Kickoff Powerpoint presentation, 1998
Download
Report
Transcript Kickoff Powerpoint presentation, 1998
Distribution System Analytical
Data (DSAD) WG
Roger C. Dugan
Electrotek Concepts
Knoxville, TN
July 1998
R. C. Dugan, DSAD Working Group, July 98
Scope
• Develop a data dictionary for
Distribution System Analytical Data
– Based on form already established by PSAD
Working Group
– Envisioned as continuing effort spanning many
years
• Due to huge volume
• New product introductions
R. C. Dugan, DSAD Working Group, July 98
Scope, cont’d
• Establish dictionary first for those
quantities most commonly used in
power flows, voltage drops, and other
similar calculations. (est. 2 yrs)
• Tackle control quantities, dist. Planning
quantities, etc. (est. ad infinitum)
R. C. Dugan, DSAD Working Group, July 98
PSAD vs DSAD Data
• PSAD is more concerned with control
center and G&T planning data
• DSAD will add definitions for data used
for distribution systems analysis
• May have to duplicate some quantities
• DSAD volume is expected to be higher
due to greater variety of equipment
R. C. Dugan, DSAD Working Group, July 98
PSAD - DSAD Conflicts
• PSAD in MW, MVA; DSAD will be kW, kVA.
• The PSAD makes very extensive use of per unit
values while distribution data uses it less
• Some Z’s are described in per unit on System MVA
base, which is sometimes not used in Dist. Analysis
– Lines
– Capacitors
– Some machine data
• (Transformers are done compatibly with DSAD
concepts.)
R. C. Dugan, DSAD Working Group, July 98
Regulator Bank Object
Adapted from Cooper Power Systems V-BASE Program
Name
NPHASES
CONN
AMPS
KV
TOTALTAPS
MINREG
MAXREG
BUCKLIMIT
BOOSTLIMIT
TAP[1..nphases]
REGCTRL[1..nphases]
Description
Number of phases
Connection (wye/Delta)
Rated Load Current
Rated Coil Voltage kV
(each phase)
Total no. Of taps boost and
buck
Minimum percent
regulation (max buck)
Maximum Percent
Regulation (Max Boost)
Present tap limit (buck)
(add-amp feature)
Present tap limit (boost)
(add-amp feature)
Present Actual Tap, Each
Phase
Pointer To Control Setting
Record In Regctrl File, each
phase
R. C. Dugan, DSAD Working Group, July 98
Data Type
INTEGER
TEXT
REAL
REAL
INTEGER
REAL
REAL
INTEGER
INTEGER
INTEGER
TEXT
CL4C Regulator Control
Name
OPMODE
Data Type
INTEGER
CONFIG
INTEGER
SYSVOLT
PTRATIO
CTRATING
FWDSETVOLT
FWDBAND
FWDDELAY
FWDR
FWDX
REVSETVOLT
REVBAND
REVDELAY
REVR
REVX
REVMETHOD
REVTHRESH
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
INTEGER
REAL
REDUCEMODE
LOCALREDUCE
REMOTE1
REMOTE2
REMOTE3
AUTO1
AUTO2
PCTAUTO1
PCTAUTO2
VLIMITMODE
HIGHVLIMIT
LOWVLIMIT
INTEGER
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
INTEGER
REAL
REAL
Description
Control operating Mode |0Sequential|1-Time Integrating|2Voltage Averaging|
|0-WYE|1-Delta Lag|2-Delta
Lead|
System nominal line voltage (kV)
Nominal PT ratio
CT Primary Rating
SET VOLTAGE (FORWARD)
BANDWIDTH
TIME DELAY (SECONDS)
! R SETTING
X SETTING
SET VOLTAGE (REVERSE)
BANDWIDTH
TIME DELAY (SECONDS)
R SETTING
X SETTING
REVERSE SENSING METHOD
REVERSE THRESHOLD
VALUE - % OF RATED
CURREN
[0,3](0)
[0.0,10.0](4.0)
[0.0,10.0](2.0)
[0.0,10.0](5.0)
[0.0,10.0](7.5)
[0.0,10.0](5.0)
[0.0,10.0](2.5)
[20.0,150.0](75.0)
[20.0,150.0](100.0)
[0,2](0)
[115,135](130)
[105,115](105)
Adapted from Cooper Power Systems V-BASE Program