Varitector VSSC – surge protection for I/O
Surge Protection ....for Power and I/O
SPD II & SPD III
VARITECTOR
VSSC
VARITECTOR
VSPC
PLC
Power protection
Imax = 40kA (8/20μs)
Pluggable arrestor module
Local status indicator
Contact for remote
status alarm
UL 1449 Edition 3
•
•
•
•
•
Signal protection
Signal protection
Imax = 20kA (8/20μs)
Imax = 20kA (8/20μs)
Pluggable arrestor module
High density / low cost
Local status indicator
4 or 6-terminal models
Group connection for
Local status indicator
remote status alarm
(6 terminal option)
UL 497B
UL 497B
•
•
•
•
•
•
•
•
•
•
VSSC ..............surge protection for I/O
What’s in a name ?
Varitector = Variable Protector
SSC = Signal Screw Connection
What is new?
The 20+ year old DKU Series is being replaced
with a new pluggable style/construction with more
functionality.
VARITECTOR
VSSC
What approvals are there?
UL is available now
Class & Division and ATEX are planned
for 2012.
DK Series
What is the availability?
The new range includes more than 100 different articles.
These are in stock – either in Richmond (high runners) or Detmold.
Where is I&C Surge protection used?
 Industries where plant / signals are outside, e.g….
 Sewage treatment plants
 Water treatment and pumping stations
 Chemical plants
 Refineries
 Customers are:
 Municipalities (+ their SIs)
 Plant end-users (above)
 Package plant OEMs (separators, dryers, coolers, effluent
treatment, chemical dosing, pumping)
VARITECTOR SSC – Surge Protection for C&I
Easy to use:
 Direct PE-contact by fit on the rail
Screw connection:
Torx-slot screw
Cross section for 0.5mm² to 6mm²
High tightening torque (0.8Nm)
Two in one:
Terminal block with integrated
surge protection
Space saving in the cabinet:
only 6.2mm width per loop
More than 100 variants:
 current loop and binary signals
 for 5V, 12V, 24V, 48V and 60V
 single components inside, e.g. MOV
 Protection for data signals
Approved to UL497B:
 High impulse current up to
20kA (8/20μs) and up to 2,5kA
(10/350) to PE
4 pole & 6 pole options:
 VSSC4 is for basic functions
 VSSC6 includes TR and LD options
Basic functions
Basic functions – VSSC6 TR SL LD
24V
0V
Conductivity
Probe (Switch)
DC Power
Supply
VSSC .......v. MTL
 MTL Surge Technologies: SD Series
- Bad:
• No LED indicator option for status
• No marking space available
• Only 6 pole format
• Wire size up to 14AWG/2,5 mm²
• LP = $154.35
(VSSC6 TR FG CL 24VAC/DC 0.5A = $60.49)
- Good:
• Direct PE- Connection
• Fuse / disconnect option for loop testing
• Function with colour code
• Wide approvals e.g. CSA, UL, ATEX,
• Installation size : 7 mm x 99 mm x 100 mm
Selection ............... step 1
What information do we need to be able to specify a product? Here is a guide.
S
Signal type…?
Analog, status, fieldbus, telecom
N
Nominal voltage….?
12V, 24V, 48V, 60V, 120V, 230V……
I
Indication of status needed…?
Locally and /or Remotely
F
Frequency….?
Fast-changing signals, Fieldbus or Telecom ?
F
Floating or Ground referenced…? Process measurement signals are often floating.
Think….. S.N.I.F.F…. !
VSSC .........Typical customer questions
“I need surge protectors for 24V lines / signal lines / measurement loops / PLC inputs”
“……… or for bus / RS485 / RS 422 / RS232 / telephone networks”
“I’m looking for over-voltage / lightning / transient protectors for …..control loops”
“I need some of your MTL / SD modules….. ”
“……… or DK 4 U, DK 5 U, DK 6 U …or MCZ OVP”
Types of process I/O signals
Exc
Type K
Thermocouple
+
Tx
Frequency
Input, 3-wire
-
2-wire
transmitter
Pwr
RTD
3-wire
Digital
Input
Tx
0v
Pwr +
Pwr -
Analog
Actuator
Tx
4-wire
transmitter
Digital
Actuator
Sig +
3-wire
transmitter
Pot.
Frequency
Input, 2-wire
+
Sig +
0v
Terminal sized surge protection
 Slim line terminal for surge protection
 4 and 6AN screw type connection
80 mm
 Surge discharge via PE rail contact
 Double disconnect lever for test function
 Accessories:
 End plate 1,5 mm
88 mm
 Frame for bigger parts 6,2mm
Breite: 6,2 mm
 Standard marker WS 10/5 middle /
DEK5 / SnapMark
55 mm
74 mm
Mechanical Data
Screw:
Torque:
Connection points
Cross-section max.
Stripping length
DIN Rail
PE-Connection
Protection class
Housing
UL
Torx / slot
0,8 Nm
4AN
solid - 6mm²
flexible - 4 mm²
10 mm
TS35
to TS 35
IP20
Wemid black
V0
Electrical Data
Discharge current Imax
Voltage (Nom.)
Current (series load)
Discharge via PE contact
Monitoring (only for 6AN)
Protection circuit for…
up to 20kA
5, 12, 24, 48 and 60V
up to 26A
up to 20kA
2 LED's
Analogue signal
Digital signal
Temperature signal
Floating Ground System
2 stage (GDT und TVS)
1 stage (GDT, MOV or TVS - parts)
Varitector SSC 6AN
Monitoring by LED:
 Signal indication
Easy to use:
 Direct PE-contact by fit on the rail
Easy to use for test functions:
 two disconnect lever to open the signal signal circuit
Easy handling for PE connection:
 Two additional connection points
for PE
Competition overview
Weidmüller
MTL
Phoenix
Dehn&Söhne
OBO
Varitector SSC
Type SD
Type TT
Type DCO
Type MDP
6 AN
screw
Yes
Yes
5AN tension clamp
4AN screw
Yes
No
5 AN tension clamp
8 AN screw
Yes
No
No
No
7mm
6,2mm
6mm
8,1mm
Connection
4 and 6 AN with
Slot-Torx screw
PE-Contact to TS35
Yes
Easy to identify in the Yes, by different
cabinet
colours on the top
marker
Width
6,2mm
Disconnection lever
Yes for 6AN
Yes
Yes
No
No
Compatible Design
TERMOPTO and
other terminals
No
UK Series
No
No
Monitoring
LED @ 6AN
No
No
No
No
Amount of variants
ATEX variants
107 products
18 products 5, 91 products from 5, 15 products from 12,
from 5, 12, 24,48
24, 48V
24, 48 and 60V
24, 48 and 60
up to 60V
6 products
4 products
2 products
1 product
9 products from 5,
24 and 48V
none
Floating ground
products
Impulse current max.
Yes
No
Yes
Yes
No
20kA
10kA
10kA
10kA
5kA
Price position
100%
120%
100%
110%
110%
VSSC ..........v. Phoenix Contact
 TERMITRAB: TT-SLKK5
- Bad:
• Bad look-and-feel, if the products are assembled on the rail
• Worse connection to the DIN Rail
• Lateral off-set (S-Form) a single unit can not disassembled in a group of terminals
- Good:
• Compact size
• Approval: cRUus
Installation size: 8 mm x 67,5 mm x 66,5 mm
VSSC ..........v. Phoenix Contact
 TERMITRAP: TT-EX(I)-24DC
- Bad:
• The prints are not readable
- Good:
• Direct PE-Connection
• Approvals: cULus, Cl1 Div 2, KEMA 99ATEX5687X
• High torque possible
Installation size : 6,2 mm x 79,6 mm x 54,6 mm
VSSC ........v. Dehn & Söhne
 DEHNconnect: RK…
- Bad:
• Individual marking only on the top of the product
• Simple PE-Contact
• Terminal made by Wago
• Only tension clamp
• No approvals
• Only one ATEX-terminal: RK Ex (i)  DCO RK MD EX
- Good:
• Good readable print
• Installation size : 6 mm x 90 mm x 57 mm
VSSC .......v. OBO Bettermann
 MDP
- Bad:
• Individual marking only on the top of the product
• Negative look-and-feel of the terminal
• Only tension clamp
• No approvals
• Only 3 parts: 5V, 24V, 48V
• Big installation size
- Good:
• Test under life with test unit “Life Control”
• 8 AN terminal
• Installation size : 8 mm x 100 mm x 99 mm
VSSC .......v. MTL
 MTL Surge Technologies: SD Series
- Bad:
• No LED indicator option for status
• No marking space available
• Only 6 pole format
• Wire size up to 14AWG/2,5 mm²
• LP = $154.35
(VSSC6 TR FG CL 24VAC/DC 0.5A = $60.49)
- Good:
• Direct PE- Connection
• Fuse / disconnect option for loop testing
• Function with colour code
• Wide approvals e.g. CSA, UL, ATEX,
• Installation size : 7 mm x 99 mm x 100 mm