NICET TRAINING FIRE ALARM TECHNICIAN
Download
Report
Transcript NICET TRAINING FIRE ALARM TECHNICIAN
Denver Fire Alarm
Test
FUNDAMENTAL, POWER SUPPLIES, CIRCUITS,
INSPECTIONS, TESTING and MAINTENANCE
• In the absence of a specific performance based design
criteria, smooth ceiling smoke detector spacing shall be a
nominal _________ feet.
• 30 feet 17.7.3.2.3.1
• Signals with carbon monoxide detectors transmitted to a
fire alarm system shall be permitted to be
_____________________________ signals.
• Supervisory
23.8.4.7
• When a supervising station receives a trouble signal they
must dispatch personnel with in ________ hours to
initiate maintenance, if necessary.
• 4 hours 26.3.7.4
• Complete records of all signals received by a supervising
station shall be kept for a period of ________________.
• 1 year 26.4.6.1
• A type public alarm system shall be required where the
number of all alarms required to be retransmitted exceeds
_____________ per year.
• 2500 27.5.2.1.2
STOP STOP STOP
STOP STOP
STOP> End of Timed
Questions
• In the absence of a specific performance based design
criteria, smooth ceiling smoke detector spacing shall be a
nominal _________ feet.
• 30 feet 17.7.3.2.3.1
• Signals with carbon monoxide detectors transmitted to a
fire alarm system shall be permitted to be
_____________________________ signals.
• Supervisory
23.8.4.7
• When a supervising station receives a trouble signal they
must dispatch personnel with in ________ hours to
initiate maintenance, if necessary.
• 4 hours 26.3.7.4
• Complete records of all signals received by a supervising
station shall be kept for a period of ________________.
• 1 year 26.4.6.1
• A type public alarm system shall be required where the
number of all alarms required to be retransmitted exceeds
_____________ per year.
• 2500 27.5.2.1.2
• A means to disconnect all circuit conductors inside a
building protected by a public alarm system shall be
provided but access shall be allowed to the building
owner and the authority having jurisdiction. True or False
• False AHJ only
27.7.2.2.1
• Central Station Operator Qualifications
• Must be qualified
• Factory trained, certification acceptable to AHJ, locally
licensed or other training approved by AHJ
• Power Supplies
• All power supplies shall be installed according to NEC
• Fire alarm shall have two reliable power supplies
• Primary
• Secondary
10.5
• Uninterruptable Power Supply (UPS)
• Must meet NFPA 111
• Must be supplied by dedicated branch circuit
• UPS failure shall result in a trouble signal
10.5.4 NEW
• Primary Power Supply
• Must be one of the following
• Light and power service circuit
• Engine driven generator when trained person is always on duty
• Engine driven generator for cogeneration with power service
• Location of disconnecting means identified at control unit
• Dedicated branch circuit, marked red and FIRE ALARM
CIRCUIT
10.5.5
• Disconnecting means accessible to authorized personnel
only
• Overcurrent protection shall be provided for ungrounded
conductors
10.5.5
• Secondary Power Supply Fire Alarm Systems
• Storage battery or automatic starting generator
• Four hour battery charge
• Secondary circuits proving power to control unit and are not
integral shall be protected against physical damage
10.5.6.1
• Secondary Power Supply for Supervising Station
• Must be one of the following:
• Storage Batteries
• Automatic starting generator with four hour storage battery
• Dedicated branch circuit of multiple generators
10.5.6.2
• Capacity of Secondary Power Supply
• 24 hours in quiescent load
• At the end of that period capable of 5 minutes of alarm
operation
• Batteries shall include 20% safety margin
• Supervising stations, 24 hours of normal operation
10.5.6.3
• Continuity of Power Supplies
• Protected Premises power to secondary supply shall
automatically switch within 10 seconds
• Supervising Station power to secondary supply shall
automatically switch within 60 seconds
• No interruption or delay in signals shall exceed 10 seconds
• UPS are allowed to provide power for transfer
• Positive means to disconnect input and output provided so that
power is continuous
10.5.7
• Power supplies for remotely located alarm systems shall
meet all the previous requirements.
10.5.8
• Storage Batteries
•
•
•
•
•
•
•
Marked with the month and year of manufacture
Mounted securely and protected from damage
Gasses not affect other equipment
Installed according to NEC
Location identified at control unit unless they are adjacent
Must be recharged within 48 hours of discharge
Supervising stations: Must maintain spare parts so that batteries
can be restored or replaced prior to losing ½ their capacity
• Charging circuits supervised and initiate trouble signal upon
failure
10.5.9
• Generators
• Installed in an approved manner
• According to NEC Article 700 and
• NFPA 110, Type 10, Class 24, Level 1 system for protected
premises
• NFPA 110, Type 60, Class 24, Level 2 system for
supervising station automatic starting generators
• NFPA 110, Type M, Class 24, Level system for supervising
station manual starting generators
10.5.10
• Fuel
• Store adequate supply for 6 months of required testing plus
the 24 hr/ 5 minute rule
• If a reliable source of supply is available with a 2 hour notice, a
12 hour supply of fuel stored is allowed
10.5.10.6
• Signal Priority
• ECS signals can be elevated by evaluation through risk
analysis to precedence over all other signals
• Fire alarm signals
• Emergency Mass Notification Signals
• Hold Up Alarms
• Supervisory Signals
• Trouble Signals
10.6
• Distinctive Signals
• Priority alarms, fire alarms, supervisory and trouble signals
shall be distinctive and descriptively annunciated.
• Audible signals can not sound like any similar device used
in the same area.
• Carbon Monoxide Sensors for example
• At the control unit this can be done by the same audible
alarm with a supplemental textual device
10.7
• ECS Priority Signals
• Must be visible indication automatically with in 10
seconds at the fire alarm control unit or other designated
location
10.8
• Fire Alarm Signals
• Fire alarm signals shall be unique
• Notification appliances shall activate within 10 seconds of
an initiating device activation
• Coded alarm signal shall consist of 3 rounds of 3 impulses
10.9
• Deactivation of Signals
• Alarms
• Visual and audible must be simultaneously deactivated
• Key operated or equivalent protection
• Subsequent activation of another circuit initiating device must
restart alarm
• If left in off position must initiate a trouble signal
10.10
• Deactivation of Supervisory Signal
• Coded: 2 complete rounds
• Restoral at least 1 complete round
• Self restoring and Latching supervisory signals indicated
within 90 seconds
• Silencing allowed by authorized personnel
• Visual continues
• Left in off position shall cause a trouble signal
10.11
• Trouble Signals
•
•
•
•
•
•
Trouble signals shall be indicated with in 200 seconds
Intermittent signal must sound at least every 10 seconds
Can be silenced
Must resound every 24 hours
Sound until manually silenced
Retransmitted to supervisory station
10.12
• Performance and Limitations
• Equipment shall be able to operate at 85% if nameplate
voltage
• Equipment shall be able to operate at 110% of nameplate
voltage
• Equipment shall operate at temperatures of 32 – 120
degrees F.
• Equipment shall be able to operate at 85% humidity and 86
degrees F.
10.14
• Automatic smoke detectors must be provided at the
location of all control equipment, NAC power extenders
and supervising station transmitting equipment
• For ceilings less 15’ or less, located on a ceiling or wall
with in 21 feet of control unit
• For ceilings over 15’, located on the wall above the
control unit within 6’ of top
10.15