DCS and DSS Status

Download Report

Transcript DCS and DSS Status

HV System Failures in Operation
German Martinez
April 28, 2010
G. Martinez – HCAL HV Primary PS Review
1
HV System
HCAL HV System Components:
• 20 Crates (18 for HPDs + 2 for HF PMT)
• 20 Primary Power Supplies
• 20 Control Modules
• 20 Status panels
• 106 HPD HV Modules (4HV+4BV Channels)
• 8 HF HV Modules (3 Cath+3Dyn7+3Dyn8 Channels)
HV Failure Statistics (2008-2010):
• 11 Primary Power Supplies
• 6 Control Modules
• 10 HV Modules
April 28, 2010
G. Martinez – HCAL HV Primary PS Review
2
Last Failures
Starting Point:
THU 18.FEB.10 Lubomir returns to Sophia, all HV modules repaired, 7 HV Primary PS spares available
Elog Incidents:
•
FRI 19.FEB.10 13:36:48
HV Module of HO1M12 replaced due to an Interlock problem.
•
MON 22.FEB.10 13:36:48
The power supply of the HV crate of HO0M failed and was replaced by an spare unit.
•
MON 26.FEB.10
01:40:42 We lost communication to all HV in HBM HV Communication module for HBMa replacement
07:50:09 We lost communication to all HV in HBM. Last night we lost the HV Controller of HBMA, now the Controller of
HBMB died. (Serial killer?) The bad unit was replaced.
•
FRI 09.APR.10 07:39:57
The power supply of the HV crate of HEPc went into short, eventually tripping the breaker of the whole rack. Despite a strong
burning smell no DSS smoke alert was triggerred. Unit has been replaced.
•
TUE 13.APR.10 08:53:02
Problem fixed. The power supply of the HEPc HV Crate died (looks like an epidemy...)and was replaced…
•
MON 19.APR.10 14:00:57
The Primary PS of the HV crate of HEPc died and was replaced. (Third casualty on the same crate in a month... we probably
have a serial killer there) …
•
MON 19.APR.10 18:07:45
The HV crate of HEPc (with all its modules) was replaced due to persistent Primary PS Failures. …
April 28, 2010
G. Martinez – HCAL HV Primary PS Review
3
HV Schematics
Main Failure Cause
4
HV Morgue
Wire fuse blowed
April 28, 2010
G. Martinez – HCAL HV Primary PS Review
5
Current Status
•
HV Primary Power Supply Failures found in Mosfet
Power transistors used to generate Vpp.
•
4 Modules already repaired
•
Resettable Fused installed to protect the circuit.
•
Ultimate reason of the failures not identified yet.
April 28, 2010
G. Martinez – HCAL HV Primary PS Review
6