EMS+Lecture+27
Download
Report
Transcript EMS+Lecture+27
Active power
The fact that power is always positive reveals that it always
flows from the generator to the resistor.
This is one of the basic properties of active power: although it
pulsates between zero and max. it never changes direction.
The average power is clearly midway between 2P and zero, and
so its value is P = 2EI/2 = EI watts.
That is precisely the power indicated by the wattmeter.
The generator is an active source and the resistor is an active
load.
The symbol for active power is P and the unit is the watt (W).
The kilowatt (kW) and megawatt (MW) are frequently used.
Lecture 27
Electro Mechanical System
1
Reactive power
The resistor is replaced by a reactor X . As a result, current I
lags 90° behind the voltage E
we can draw the waveforms of E and I & by multiplying their
instantaneous values, we obtain curve of instantaneous power
Positive waves correspond to instantaneous power delivered
by the generator to the reactor and the negative waves
represent power delivered from the reactor to the generator
Duration of each wave corresponds to one quarter of a cycle
Frequency of power wave is therefore twice the line frequency
Power that surges back and forth is called reactive power (Q)
To distinguish this power from active power, another unit is
used the var. Its multiples are kilovar (kvar) and megavar (Mvar)
Lecture 27
Electro Mechanical System
2
Reactive load & reactive source
Reactive power involves real power that
oscillates back and forth between two devices
over a transmission line.
Consequently, it is impossible to say whether
the power originates at one end of the line or
the other.
It is useful to assume that some devices
generate reactive power while others absorb it.
In other words, some devices behave like
reactive sources and others like reactive loads.
A reactor is considered to be a reactive load
that absorbs reactive power.
Lecture 27
Electro Mechanical System
3
Example
A reactor having an inductive reactance of 4 Ω is connected to the
terminals of a 120 V ac generator.
a) Calculate the value of the current in the reactor
IL = E / XL = 120V / 4 Ω = 30 A
b) Calculate the power associated with the reactor
Q = EI = 120 X 30 = 3600 var = 3.6 kvar
c) Calculate the power associated with the ac generator
Because the reactor absorbs 3.6 kvar of reactance power, the ac
generator must be supplying it. Consequently, the generator is a
source of reactive power: it delivers 3.6 kvar.
d) Draw the phasor diagram for the circuit
The phasor diagram show that current I, lags 90° behind voltage E
Lecture 27
Electro Mechanical System
4
Capacitor and reactive power
If we add capacitor having a reactance of 4 Ω to the circuit.
capacitor current IC = 120 V/4Ω = 30A & leads the voltage by 90°
The vector sum of IL and IC is zero and so the ac generator is
no longer supplying any power at all to the circuit.
The current in the reactor has not changed; consequently, it
continues to absorb 30 A X 120 V = 3.6 kvar of reactive power.
Where is this reactive power coming from? It can only come
from the capacitor, which acts as a source of reactive power.
Q = Elc = 120 V X 30 A = 3600 var = 3.6 kvar
It means a capacitor is a source of reactive power. It acts as a
reactive power source whenever it is part of a sine-wave-based,
steady-state circuit.
Lecture 27
Electro Mechanical System
5
Capacitor and reactive power
Remove the reactor from the circuit. Capacitor is now alone.
It still carries a current of 30 A, leading the voltage E by 90°
Capacitor acts as a source of reactive power, delivering 3.6 kvar
Where does this power go? Capacitor delivers it to the generator
How, can a passive device(capacitor) produce any power?
Reactive power really represents energy, like a pendulum, swings
back and forth without ever doing any useful work
The capacitor acts as a temporary energy-storing device
Instead of storing magnetic energy, it stores electrostatic energy
If we connect a varmeter, it will give a negative reading of
EI = – 3600 var, showing that reactive power is indeed flowing
from the capacitor to the generator.
Lecture 27
Electro Mechanical System
6
Example
An ac generator is connected to a group of R, L, C circuit elements
carrying, the currents shown. Calculate the active and reactive power
associated with the generator.
The two resistors absorb active power given by
P = I2R =(16.122 X 2) + (142 X 4) = 784 + 520 = 1304 W
The 3 Ω reactor absorbs reactive power:
QL = I2XL = 142 X 3 = 588 var
The 3.5 Ω capacitor generates reactive power:
QC=I2Xc = 202 X 3.5 = 1400 var
R, L, C circuit generates a net reactive power of 1400 – 588 = 812 var
In conclusion, the ac generator is a source of active power (1304 W)
and a receiver of reactive power (812 var).
Lecture 27
Electro Mechanical System
7
Distinction between active and reactive power
Active and reactive power, are separate quantities and one
cannot be converted into the other.
Both place a burden on the transmission line.
Active power eventually produces a tangible result (heat,
mechanical power, light, etc.)
Reactive power represents power that oscillates back and forth.
All ac inductive devices such as magnets, transformers, ballasts,
and induction motors, absorb reactive power because one
component of the current they draw lags 90° behind the voltage.
The reactive power plays a very important role because it
produces the ac magnetic field in these devices.
A building, shopping center, or city may be considered to be a
huge active/reactive load connected to an electric utility system.
Load centers contain thousands of electromagnetic devices that
draw both reactive power (to sustain their magnetic fields) and
active power (to do the useful work).
Lecture 27
Electro Mechanical System
8
Combined active & reactive loads: apparent power
Loads that absorb active power P and reactive power Q is made
up of a resistance and an inductive reactance.
Resistor draws a current Ip, while the reactor draws a current Iq
Consequently, Ip is in phase with E while Iq lags 90° behind.
Resultant line current I lags behind E by an angle . I I p2 I q2
If we connect a wattmeter and a varmeter , the readings will both
be positive, indicating P = EIp watts and Q = EIq vars
An ammeter will indicate a current of I amperes, so the power
supplied to the load should be equal to EI watts.
This is incorrect because the power is composed of an active
component (watts) and a reactive component (vars). For this
reason the product EI is called apparent power, symbol is S.
Apparent power is expressed in voltamperes. (kVA) & (MVA).
Lecture 27
Electro Mechanical System
9