RTU Magnum Overview - Micro Control Systems
Download
Report
Transcript RTU Magnum Overview - Micro Control Systems
Roof Top Unit Overview
(MAGNUM)
Revision- 4/10/2017
Visit us at www.mcscontrols.com
RTU
Magnum
Joins the Magnum family of software:
- HVAC (and LWC)
- CENT
- REFR
MCS-CONNECT
All Magnum software is supported by
a common MCS-CONNECT for
Communications and MCS-Config
to build the units profile.
All software indicates the current
state of the system.
MCS-CONFIG
RTU
Magnum Purpose
Purpose is to provide flexible control to roof top units
that provide heating, cooling and dehumidification to a
building.
Plus the necessary ventilation control of fans and dampers,
to insure proper air quality and building pressure.
Plus the necessary ventilation control of fans and dampers,
to insure proper air quality and building pressure.
MCS
RTU Magnum
• Supports up to 80 Relay Outputs
• Supports up to 112 Sensors Inputs
• Supports up 28 Analog Outputs
• Supports 255 Set points
• Supports storage of last 100 alarms (plus extended info for
safety alarms)
• Supports 1008 History Samples for all inputs & outputs
RTU
Magnum Safeties
-
All HVAC safeties & preventive action are active.
-
Individual safeties are provided for each fan, damper, etc.
-
Smoke & fire safeties which also provide the ability to purge
the building,
-
Clogged filter safeties
-
Energy Recovery Wheel safeties
RTU
Magnum Modes
Modes of operation
- Ventilation
- Cooling
- Heating
- Dehumidification
Screen Shows Ventilation Settings
in MCS-CONFIG
The sensor control of the modes are selected
independently based upon associated set points or
a digital input can be selected to ‘Force’ that mode
to be active if it is on.
The control sensor for ‘Switch to Cooling/Heating’
will keep the unit in the Ventilation Only mode or
enable the other modes.
RTU
Magnum Occupied/Unoccupied
-
Occupied can be indicated based on a schedule
or digital input
-
Unoccupied can be over ridden with an override
indicator
Status:
- Occupied, set point values.
- Unoccupied, set point values adjusted with
night set back
- Override, same as occupied
RTU
Magnum Cooling Mode
This mode is based upon the existing HVAC control functions to
control compressors and their safeties. The controlling sensor is
selected in the General Info screen.
- 20 circuits
- Various types of Compressors & refrigerant types
- Etc. same as HVAC.
Also added a Digital Scroll type of Analog Output. If
selected less than 10% will provide 0 voltage output. 10
to 100% will be proportional between 1.5 to 5.0 voltage
output.
RTU
Magnum Heating Mode
This mode provides either 1 or multiple steps of heating.
The controlling sensor is independent from other modes.
The types of heating can be:
- Direct Fire (up to 6 valves)
- Modulating Gas (up to 6 valves)
- Modulating Hot Water
- Split Manifold (up to 6 valves)
- (above types of heating support Auxiliary Heating)
- Modulating SCR (VFD & up to 30 steps)
- On/Off Hot Water (up to 30 steps)
- Staged Gas (up to 30 steps)
- Staged Electric (up to 30 steps)
If multiple steps, current step must be at maximum
capacity before next step is allow to start.
RTU
Magnum Condenser Info
In this screen the following is specified:
- Condenser Type, this will be the same options as HVAC.
RTU
Magnum Dehumidification Mode
Area is too moist, humidity needs to be reduced.
In this mode a fixed number of cooling stages are indicated.
Only cooling stages that have reheat capability are allowed on.
Cooling will reduce the humidity in the air. If heating is required the cooling
stages reheat will be used.
The types of reheat are:
- Modulating
- Fixed Step (number will be provided)
- None
A Return Air Bypass Damper can also be controlled.
If additional heating is required the heating specified for the heat mode can
be used, this is an option.
RTU
Magnum Humidification Mode
Area is too dry, need to increase humidity.
When the system is NOT in cooling mode, humidity can be increase by
modulating a Steam/Mist valve.
The control sensor is specified and based upon a set point the
associated analog VFD will be modulated.
RTU
Magnum Ventilation Information
Individual control can be specified for:
-
Building PSI
-
Supply Fan
-
Exhaust Fan
-
Return Fan
-
Outside Air Damper
-
Exhaust Damper
-
Relief Damper
-
Energy Recovery Wheel
RTU
Magnum Ventilation Fan Options
-
Building PSI: control can be either Direct, Reverse, or Not Used
Supply Fan: (control on Building Static PSI)
- Always On ( applies only if Occupied)
- Cycle (on if heating or cooling needed)
- Set up as modulating or fixed on/off
- Can have 1 or 2 fans
There is a pre-delay, post delay on the supply fan and once on a
delay before heating or cooling steps can be turned on.
Exhaust Fan: (control on Duct Static PSI)
- Set up as modulating or fixed on/off
Return Fan: (control opposite of supply fan)
- Set up as modulating or fixed on/off
RTU
Magnum Ventilation Damper Options
Outside Air Damper:
Set up as modulating or fixed on/off
Control can be based upon:
- Local minimum fresh air requirement
- Level of CO2
- CFM (air movement)
- Building Static PSI
- Will provide economizer cooling as first stage of cooling if ambient
temperature is less than the set point value to allow free cooling.
Report on Fault Detection & Diagnostics (based upon California
Energy Commission requirements)
RTU
Magnum Energy Recovery Wheel
Purpose is to capture potential lost energy by using the leaving air
temperature to precondition the incoming fresh air.
During the warmer seasons, the system pre-cools and pre-heats in
the cooler seasons.
The Energy Recovery wheel relay can be active when the supply fan
is on and the system is not in economizer (free cooling) state.
A Bypass Damper can also be controlled
When on for a given period of time a defrost cycle will be initiated if
the outside temperature is less than the defrost temperature.
MCS RTU Magnum
Review MCS-Configuration with RTU set up.