Introduction
Combined humidity and temperature sensing
The polymer capacitance humidity sensor is not
affected by condensation, fog, high humidity, or
contaminants
www.hvac.vn
General Specifications
Accuracy, RH:
RHP-2XXX ±2% 10-90% RH @ 25°C
RHP-3XXX ±3% 20-80% RH @ 25°C
RHP-5XXX ±5% 20-80% RH @ 25°C
Accuracy, Thermistor Temp Sensor: ±0.2°C @
25°C (±0.36°F @ 77°F)
Accuracy, RTD Temp Sensor: DIN Class B; ±0.3°C
@ 0°C (±0.54°F @ 32°F)
Output signal: 4 to 20 mA/ 0 to 10V @ 5 mA max
www.hvac.vn
General Specifications
RH Sensor: Capacitance polymer
Temperature Sensor:
Types 1, 2, 3: Solid state band gap
Curves A, B, C: Thermistor
Curves D, E: Platinum RTD DIN 385
Enclosure: Duct mount: PBT; OSA: Polycarbonate.
Enclosure Rating: NEMA 4X (IP66) for OSA mount
only
Agency Approvals: CE
www.hvac.vn
Relative Humidity
Relative humidity (RH) is the amount of water
vapor in a volume of air as a proportion of the
amount of water vapor the same volume of air
will hold at saturation (100% RH) at any given
temperature
www.hvac.vn
Capacitance Polymer
Humidity Sensors
Works similar to a plate capacitor
Consists of hygroscopic polymer between two
electrodes
One of the electrodes is a sensing surface
Porous to allow water to pass in and out of polymer
Keeps out condensation and contaminants
As polymer absorbs water, its dielectric constant
changes, creating changes in capacitance proportional
to changes in relative humidity
www.hvac.vn
Features
Sensor
RH range: 0-100%
15 second response time
Sensor recovers 100% from saturation
Factory calibrated, field replaceable sensors available
www.hvac.vn
Features
Wall mount
Optional remote or integral LCD display
Universal current/voltage output for
humidity/temp.
Resistive temp. Outputs available
Replaceable sensors
Well ventilated for more accurate measurements
www.hvac.vn
Features
Duct mount
Weather resistant PBT construction
Dual temp./RH output
Optional display reads both temp. And RH
Field replaceable sensor cap of filter
Twist-off cover, no screws
Available with membrane or sintered filter
www.hvac.vn
Features
Outside air
NEMA 4X / IP66 housing
Field replaceable sensor
Multiple knock outs for conduit
Screws anchored inside lid top
Available w/ SS sintered filter or radiation shield
www.hvac.vn
Applications
Wall mount humidity/temp.
Mounted in a room – sends signal to controller on vav system
to adjust amount of air flow supplied to the space
www.hvac.vn
Applications
Duct mount humidity/temp.
Monitors the humidity of the air after a humidifier and the
humidity in return duct for economizer applications.
www.hvac.vn
Applications
Outside air humidity/temp.
Used to determine if additional hot or cold water is needed
to feed AHU