Transcript ABB The
Protection - Overload
What do we mean by a fault?
Overload
Operating condition in an electrically undamaged circuit which
causes an current to flow in excess of the full load current
Example: Starting condition during DOL start
© Abb Control Ltd - 1
If this type of fault continues indefinitely because of an anomolous
operating condition., damage begins to occur creating……….
ABB
Protection – Short Circuit
What do we mean by a fault?
Short Circuit
© Abb Control Ltd - 2
Operating condition in an electrically damaged circuit where there is an
accidental or intentional connection by a relatively low resistance
between two points of a circuit which are normally at different
voltages
This type of fault can generate high current flows, arcing and fire if
not cleared quickly
ABB
© ABB Control Ltd - 3
01-04-06 -
An explanation of the terms
BS EN 60947 standard
for Industrial Switchgear
&
BS EN60898 for
Domestic Circuit
Breakera
ABB
© Abb Control Ltd - 4
The ‘British Standards’
BS EN 60947 (Industrial switchgear)
BS EN 60898 (Domestic circuit breakers)
ABB
© Abb Control Ltd - 5
BS EN 60947 Which section ?
EN 60947-2 for Circuit breakers
EN 60947-3 for Switches
EN 60947- 4-1 for Motor protection
EN 60947-6-1 for Auto changeover
ABB
© Abb Control Ltd - 6
BS EN60947-2
Icu - Ultimate Short Circuit breaking capacity
O - 3 min - CO ALL at full fault level
Breaker must be intact and be able to pass insulation resistance test at the
end of the test
Breaker does not need to able to carry full rated current continuously
without overheating after test
Ics - Rated duty Short Circuit Breaking capacity
Often expressed as a % of Icu
O - 3 min - CO - 3min - CO
The test may be at fault level lower than Icu value
Breaker must be intact and be able to pass insulation resistance test at the
end of the test
Breaker MUST be able to carry full rated current continuously without
overheating after test
Note:
ABB
O test begins with breaker closed before current applied
CO test requires breaker to close onto fault current
BS EN60947-2
© Abb Control Ltd - 7
Icw - Rated Short-time Withstand current
Preferred rating - 1 sec
Limits are
12x In or 5kA whichever is greater for In <= 2500A
30kA for In > 2500A
Utilisation Category
A type - Instantanous type
B type - Selective short circuit
B type MUST have withstand (Icw)rating defined
Icm Rated duty Short Circuit Making Capacity
ABB
© Abb Control Ltd - 8
BS EN60947-2
It is recommended that circuit breakers are examined for
contact and arc chute damage after every fault
clearance
Icu/Ics values mean breakers can be put back into
temporary service after fault clearance
ABB
© Abb Control Ltd - 9
Definitiions within BE EN 60947
In – Nominal current rating
Iu – Rated uninterrupted current
Ue – Operational Voltage
ABB
AC/DC Distribution
Which mcb curve?
© Abb Control Ltd - 10
BS EN 60898 B type
General purpose lighting & power
Magnetic setting 3 - 5x In
BS EN 60898 C type
Industrial application with high surges
Magnetic setting 5 - 10x In
Different devices for DC applications above 60V
ABB