INSULATION COORDINATION
Specifying Insulation Strength
In Standards
- There exist a standard number series for
both BIL & BSL that equipment standards
are encouraged to use
- For any specific equipment there is a
relation between BIL & BSL
- For example for a transformer, BSL is
approximately 83% of BIL
INSULATION COORDINATION
Specifying Insulation Strength
In Standards
INSULATION COORDINATION
Specifying
Insulation Strength
In Standards
In IEC phase-phase tests are specified to
verify phase-phase BSL
The phase-phase BSL is specified as 1.5
to 1.7 phase-ground BSL
In this case BSL are not the values listed
INSULATION COORDINATION
ANSI Specification for BIL and BSL
INSULATION COORDINATION
Specifying
In
Insulation Strength
Standards
In ANSI C92, no required voltage given for
alternate system voltages
That is user is free to select BIL & BSL from as
desired
However, practically there are a limited number
of BILs and BSLs used at each system voltage
INSULATION COORDINATION
Specifying
In
Insulation Strength
Standards
for USA these values presented in
next tables for transformers, circuit
breakers, and disconnecting switches
INSULATION COORDINATION
ANSI
Table:
INSULATION COORDINATION
ANSI standard values for substations (ANSI)
INSULATION COORDINATION
For Gas-insulated station (ANSI)
INSULATION COORDINATION
ANSI standard levels for Cables
INSULATION COORDINATION
Specified insulation withstands in In IEC standards