PermAlert ESP

Download Report

Transcript PermAlert ESP


Liquid Leak Detection/Location Systems
for piping, raised floors, semiconductor
tools, containment piping, fuel systems
and other applications
Company Profile



PermAlert is part of Perma-Pipe the largest
prefabricated – preinsulated pipe
manufacturer in the US
PAL-AT Leak Detection was introduced in
1988 and was the reason for founding
PermAlert ESP
Sales Volume of the parent corporation
(MFRI) is about US $178 million with over
500 employees worldwide
PAL-AT Cable Systems and
LiquidWatch Probe Systems


PAL-AT uses coaxial cables and probes to
monitor for liquid leakage. The system can
detect and locate leaks, breaks and shorts on
the sensor cable as well as probe activations.
LiquidWatch is a probe monitoring system
and can monitor up to 64 probes from a
single panel. The probes are monitored for
activation, breaks and shorts.
Time Domain Reflectometry
PAL-AT

TDR is a cable measuring technology
related to sonar and radar. By sending
energy pulses down the center
conductor of a coaxial cable and
measuring the reflected energy to the
outer braid a map can be stored of the
cable and monitored for change. When
change occurs the type of alarm and its
location is displayed on the panel.
TDR Trace of Dry Cable
TDR Trace with Leak Detected
TDR Trace of System with Wet Cable
TDR Trace showing Growing Leak
Map 3 Response
Second Leak Detected
Monitoring with Liquid on the Cable
Break Detected
Short Detected
Probe Activated
PAL-AT Panels





AT20C - Monitoring up to 2,000’ (600 m) on a single
cable
AT50C - Monitoring up to 5,000’ (1500 m) equivalent
length on a single cable
AT20K - Monitoring up to 7,500’ (2500 m) equivalent
length per cable with a maximum of two cables
AT40K - Monitoring up to 5,000’ (1500m) equivalent
length per cable with a maximum of eight cables
AT80K - Monitoring up to 7,500’ (2500 m) equivalent
length per cable with a maximum of eight cables
Types of Cable
PAL-AT



AGW Gold Sensor cable for use in
containment piping, trenches, trays
and subfloors
AGT Gold Sensor cable for use
in subfloors and trays. More
sensitive than AGW
TFH Sensor cable for detecting
hydrocarbons and solvents while
ignoring water
TFH
TFH
Types of Probes
PAL-AT and LiquidWatch
PHL/PWS Solid state probes for
hydrocarbon and conductive liquids
 PSTV/PTHL/PFS Float switches for
high/low level
 PT10 (PAL-AT) Probe integrators and
PA-10 (LiquidWatch) Probe Adaptors for
dry contacts

LiquidWatch

LiquidWatch has two basic panels. The
LW64 is for use in normal classified
probe locations while the LW64IS
provides a UL Listed System for
monitoring in Class 1, Division 1 Groups
C & D locations. The basic panel
monitors up to eight probes with
modules being added for additional
probe requirements.
Applications





Raised Floors - Data Centers, ISPs, Clean Rooms
Telecommunication, Semiconductor, Office Bldgs
Pharmaceutical
Piping - Containment piping, single wall piping,
hydrocarbon piping, waste drains
Trenches and Trays - Under wet benches, piping
and equipment
Generators, Electrical Switch Gear and
Transformers for hydrocarbon leakage or water
seepage
What ever needs liquid leakage detection that a
probe or sensor cable can be used
Palcom Software
PAL-AT and LiquidWatch

Palcom allows remote control of up to
254 panels with the ability to review
TDR traces, review the history of each
unit and to pull down a Cad drawing for
each system for location of leaks,
breaks, shorts or probe activation's.
Archive Data


























POWER LOST AT 8985 ON 18/95 RESTORED AT 0853 ON 5/8
YEAR CHANGED FROM 29 TO 98 AT 0853 ON 5/8
CABLE 1 SETUP, WITH LENGTH OF 514 FEET AT 0921 ON 5/8
LEAK DETECTED IN CABLE 3 at 225 FEET AT 1157 ON 5/8
ALARM ON CABLE 3 SILENCED AT 1157 ON 5/8
CABLE 4 SETUP, WITH LENGTH OF 538 FEET AT 1208 ON 5/8
SECURITY CODE 1 ENTERED, LEVEL 250 AT 1210 ON 5/8
NEW CABLE 4 REFERENCE, STORED AS MAP 1 AT 1210 ON 5/8
CABLE 4 MONITORING ON, MAP 1 AT 1210 ON 5/8/98
CABLE 4 RETURNED TO NORMAL AT 1211 ON 5/8
SECURITY CODE 1 ENTERED, LEVEL 250 AT 1217 ON 5/8
CABLE 3 SETUP, WITH LENGTH OF 833 FEET AT 1217 ON 5/8
NEW CABLE 3 REFERENCE, STORED AS MAP 1 AT 1217 ON 5/8
CABLE 3 MONITORING ON, MAP 1 AT 1217 ON 5/8/98
CABLE 3 RETURNED TO NORMAL AT 1218 ON 5/8
SECURITY CODE 1 ENTERED, LEVEL 250 AT 1225 ON 5/8
CABLE 2 SETUP, WITH LENGTH OF 815 FEET AT 1225 ON 5/8
NEW CABLE 2 REFERENCE, STORED AS MAP 1 AT 1225 ON 5/8
CABLE 2 MONITORING ON, MAP 1 AT 1225 ON 5/8/98
CABLE 2 RETURNED TO NORMAL AT 1226 ON 5/8
SECURITY CODE 1 ENTERED, LEVEL 250 AT 1231 ON 5/8
CABLE 1 SETUP, WITH LENGTH OF 514 FEET AT 1231 ON 5/8
NEW CABLE 1 REFERENCE, STORED AS MAP 1 AT 1231 ON 5/8
CABLE 1 MONITORING ON, MAP 1 AT 1231 ON 5/8/98
CABLE 1 RETURNED TO NORMAL AT 1232 ON 5/8
**********End of Archives**********
Benefits of PermAlert’s PAL-AT











Wet cable startup
Multiple Leak location capability
Location of Breaks
Detection of Shorts versus Leaks
Not susceptible to contamination from dirt/dust, etc.
Archive History Data
UL Listed, FM Approved, CE Approval available
Class 1 Div 1 Groups C & D Sensor Circuits
Up to 8 circuits and 7,500’ (2500 m) per circuit
Corrosion resistant sensor cables
Different cable types on the same circuit
EPA third party tested
Benefits of LiquidWatch






Modular in design allowing for easy expansion
Monitoring of probes for activation and the
leader cable for breaks and shorts
History log of events
UL Listed for Class 1 Div 1, Groups C & D
locations
Different probe types
Probe adaptor to allow interface of any dry
contact probe device
Questions and Answer Period