1-5 secs: Speed-Up
(0.1 sec/min)
• 5-20 secs: Forced Defrost
Run to normal
termination or
30 secs minimum
Controls: Electric Heat
Accessory installation
1 or 2 stages
Fan housing limit switch (pilot, manual)
Element line-break
(or secondary contactor)
Heater control contactor(s)
Electric Heat: Single-Point Box
• Required with all electric heater installations
• Splice box with cover
• Power terminal block
• Tap conductors
• If FLA > 48-A:
Fuse blocks and 60-A fuses
SERVICE MANUAL
CONTROLS TERMINAL BOARD
CONVENIENCE OUTLETS
SMOKE DETECTORS
Installation Instructions
and
Service Manuals (SM)
The complete unit installation procedure
(rig and position through start-up) will
require reference to two (or more) technical
manuals.
Mechanical Installation: SI (II)
Configure/Start-up/Troubleshoot: SM
Service Manual:
LP Gas Conversion
Service Manual: Heat Pump Piping
Service Manual: Appendix
Specific Topic Tech Support
Smoke Detectors: Application Tip Cat# HKRNKA-1XA
(integration with building alarm systems)
PremierLink:
Form 33CS-58SI (configuration, t-s)
RTU-MP:
Form 48-50H-T-2T (configuration, t-s)
RTU-MP 3rd Party Integration Guide
Controls Terminal Board
aka
Light Commercial Terminal Board (LCTB)
Command Center Terminal Board
Carrier PN HK50AA049
UTEC PN CEPL130904-01
Array of terminal strips, housings and QCs
Contains NO LOGIC, no software
Controls Terminal Board
Gas
Controller
Provides:
- Clean connection
points
Phase
Monitor
OR
Fire / Remote
Shutdown
- Insures positive
connections
- Visual aid
OR
Smoke
Alarm
LPS
HPS
Controls Terminal Board
11 terminal strips:
J1-J2: Screw terminals
(thermostat wires)
0.046-in square pin
18 quick-connect
terminals
CTB: Jumpers
JMP7
• JMP1
Phase Monitor
• JMP2
Occupancy Control
• JMP3
Smoke Detector
Shutdown
• JMP4
Remote Shutdown
JMP6 JMP5
JMP1
JMP4
• JMP5, 6, 7 Heat Pump / Reheat
JMP3
JMP2
CTB: Actual vs Schematic View
2010 FIOPs
• Convenience Outlets
• Smoke Detectors
• CO2 Sensor (new)
Convenience Outlets
• Non-Powered
• Unit-Powered
• Neither is connected as delivered
• Hinged cover shipped loose
(in control box)
Convenience Outlets
Non-Powered:
Duplex GFCI
Weatherproof box
Hinged cover
Powered:
Duplex GFCI
Weatherproof box
Transformer
15-A fuse/switch
Hinged cover
Non-Powered CO
• Provide a separate 115-v 15-A power
supply and circuit disconnect from the
building
• Connect to the duplex outlet in the unit’s
splice box
• Install the weatherproof hinged cover
Powered CO
• Check local codes to determine if connecting the
convenience outlet transformer to the LINE side
of the unit disconnect is acceptable.
• If acceptable: Connect primary leads at the
power transformer together as required for unit
line voltage and connect to unit disconnect’s line
side terminals.
• If not acceptable: Connect primary leads at the
power transformer together as required for unit
line voltage and connect to unit disconnect’s
load side terminals.
• Install the weatherproof hinged cover.
Powered CO: Label
Powered CO:
Transformer Primary Connections
Weatherproof Hinged Cover
Powered Convenience Outlet:
Duty Cycle Limit
Smoke Detector FIOPs
•
•
•
•
Supply Air (on supply fan housing)
Return Air w/o Economizer
Return Air with Economizer
Combine S/A and R/A
R/A Smoke Detector is for VERTICAL only
“Some assembly required”
Smoke Detector Hardware
• Controller Module (one per unit)
• Sensor Module (one or two required)
• R/A application: Sensor tube
Smoke Detectors
R/A Sensor: Site Installation
Smoke Detector: LED
Smoke Detector:
Alarm Integration
• Application Tip Cat# HKRNKA-1XA
NEW FIOP:
Unit-Mounted CO2 Sensor
•
•
•
•
Same control logic as on accessory CO2
No LCD display on sensor
Requires PC access to configure
Software and cable available thru RCD
• Details to follow in full training program
2010 SRT FIOPs
•
•
•
•
•
•
•
•
•
Economizers (15th digit)
CO2 sensors (9th digit)
Smoke Detectors (9th digit)
Louvered Hail Guard (11th digit)
2-position Damper (15th digit)
Convenience Outlet (16th digit)
Thru-The-Base Connections (17th digit)
PremierLink (14th digit)
RTU-MP/Open (14th digit)
2010 SRT Accessories
•
•
•
•
•
•
•
•
•
•
•
•
Economizers & Roofcurbs
CO2 & Enthalpy sensors
Power Exhaust
Motormasters (low ambient) and winter start
LP Conversions
High Altitude Kits
2-pos damper / Man damper
Thru-The-Base
Louvered Hail Guards
Electric Heat / Single Point
Phase Monitor, Status switch, time guard
PremierLink
Economizer Plugs
• Command Center aka Low
Voltage Terminal Board (LVTB)
ECON 10pin Plug
• Used for all Economizers
SAT/OAT 4pin Plug
• Used for Econ 2 only
OCCUPANCY Terminals
• Used for Econ IV and 2-pos Damper
• 12-Pin Plug (male) – Unit Side
plug in Econ Section
Same plug and arrangement as old
units
• 12-Pin Plug (female) – Econ Side
Comes with specific FIOP or
Accessory
Small change on the Econ IV plug
Economizer Plugs
• Table to help Troubleshoot Economizer
wiring at the LVTB and the 12-pin plug
Economizer IV
• Electro-mechanical Unit Economizer
• Stand alone operation with Honeywell
W7212 controller.
• Compressor control runs through the W7212
If no econ then jumpers must be in 12-pin plug
for cooling to operate
• Actuator is 2-10 vdc pre-programmed ready
for W7212 output
• SAT in 12-pin plug (PL6)
Economizer IV
• Added occupancy control
The “N” terminal tells the controller when occupied
R-22 units had W7212 main power fed from the IFC and jumper to the N
terminal
410a units have main power fed from transformer, and IFC feeds the N
terminal trough the Occupancy terminals
So W7212 is powered up when the unit is, instead of only when the fan
is on
• Low Ambient Lockout
The “LA” switch is installed on the Y2 input to the controller
Part number HH18HA286, Contacts Open: 42°F ±5°F, and Contacts
Close: 57°F. ±5°F.
Below 42°F the second compressor will not run, econ will be stage one
and 1st comp is stage 2
• Power exhaust wire
Tan wire that is connected to 24Vac HOT, move to EF1
Add jumper from 24Vac HOT to EF
Connect other end of the tan wire to the tan wire in the PE Kit harness
Connect the Grey wire in the PE kit harness to the 24Vac COM terminal
Economizer IV
• CO2 Sensor
IAQ install, uses 24Vac (TR & TR1), and 0-10Vdc signal (AQ & AQ1), TR1 &
AQ1 are common
Demand Control Ventilation (DCV) is the only CO2 control available for Econ IV.
• DCV SET (POT) tells the controller at what input vdc from the IAQ sensor do we
want to start opening the damper
• DCV MAX (POT) tells the controller at what damper position do you want us to
stop opening for DCV
• The damper will modulate between the MIN POS (POT) and DCV MAX (POT)
settings proportional to the IAQ vdc input from DCV SET (POT) to 10Vdc
• Enthalpy
The Single Enthalpy sensor uses the same terminals as dry bulb (SO+ & SO).
For Differential Enthalpy, 2 enthalpy sensors required. One installed per
above and the other on terminals SR+ & SR (after removing the resistor).
Set the cross over POT to “D”
• Whichever is lower is the air used for cooling
• Remember O for outdoor and R for Return
Enthalpy sensors are HH57AC078 and Dry bulb are HH57AC074
• Power Exhaust (PE)
Terminals EF and EF1 are dry contacts and switch when the damper pos (in
Vdc) gets above the EXH SET (POT) setting (in vdc)
Economizer IV
Economizer 2
• Econ2
No controller, requires Plink or RTU-MP/open
Jumper wires in 12-pin plug for cooling
operation
Actuator is 2-10vdc pre-programmed
• 500 ohm resistor (pre-installed) required for 4-20
controller output
OAT in 12-pin plug (PL6)
Economizer 2
• CO2 Sensor
IAQ is installed on the specific controller via PL18 for FIOP and
direct to controller when field installed
DCV is set in the specific controller with a user interface.
• Enthalpy (only field installed)
Single or Differential control from the DDC controller
Uses the 2 loose Grey wires near unit’s 12 pin plug
Sensor wires run to the LVTB and then to DDC
• PE
Wires provided with the PE accessory have to be run to the
control box specifically to which ever DDC is installed
Switch one stage on and off based on damper position
Economizer 2
• Cooling jumpers must be in
harness for cooling to work
• Resistor must be between the
White signal wire and Black
actuator common
Actuator is 2-10v and
controllers output 4-20mA
• Enthalpy sensor power from
Actuator power
Switch signal using 2 grey
wires
• When troubleshooting
Read vdc across resistor
• Determine if it’s the actuator or
the controller
Shorting the actuator signal to
24VAC will drive it 100%, but
disconnect the actual signal
first
Spring return Closed
Direction switch set to same
direction as the spring return
2-Position Damper
• Opens to set position
whenever the fan is running
• To set position, set the screw
on the actuator face near the
shaft opening
Low Ambient
• Winter start Kit (CRWINSTR001A00)
3 minute timer relay to bypass low pressure switch
Field supply wires to tie into the LVTB, contact
across LPS and coil between HPS and compressor
contactor
Current Literature – IIK-CRWNTRAN01-01
• Motormaster I (32LT)
Wave Chopper, varies voltage to vary fan speed,
single phase approved motors, clip on sensor
May need to replace motor and capacitor. Usage
chart in literature.
Copper Coil Controller with sensor – 32LT900301
(230v), and 32LT900611 (460v)
MCHX coil controller with sensor – 32LT901247
(230v), and 32LT901647 (460v)
Tries to maintain 100 deg SCT, unit operation down
to -20 deg
Current Literature – IIK-32LT903-01
Low Ambient
• Motormaster II (CPLOWAMB001A00)
Fan cycle switch, on/off only, single phase motors, clip on sensor
Tries to maintain 130-110 high and 70-50 low SCT, unit operation
down to -20 deg
• Motormaster V
Kits CRLOWAMB030A00, 031A00, and 032A00 for specific
voltage
For use on three phase motors (48/50TC 14 and 50TCQ 12)
VFD, varies frequency (HZ) to vary fan speed, 3 phase approved
motors
Pressure sensor on liquid line, unit operation down to -20 deg
Gas Conversion Kits
Four kits for use with LP
and/or high altitude
applications. Each contain
25 spuds, 5 of 5 different
sizes.
Manifold Pressure
Natural Gas still 3.5-in.wc.
LP now 10.5-in.wc.
• High Altitude Conversion
Pick kit based on orifices needed
Use only spuds and High-Alt label in kit
Some spuds may have to be purchased separately
Literature contains conversion tables
Gas Conversion Kits
• LP Conversion
New, low pressure switch on supply side
• Closes at 10.2-in.wc. and opens at 7.2-in.wc.
• Gas piping included in kits
Kits include springs for gas valve to operate at higher pressure
Labels for LP and high alt (if needed)
Chose Kit based on orifices needed, some orifices may have
to be purchased separately
LPS
Controls
• PremierLink
FIOP or Accessory. If field installed make sure the CRPREMLK001A01
kit was also purchased. It has the harness for LVTB and the TB to install
other accessories to.
• RTU-MP
FIOP only and only available through mid-2009
Overview training PES0810302 on partners
Controller training PES0803241 on Partners
Other information and tools on HVACpartners (CCN Support – MultiProtocol Controls)
• RTU-Open
Only FIOP until 3 Qtr 2009, then the retrofit should be available
Replaces the RTU-MP, direct replacement
Improved control and improved networking
Fixes battery memory with flash memory, otherwise hardware is the
same
RTU-Open Support
Open release – FIOP around June 2009
– Accy around July 2009
• Contact Equipment Product support for:
Specific base unit operation or problems
Questions/problems with the Controller or how it controls the unit,
if it was Factory installed (FIOP)
Questions/problems with how the FIOP was installed
Controller operation, start-up, configuration, and troubleshooting
questions
• Contact CCN support for:
Network Integration and Communication questions or problems
Questions/problems with the controller if it was field installed
(accessory)
Questions/problems with the accessory installation
Controller operation, start-up, configuration, and troubleshooting
questions
What’s Next
• Bynum Training program 4th Qtr
Questions???