Transcript document

Louis T. Fiore
FIRE ALARM TRANSMISSION METHODS
“NFPA 72 2013”
March 14, 2012
Methods in NFPA 72 Chapter 26

DACT

One-Way Private Radio

Two-Way Radio

Performance Based Technologies
DACT
“Digital Alarm Communicator Transmitter”
First defined in NFPA 71
NFPA 72





The next edition (2013) will see DACT and a
second technology (not two phone lines).
The current (and perhaps final) version of
NFPA 72-2013 requires a 6 hr DACT test
rather than 24 hrs.
The 2016 Edition will probably “sunset”
DACT altogether.
Two-Way radio, Private One-Way Radio,
Digital Cellular and IP will survive as your
only communications alternatives.
NITNAM Procedure
26.6.3.1
Performance Based Technologies


Single Path
60 second polling or check-in
Multiple Paths
6 hour polling or check-in on each side
Digital Cellular
IP/Internet
Current Version (2010):
26.6.3.2.1.4 Transmission Channels.
(A) A system employing a DACT shall employ one
telephone line (number). In addition, one of the
following transmission means shall be employed:
(1) A second telephone line (number)
(2) A cellular telephone connection
(3) A one-way radio system
(4) A one-way private radio alarm system
(5) A private microwave radio system
(6) A two-way RF multiplex system
(7) A transmission means complying with new
technologies section
VoIP
Issues for Alarms with VoIP
1.
2.
3.
4.
Pass alarm DACT signal formats in an
undistorted fashion
Ensure Line Seizure is not compromised
The ability to provide for our control
panels to "see” a telephone line equivalent
(voltage and dialtone)
VoIP and cable/ISP hardware should have
sufficient backup power
MFVN in NFPA 72-2010
Definition:
3.3.141
Manage and maintain their network to ensure service quality
and reliability
Provide a service that is functionally equivalent to traditional
analog phone service (dialing, dial plan, and loop voltage
treatment),
Provide real-time transmission of voice signals that carry
alarm system formats unchanged,
Provide both professional installation and subscriber
information …….which preserves primary line seizure for
alarm system interconnection, and
Have disaster recovery plans to address both individual
customer outages and widespread events of a catastrophic
nature, including network power restoration equivalent to
traditional landline telephone services.
One Way Private Radio


AES-Intellinet
AlarmNet A
Two-Way RF Multiplex
• AlarmNet M
• AAGARD
• HolmesNet
Transmission Channels
(A) A system employing a DACT shall employ one telephone
line (number).
In addition, one of the following transmission means shall be
employed:
(1) A one-way private radio alarm system
(2) A two-way RF multiplex system
(3) A transmission means complying with 26.6.3.1
(performance-based technologies)
Exception: Where access to two technologies listed above is
not available at the protected premises, with the approval
of the authority having jurisdiction, a telephone line
(number) shall be permitted to be used as the second
transmission means.
26.6.3 Communications Methods.
The communications methods used to transmit
signals to supervising stations shall meet the
requirements of 26.6.3.1 for performance-based
technologies, or 26.6.3.2 (Digital Alarm
Communicator Systems) or 26.6.3.3 (Radio
Systems) for prescriptive-based technologies.
26.6.3.1 Performance-Based Technologies.
26.6.3.1.1 Conformance. Communications
methods operating on principles different from
specific methods covered by this chapter shall be
permitted to be installed if they conform to the
performance requirements of this section and to
all other applicable requirements of this Code.
26.6.3.1.5 Single Communications Path.
Unless prohibited by the enforcing authority, governing laws,
codes, or standards, a single transmission path shall be permitted,
and the path shall be supervised at an interval of not more than
60 minutes. A failure of the path shall be annunciated at the
supervising station within not more than 60 minutes. The failure
to complete a signal transmission shall be annunciated at the
protected premises in accordance with 10.12.
26.6.3.1.6 Multiple Communications Paths.
If multiple transmission paths are used, the following
requirements shall be met:
(1) Each path shall be supervised within not more than 6 hours.
(2) The failure of any path of a multi-path system shall be
annunciated at the supervising station within not more than 6
hours.
(3) The failure to complete a signal transmission shall be
annunciated at the protected premises in accordance with 10.12.
26.6.3.1.7 Single Technology. A single technology shall be
permitted to be used to create the multiple paths provided the
requirements of 26.6.3.1.6(1) through 26.6.3.1.6(3).
26.6.3.1.5 Single Communications Path.
Unless prohibited by the enforcing
authority, governing laws, codes, or
standards, a single transmission path shall
be permitted, and the path shall be
supervised at an interval of not more than
60 minutes. A failure of the path shall be
annunciated at the supervising station
within not more than 60 minutes. The
failure to complete a signal transmission
shall be annunciated at the protected
premises in accordance with 10.12.
26.6.3.1.6 Multiple Communications Paths. If
multiple transmission paths are used, the
following requirements shall be met:
(1) Each path shall be supervised within not more
than 6 hours.
(2) The failure of any path of a multi-path system
shall be annunciated at the supervising station
within not more than 6 hours.
(3) The failure to complete a signal transmission
shall be annunciated at the protected premises in
accordance with 10.12.
26.6.3.1.7 Single Technology. A
single technology shall be permitted
to be used to create the multiple
paths provided the requirements of
26.6.3.1.6(1) through 26.6.3.1.6(3).
Questions?
Thank you!