Modular Inverter Series INV

Download Report

Transcript Modular Inverter Series INV

Modular Inverter
1
Modular Inverter Series UNV
[HF Technology 1st Generation]
UNV-F1.2
-
UNV-F1.8
–
UNV-F2.5
–
UNV-F3.3
–
UNV-F5.0
Available input
voltages of:
48V DC
1200VA(960W)
1800VA(1440W)
2500VA(2000W)
3300VA(2640W)
5000VA(4000W)
60V DC
110V DC
Available output
voltages of:
230V AC / 50Hz
| --------------------------------------------------------- 19“ x 3U ------------------------------------------------------------ |
2
Modular Inverter Series UNV
UNV-F
Technical information
Input:
Output
power
1,2kVA = 960W
1,8kVA = 1,44kW
2,5kVA = 2,0kW
3,3kVA = 2,64kW
5,0kVA = 4,0kW
Vin
48V
60V
110V
48V
60V
110V
48V
60V
110V
48V
60V
110V
48V
60V
110V
Ain
22,8A
18,2A
9,9A
34,2A
27,4A
14,8A
47,3A
37,9A
20,4A
62,5A
60,5A
26,6A
94,7A
74,9A
39,9A
Output: 230V, 50 or 60Hz (programmable), single phase
It is possible to build three phase system, each phase with numbers inverter in parallel.
Max. number of inverter working in parallel: 16 pieces
3
Modular Inverter Series UNV
UNV-F
Special features
>> Electrical isolation between input and output
>> Input over/under voltage shutdown
>> Hot-plug-in able
>> Ready for paralleling (no fixed master) >>Current sharing based on decrease line of max. 1% for the output voltage
>> Load balance max +/- 5% INom >> n+x redundancy
>> Ability to build three phase systems with a number of inverters per phase
>> Output overload and short circuit proof
>> Temperature controlled fan cooling (font-to-rear airflow)
>> Digital display for output voltage / current and adjustment of internal default settings
>> Crest factor < 3
>> Can bus interface for communication with static bypass switch and/or monitoring unit
>> Working temperature: -20°C up to +45°C
>> Power factor range: 0,5 ind. - 1 – 0,5 cap.
>> Ability for stand-alone operation
>> Designed to operate together with static bypass switches
>> overload capability 130% for 30sec
4
Modular Inverter Series UNV
UNV-F
Signalling
High input voltage
Output voltage O.K.
Operation
Relay signalling:
Dry contact for common alarm.
Contact rating: 8A@250VAC, 8A@30VDC
Display for output voltage (top line, 3 signs) and
output current (second line, 3 signs)
flashing: ventilator fault
Constant : high internal temperature
Common alarm
Overload
Low input voltage
5
Modular Inverter Series UNV
UNV-F
Mounting (mounting kit):
View into a system (left side)
Plugs for inverter UNV-F
Slide rails
6
Modular Inverter Series UNV
UNV-F
Needed / available accessories
- mounting kit
>> article number: 880-MEC-MKT.01 (except
UNV48-5,0F)
>> article number: 880-MEC-MKT.02 (only UNV485,0F)
- socket (standard: part of delivery scope)
>> article number: 880-MEC-MKT.21 (except
UNV48-5,0F)
>> article number: 880-MEC-MKT.22 (only
UNV48-5,0F)
7
Modular Inverter Series INV
[HF Technology 2nd Generation]
INV211
-
INV216
-
INV245x
(x=still in development)
Available input
voltages of:
24V DC
48V DC
1100W(1375VA)
1600W(2000VA)
4500W(5600VA)
(24V only)
60V DC
110V DC
220V DC
Available output
voltages of:
230V AC / 50Hz
|-------------------- 1/4-19“ x 2U ------------------- | ---------------------- 19“ x 2U ------------------------- |
8
Modular Inverter Series INV
INV 222
(INV215@24VDC)
Technical information
Input:
Output
power
INV211 (Still in
development)
1,1kW /
1,37kVA
INV216
1,6kW /
2,0kVA
available
INV 222 (Still in development)
1,8kW / 2,2kVA
Vnom
24V
48V
48V
60V
110V
220V
48V
60V
110V
220V
Inom
67,4A
46,8A
46,8A
37,5A
20,8A
10,4A
131,1A
104,9A
58,3A
29,2A
Output: 230V, 50Hz, single phase
Max. number of inverter working in parallel: 8 pieces
9
INV245 (still in development)
4,5kW / 5,6kVA
Modular Inverter Series INV
INV 222
(INV215@24VDC)
Technical information
Signalling:
Operation: input voltage within nominal value
Output voltage within nominal value
Common alarm
Remote signalling:
Dry contact for common alarm. Contact rating 60V/0,1A
10
Modular Inverter Series INV
INV 222
(INV215@24VDC)
Special features
>> Electrical isolation between input and output
>> Input over/under voltage shutdown
>> Hot-plug-in able
>> Ready for paralleling (no fixed master) >>Current sharing based on decrease line of max. 1% for the output voltage
>> Load balance max +/- 10% INom >> n+x redundancy
>> Output overload and short circuit proof
>> Temperature controlled fan cooling (font-to-rear airflow)
>> Crest factor < 3
>> Can bus interface for communication with static bypass switch and/or monitoring unit
>> Working temperature: -20°C up to +55°C
>> Power factor range: 0,5 ind. - 1 – 0,5 cap.
>> Designed to operate together with static bypass switches
>> Overload capability 130% for 5sec; 110% for 1min
11
Modular Inverter Series INV
INV 222
(INV215@24VDC)
Mounting:
Front view of 19” rack
Mounting angles
Static bypass switch STS207
Three slots for inverter INV222
12
Modular Inverter Series
INV216
INV 222
Needed / available accessories
>> 19” rack, 2 HU, including backplane for 3x inverter + 1x STS
>> article number: 502-222-315.LV (for DC input 24-60V)
>> article number: 502-222-315.HV (for DC input 108-216V)
>> 19” rack, 2HU, with backplane for 4x inverter (without STS)
>> article number: 502-222-405.LV (for nominal DC voltages 24-60V)
>> article number: 502-222-405.HV (for nominal DC voltages 108-216V)
>> Cover plates to cover not used inverter slot, 2HU, RAL7035
>> article number: 881-MEC-BPL.02.21.B
13
Modular Inverter Series PWS
PWS-1.0
-
PWS-2.5
-
PWS-5.0
Available input
voltages of:
1000VA(800W)
1800VA(1440W)
2500VA(2000W)
3300VA(2640W)
5000VA(4000W)
24V DC
110V DC
220V DC
Available output
voltages of:
230V AC / 50Hz
Other voltages /
frequencies on
request
Available mechanical design:
19” 4/5U or wall
cabinet
14
Modular Inverter Series PWS
PWS
Technical information
Input:
Output
power
1,0kVA = 800W
2,5kVA = 2,0kW
5,0kVA = 4,0kW
Vin
24V
110V
220V
24V
110V
220V
Ain
38,8A
8,2A
4,1A
96,6A
20,4A
10,2A
24V not
available
110V
220V
39,9A
20A
Output: 230V, 50 single phase
It is possible to get special output voltages / frequencies
Max. number of inverter working in parallel: 12 pieces
15
Modular Inverter Series PWS
PWS
Special features
>> Electrical isolation between input and output
>> Input over/under voltage shutdown
>> Available as 19” rack or as wall cabinet
>> Ready for paralleling (no fixed master) >>Current sharing based on decrease line of max. 1% for the output voltage
>> Load balance max +/- 10% INom >> n+x redundancy
>> Crest factor < 2,5
>> Output overload and short circuit proof
>> Temperature controlled fan cooling (font-to-rear airflow)
>> Overload capability 160% for 1min; 130% for 10min
>> Special output voltages / frequencies on request
>> Working temperature: -20°C up to +45°C
>> Power factor range: 0 ind. - 1 – 0 cap.
>> Analogue measurement instruments for output voltage / current
>> Ability for stand-alone operation
>> Designed to operate together with static bypass switches
16
Modular Inverter Series PWS
PWS
Signalling
High input voltage
Output voltage O.K.
Operation
Relay signalling:
Dry contact for common alarm.
Contact rating: 5A@250VAC, 5A@30VDC
High internal temperature
Common alarm
Failure
Low input voltage
17
Modular Inverter Series PWS
PWS
Needed / available accessories
- mounting kit
>> article number: 880-MEC-MKT.03
18
Modular Static Switches
19
Modular Static Switches
Series STS
STS207
7kVA@230V AC
-
STS114
still in development
14.5kVA@230V AC
STS230
still in development
30kVA@230V AC
-
STS350
still in development
50kVA(1/3phase)
|---- 1/4-19“ x 2U ---- | ------------------ 19“ x 1U ------------------ | ---------------------------------------------- 19“ x 3U -------------------------------------------- |
20
Modular Static Switches
Series STS
STS
Technical information
Input:
- Special versions for nominal input voltage of 24-60VDC and 108-216VDC.
- 1x 230VAC bypass mains
- 1x 230VAC inverter output
Output:
- 1x 230VAC, in phase with bypass input
21
Modular Static Switches
Series STS
STS
Signalling
Load on Inverter
Load on Mains
Bypass input
Inverter input
Operation
Remote signalling:
Optocoupler for common alarm, Relay on
backplane:
Max. contact rating: 30W / 50VA; 60VDC /
125VAC; 1ADC / 1AAC
Display of 4 lines
Synchron bus in phase with bypass mains input
Common alarm
Ethernet Interface
CAN-bus Interface
23
Modular Static Switches
Series STS
STS
Special features
>> Hot-plug-in able
>> Display for all main operating parameters, settings and measuring values
>> Ethernet interface for remote connection via SNMP protocol or WEB-Browser
>> Minimized synchronisation time (because of digital PLL) >> It is possible to use diesel gensets as bypass mains
>> Transfer time < 4ms
>> Monitoring of both incoming sources according to voltage level, frequency and synchronisation
>> Temperature controlled fan cooling (font-to-rear airflow)
>> Free programmable operation mode (inverter priority or bypass priority)
>> Overload capability 1000% for 10ms
>> CAN bus interface
24
Modular Static Switches
Series STS
STS
Needed / available accessories
>> 19” rack, 2 HU, including backplane for 3x inverter + 1x STS
>> article number: 502-216-315.LV (for DC input 24-60V)
>> article number: 502-216-315.HV (for DC input 110-220V)
>> Manual bypass switches (recommended by ELTEK VALERE INDUSTRIAL, please have a look on separate
description)
>> article number: 881-880-HBS-7.0 (max. 7,0kVA)
>> article number: 881-880-HBS-14.5 (max. 14,5kVA)
>> article number: 881-880-HBS-30.0 (max. 50kVA)
25
Modular Static Switches
Series STS
[1st Generation]
UNB-5.0
-
UNB-12.5
–
UNB-23.0
–
UNB-30.0
–
UNB-40.0
Available DC input
voltages of:
24 DC
5000VA
12500VA
23000VA
30000VA
40000VA
48/60V DC
110V DC
220V DC
| --------------------------------------------------------- 19“ x 3U ------------------------------------------------------------ |
26
Static Switches Series UNB
UNB
Technical information
Input:
DC input: Special version for 24VDC, 48/60VDC, 110VDC or 220VDC
AC bypass input:
230VAC, 50/60 Hz, single phase
also available
3x 230/400VAC, 50Hz, three phase with loadable neutral
AC inverter input:
230VAC, 50/60Hz, single phase
also available
3x 230/400VAC, 50Hz, three phase with loadable neutral
Output: 230V, 50/60Hz, single phase, in phase with bypass input
also available
3x 230/400VAC, 50/60 Hz, three phase with loadable neutral, in phase with bypass input
27
Free programmable operation mode (inverter to load / bypass to load as standard)
Static Switches Series UNB
UNB
Signalling
Second source (substitute source)
Priority source
Operation
Relay signalling:
Dry contact for common alarm.
Contact rating: 8A@230VAC, 8A@24VDC
Display of 4 lines
Common alarm
Load on Mains
28
Load on Inverter
Synchron bus in phase with bypass mains input
Static Switches Series UNB
UNB
Special features
>> Hot-plug-in able
>> Display for all main operating parameters, settings and measuring values
>> Optional three phase versions
>> Designed for AC systems consisting of UNV- or PWS inverters
>> Transfer time < 4ms
>> Monitoring of both incoming sources according to voltage level, frequency and synchronisation
>> Temperature controlled fan cooling (font-to-rear airflow)
>> Free programmable operation mode (inverter priority or bypass priority)
>> Overload capability 1000% for 10ms
>> CAN bus interface
29
Static Switches Series UNB
UNB
Needed / available accessories
>> mounting kit
>> article number: 880-MEC-MKT.01 (5.0 to 12.5kVA)
>> article number: 880-MEC-MKT.03 (> 23.0kVA)
>> Manual bypass switches (recommended by ELTEK VALERE INDUSTRIAL, please have a look on separate
description)
>> article number: 881-880-HBS-7.0 (max. 7,0kVA)
>> article number: 881-880-HBS-14.5 (max. 14,5kVA)
>> article number: 881-880-HBS-30.0 (max. 50kVA)
Needed / available accessories
>> socket (standard: part of delivery scope)
>> article number: 880-MEC-MKT.21
30
Other applicable products?
Inverter with built-in static switch
UNV-UE series
Input: 48/60VDC
Output: 230V/50Hz/1000VA out
Mechanical design: 19” x 3U
31
Other applicable products?
Monoblock inverter
MBI series
Input: 110VDC or 220VDC
Output:115VAC or 230VAC
30-50kAV
(up to 100kVA at 220VDC)
Mechanical design:
stand cabinet in RAL7035
32
Other applicable products?
Monoblock UPS systems
MBS series
Input: 3x 230/400VAC
Output:1ph. 230VAC or 115VAC
50 or 60 Hz
60 up to 100kVA
Mechanical design:
stand cabinet in RAL7035
33