Generator Protection
Download
Report
Transcript Generator Protection
Bapuji S Palki, INCRC/PowerTechnologies, 15-11-2009
Protection Application – An Overview
Part 2A
© ABB Group
April 4, 2016 | Slide 1
© ABB Group
April 4, 2016 | Slide 2
Layouts
Typical Parts of a Power Plant
Substation
Busbar in Substation
HV - Breaker
Power plant
Main Transformer
Auxiliary Transformer
Generator Breaker
Excitation Transformer
Excitation System
Turbine valve
Turbine - Generator
Earthing System
G
Field Circuit Breaker
Generator
Protection
Possible Faults
Stator Earth Faults
Rotor Earth Faults
Stator Short Circuits
Stator/Rotor Interturn faults
External faults
Generator
Protection
Abnormal Operating Condition
overcurrent/overload
unbalanced load
overtemperature
over- and undervoltage
over- and underexcitation
over- and underfrequency
over-fluxing
asynchronous running
out of step
generator motoring
failures in the machine control system
(i.e. AVR or governor failure)
failures in the machine cooling system
failures in the primary equipment (i.e.
breaker head flashover)
open phase
• Following are the various protections recommended for the generator
and generator transformer protection:
Type of fault
GENERATOR
STATOR
Short Circuits
Asymmetry
Stator overload
Earth fault stator
© ABB Group
April 4, 2016 | Slide 6
ANSI Device Protection Functions
No.
87G
87GT
21G
51 / 27 G
46G
51G
64G1
64G2
Generator differential
Overall differential
Minimum impedance (or alternatively
Over current / under voltage)
Negative sequence
Overload
95% stator earth fault
100% stator earth fault
Loss of excitation
40G
Out of step
Monitoring
98G
32G / 37G
Blade fatigue
Inter turn fault
Mag. Circuits
Higher voltage
Accidental
energisation
Monitoring
81G
95G
99G
59G
27 / 50 G
© ABB Group
April 4, 2016 | Slide 7
60 G
Loss of excitation
Pole slip
Low forward power / reverse power
(double protection for large generators)
Minimum frequency
Over voltage or over current
Overfluxing volt / Hz
Over voltage
Dead machine
PT fuse failure
GENERATOR
ROTOR
Rotor ground
GENERATOR
TRANSFORMER
Short Circuits
Ground fault
Overhang
UNIT AUXILIARY
TRANSFORMER
Short circuit
Ground fault
© ABB Group
April 4, 2016 | Slide 8
64F
Rotor earth fault
87GT
51GT
87T
51NGT
87NT
87HV
Overall differential
Overcurrent
Transformer differential
Earth fault over-current
Restricted earth fault
HV winding cum overhang differential
87 UAT
51 UAT
51 UAT
64 UAT
Transformer differential
Over-current
Restricted over-current
Restricted earth fault
50/51
Unit aux.
transformer
64F
Field winding
ground-fault
RAGRA
(RXNB4)
1) Instruments
© ABB Group
April 4, 2016 | Slide 9
Protection
and Monitoring
REG 670 – Different applications
REG 670 provides extensive
protection and monitoring functionality
1ph U
3ph U
The REG 670 provides protection functions and
concepts for:
Turbine (frequency, reverse power)
Generator (Main1/Main2, Main/Back-up)
Generator transformer/Step-up transformer
Auxiliary/Station service transformer
Excitation transformer
3ph I
1ph U
G
1ph I
3ph I
1ph U
REG 670 focus on the
optimized integration and function
to protect your generator
IEC 61850
A Breakthrough for Substation Automation
One world
One technology
One standard
IEC 61850
“Combining the best properties in a new way...”
© ABB Group
April 4, 2016 | Slide 12
Power transformers in a power system
400 kV AC Transmission
130 kV Subtransmission
Generation
MV
Distribution
LV
M
© ABB Group
April 4, 2016 | Slide 13
315MVA Transformer
© ABB Group
April 4, 2016 | Slide 14
Cooling
Outer Ci rcui t
H eat
D i ssi pati on
Pump
opti onal
I nner Ci rcui t
Heat
Producti on
(Core and
Wi ndi ngs)
F an
opti onal
© ABB Group
April 4, 2016 | Slide 15
Oi l i mmersed
Tank
In principle the larger the losses in the Inner
Circuit the larger the size of the Outer Circuit
(coolers or radiators)
There is nevertheless a limit either due to
the size of the coolers or to the impossibility
of cooling a certain spot (hot-spot) in the
Inner Circuit
A pump to move the oil is often
unnecessary. The generated heat will act as
a siphon
Types of Internal Faults
© ABB Group
April 4, 2016 | Slide 16
Earth faults
Short-circuits
Inter turn Faults
Core Faults
Tank Faults
Reduced cooling
Abnormal Conditions
© ABB Group
April 4, 2016 | Slide 17
Overload
Over voltage
Reduced system voltage
Over excitation
Overload Capability
It is possible to overload power transformers
Older transformers may withstand 140% continuously
Overloading and loss of cooling causes overheating
© ABB Group
April 4, 2016 | Slide 18
Protective Relays Used ( Transformers > 5 MVA)
© ABB Group
April 4, 2016 | Slide 19
Gas detector relay ( Buchholz)
Over load protection
Thermal relays
Temperature monitoring relays
Over current protection
Ground fault protection
Differential protection
Interturn faults
Pressure relay for tap changer
Oil level monitor
Protective Relays Used ( Transformers < 5
MVA)
© ABB Group
April 4, 2016 | Slide 20
Gas detector relay
Overload protection
Overcurrent protection
Ground fault protection
Monitors
Monitors are very important devices which detect
faults and abnormal service conditions which may
develop into fault.
© ABB Group
April 4, 2016 | Slide 21
Transformer Monitors
Mechanical fault detectors
Sudden gas pressure protection
Buchholz protection
Oil level monitoring
Temperature Monitoring
© ABB Group
April 4, 2016 | Slide 22
The oil thermometer
The winding thermometer
Transformer protection with 670/650 series
Introduction
Transformer Protection
670/650 series
Openness
and flexibility
Reliable Operation
Complementary
functionality
Control Capabilities
Communication
Offering and
application examples
Technology Summary
Relion®
Summary
© ABB Group
November 2009
| Slide 23
670 series – optimized for generation
and transmission applications provide
versatile functionality, maximum
flexibility and performance to meet
the highest requirements of any
application in generation and
transmission protection systems.
650 series – your best choice for subtransmission applications provide
“off-the-shelf”, ready to use solutions
for transformer protection
applications primarily in subtransmission networks.
Fully compliant to the IEC 61850 standard
Introduction
Line Distance Protection
670/650 series
Reliable Operation
Complementary
functionality
Control Capabilities
Communication
Offering and
application examples
Technology Summary
Relion®
Summary
© ABB Group
November 2009
| Slide 24
Unrivalled compatibility for new and
retrofit installations
Designed for IEC 61850,
implementing the core values of this
standard
Ensures open, future-proof and
flexible system architectures, with
state-of-the-art performance
Interoperates with other IEC 61850
compliant IEDs
© ABB Group
April 4, 2016 | Slide 25
The reactor absorbs the capacitive power
generated in long lines
© ABB Group
April 4, 2016 | Slide 26
Shunt Reactor
© ABB Group
April 4, 2016 | Slide 27
A B C
A B C
L
R
Lp
Lp
Ln
© ABB Group
April 4, 2016 | Slide 28
Lp
General
Shunt reactors are used in EHV systems to limit
the over voltages due to capacitive VAR
generation in Long Transmission Lines
The shunt reactors are normally connected
Through isolators to a line
Through circuit breakers to a busbar
© ABB Group
April 4, 2016 | Slide 29
Through circuit breakers to the tertiary of a
Interconnecting transformer
Different locations of reactor
© ABB Group
April 4, 2016 | Slide 30
Internal Faults
Faults occur in shunt reactors due to insulation breakdown, ageing
of insulation, overheating due to over excitation, oil contamination
and leakage
Dry air-core reactors
Phase-to-phase faults , resulting in high magnitude phase
current
Phase-to-earth faults ,, resulting in a low-magnitude earth-fault
current, dependent upon the size of the system earthing.
Turn-to-turn faults within the reactor bank, resulting in a very
small change in phase current
Oil-immersed reactors
High current phase-to-phase and phase-to-earth faults.
Turn-to-turn faults within the reactor winding.
Miscellaneous failures such as loss of cooling or low oil
© ABB Group
April 4, 2016 | Slide 31
Abnormal Conditions
Inrush currents
Inrush currents flow in connection with energisation
Inrush currents usually lower than 200% of rated
current
Transient overvoltages
Temporary overvoltages
© ABB Group
April 4, 2016 | Slide 32
Shunt Reactor Protections
© ABB Group
April 4, 2016 | Slide 33
Differential protection
Distance protection
Phase over current protection
Restricted earth fault protection
Mechanical fault detectors
Oil temperature and winding temperature
protection
Monitors
Monitors are very important devices which detect
faults and abnormal service conditions which may
develop into fault.
© ABB Group
April 4, 2016 | Slide 34
Reactor Monitors
Mechanical fault detectors
Sudden gas pressure protection
Buchholz protection
Oil level monitoring
Temperature Monitoring
© ABB Group
April 4, 2016 | Slide 35
The oil thermometer
The winding thermometer
Shunt reactor protection and control
Introduction
Transformer Protection
670/650 series
Openness
and flexibility
Reliable Operation
Complementary
functionality
Control Capabilities
Communication
Offering and
application examples
Technology Summary
Relion®
Summary
© ABB Group
November 2009
| Slide 36
Protection
Phase segregated biased
differential protection
Low impedance restricted
earth-fault
High impedance differential
protection
Switching control for lines
and buses
© ABB Group
April 4, 2016 | Slide 37
Capacitor Construction
© ABB Group
April 4, 2016 | Slide 38
Power Factor Correction
Working Power (kW)
Reactive Power (kVAR)
KW is the Working Power component
kVAR is the Non- Working Power or Reactive Power component to serve inductive loads, which require magnetizing current:
Motors, Transformers, Lighting ballast
KVA is the Total Power required to serve a load
Capacitors supply the reactive power component
Power Factor is a measurement of how efficiently power is being used.
© ABB Group
April 4, 2016 | Slide 39
Increased System Capacity
Extra capacity for more KVA
released system capacity
Total Power (KVA) = Working Power (KW) Power Factor
Power Factor
Real Power kW
Reactive Power kVAR
Total Power kVA
60%
600
800
1000
70%
600
612
857
80%
600
450
750
90%
600
291
667
100%
600
Zero
600
By supplying reactive current (kVAR) close to the load, capacitors release system
capacity on the entire system and reduce costs.
© ABB Group
April 4, 2016 | Slide 40
Voltage Stability
A feeder circuit will have a voltage drop related to the
impedance of the line and the power factor
Adding capacitance will actually cause a voltage rise by
supplying reactive current to the bus
(less current = less voltage drop)
© ABB Group
April 4, 2016 | Slide 41
Products
Capacitors – HV Products / Filter Capacitor Banks
Improving the performance, quality
and efficiency of electrical systems
© ABB Group
April 4, 2016 | Slide 42
Capacitor banks- General
Normally used in MV networks to generate reactive power
Series reactors are used to limit inrush current
Harmonic filters for thyristor controlled reactors are also
variation of capacitor banks having reactance tuned to
capacitance
Shunt
Capacitors-General
Shunt Capacitor Faults
Terminal shunt faults
Capacitor unit failures
Capacitor unit over voltages
Capacitor rack arc-over
Abnormal Conditions
Inrush currents
Transient over voltages
Temporary over voltages
Out rush currents
Capacitor Bank Protections
Short -circuit protection
(3I >>)
Ground-fault protection
(I )
Overload protection(3I/U >)
Under current protection
(I/U <)
Unbalance protection
(IN-N)
Fusing
Capacitor Fusing
Internally Fused
Fuse
© ABB Group
April 4, 2016 | Slide 48
Externally Fused
Discharge Resistor
Internal Strings
Fuseless
Conventional
SPAJ
160 C : Unbalance , Overload and
Under current functions
Bapuji S Palki, INCRC/PowerTechnologies, 15-11-2009
Protection Application – An Overview
Part 2B
© ABB Group
April 4, 2016 | Slide 50
© ABB Group
April 4, 2016 | Slide 51
The Electric Utility
Power Evacuation Substation
Transmission Substation
Switching Substation
Distribution Substation
© ABB Group
April 4, 2016 | Slide 52
Transmission Line
© ABB Group
April 4, 2016 | Slide 53
Electrical faults in the power system
Transmission lines
85%
Busbar
12%
Transformer/ Generator
3%
100%
© ABB Group
April 4, 2016 | Slide 54
Fault types
© ABB Group
April 4, 2016 | Slide 55
Transient faults
are common on transmission lines, approximately 80-85%
lightnings are the most common reason
can also be caused by birds, falling trees, swinging lines
etc.
will disappear after a short dead interval
Persistent faults
can be caused by a broken conductor fallen down
can be a tree falling on a line
must be located and repaired before normal service
Measuring principles
© ABB Group
April 4, 2016 | Slide 56
Overcurrent protection
Differential protection
Phase comparison
Distance protection
Directional- wave protection
Overcurrent protection
Are normally used in radial networks with system voltage
below 70 kV where relatively long operating time is
acceptable.
On transmission lines directional or nondirectional over
current relays are used as back-up protections.
I>
block
© ABB Group
April 4, 2016 | Slide 57
I>
I>
I>
Pilot wire differential protection
© ABB Group
April 4, 2016 | Slide 58
Pilot wires can be in soil or on towers.
The resistance in the wires will limit the use on
longer lines. The use is mostly restricted to
distances up to 10 km.
Digital differential communication
L1
L2
L3
DL1
DL2
DL3
© ABB Group
April 4, 2016 | Slide 59
Digital communication with
optical fibres or by
multiplexed channels
DL1
DL2
DL3
Phase comparison
load
I1
>
>
Phase comparison relays compare
the angle difference between the two
currents at both ends of the line.
The measured time for zero crossing
is transmitted to the other end.
Normally a start criteria is added to
the phase angle requirement.
I2
I1 I2
e
1
e
2
e1 e
-
2
I2
func-
tion
I1
I2
© ABB Group
April 4, 2016 | Slide 60
The principle of distance protection
ZK=Uk/Ik
Uk
Uk=0
metallic fault
Zk
A
Z<
© ABB Group
April 4, 2016 | Slide 61
Ik
B
Fault resistance
multi-phase faults
consist only of arc resistance
© ABB Group
April 4, 2016 | Slide 62
L1
L1
L2
L2
L3
earth faults
consist of arc and tower
footing resistance
Warrington´s
formula
Rarc =
L3
28707 x L
1.4
I
L= length of arc in
meters
I= the actual fault current in
A
Footing resistance
Distance protection on short lines
jX
Quadrilateral characteristic improves
sensitivity for higher RF/XF ratio
It still has some limitations:
RF
XF
© ABB Group
April 4, 2016 | Slide 63
R
the value of set RF/XF ratio is
limited to 5
jX
Distance protection on long lines
Load impedance limits the reach in
resistive direction
High value of RF/XF ratio is generally not
necessary
Circular (mho) characteristic
R
© ABB Group
April 4, 2016 | Slide 64
Has no strictly defined reach in
resistive direction
Needs limitations in resistive
direction (blinder)
The principle of distance protection
t
t3
t2
t1
l
A
B
f
1
Z<
C
f
3
f
2
Z<
Z<
Z<
t
t3
t2
l
© ABB Group
April 4, 2016 | Slide 65
t1
The principle of distance protection
Reach setting of zones
R/ X Relation
GFC (General Fault Criterion)
GFC
ZL
ZL
Zb
© ABB Group
April 4, 2016 | Slide 66
PLCC equipment
© ABB Group
April 4, 2016 | Slide 67
Power Swing Blocking function
X
Power swing
locus
R
t
t = 40 ms
© ABB Group
April 4, 2016 | Slide 68
Series compensated
system
jX
B´
A
XC =70%
100%
Xl =100%
B
F1
gape flashed
Consideration for line
distance protections
B
A
70%
© ABB Group
April 4, 2016 | Slide 69
R
gape not flashed
• Correct direction discrim-ination
at voltage reversal (negative
fault reactance)
• variation in resulted line
impedance
Line distance protection with Relion® 670/650 series
For maximum reliability of your power system
Introduction
Line
Distance Protection
670/650
series
Reliable
Operation
Complementary
functionality
Control
Capabilities
Full scheme distance protection
with independent phase selection
Power swing detection
Wide range of scheme
communication logics
Five zone distance protection
Communication
Offering
and
application
examples
Technology
Relion®
Summary
© ABB Group
November 2009
Slide 70
Summary
Phase to phase
Phase to earth faults
Fully compliant to the IEC 61850 standard
Introduction
Line
Distance Protection
670/650
series
Reliable
Operation
Complementary
Unrivalled compatibility for new and
retrofit installations
Designed for IEC 61850,
implementing the core values of this
standard
Ensures open, future-proof and
flexible system architectures, with
state-of-the-art performance
Interoperates with other IEC 61850
compliant IEDs
functionality
Control
Capabilities
Communication
Offering
and
application
examples
Technology
Summary
Relion®
Summary
© ABB Group
November 2009
Slide 71
© ABB Group
April 4, 2016 | Slide 72
Auto reclosing Cycle
OH-lines
High fault-rate
(80-90%)
Fast
simultaneous
Fault clearing
© ABB Group
April 4, 2016 | Slide 73
AUTORECLOSING CYCLE
OH-lines
Intermittent faults
(80-90%)
Successful
AR-rate :
High (80-90%)
© ABB Group
April 4, 2016 | Slide 74
Auto reclosing principles
95% of faults are transient type
3 Ph autoreclosing synchrocheck is used
1 Ph autoreclosing needs identification of
faulty phase
© ABB Group
April 4, 2016 | Slide 75
Helps verify phase angles are not out of phase
e.g: due to heavy power swing
Phase identification is difficult for high resistance
faults
Single-pole Reclosing
Single-Pole Reclosing
A B C
© ABB Group
April 4, 2016 | Slide 76
A B C
Artificial extinction of secondary arc by Fixed
Four-reactor Scheme
ABC
ABC
L
R
Lp Lp Lp
Ln
© ABB Group
April 4, 2016 | Slide 77
Synchronism and Energizing check
UBus
ULine
UBus
FreqDiff < 50-300 mHz
o
PhaseDiff < 5-75
UDiff < 5-50% Ur
UHigh > 50-120% Ur
U Bus
1-ph
U Line
3-ph (or 1-ph)
ULow < 10-100% Ur
SYNC-BLOCK
© ABB Group
April 4, 2016 | Slide 78
Fuse fail
ULine
© ABB Group
April 4, 2016 | Slide 79
Need for Busbar protection
In its absence fault clearance takes place in Zone-II of
distance relay by remote end tripping
This means slow and unselective tripping and wide spread
black out
Effect of delayed clearance
© ABB Group
April 4, 2016 | Slide 80
Greater damage at fault point
Indirect shock to connected equipments like shafts
of Generator and windings of transformer.
Types of BB Protections
© ABB Group
April 4, 2016 | Slide 81
High impedance
Medium impedance
Low impedance
Blockable O/C relay ( For radial systems in
distribution systems)
High impedance bus differential relay
Basic features
SETTING VR > IF ( RCT + 2 RL)
VK > 2 VR
RL
A
VR
RCT
B
FOR VR TO BE ZERO FOR
EXTERNAL FAULT
nA = nB 1 + RA / ZA
1 + RB / ZB
n = TURNS RATIO
R = RCT + 2 RL
Z = MAGNETIZING IMPEDANCE
© ABB Group
April 4, 2016 | Slide 82
Limitations of High impedance differential relay
© ABB Group
April 4, 2016 | Slide 83
Puts stringent requirements on CTs
Need for dedicated CTs
Identical CT ratios , magnetising impedances
Aux CTs not acceptable
Inability to cope with increasing fault levels
RADSS medium
impedance relay
IR1
T MD
n MD
Ud3
dR
D2
US
© ABB Group
April 4, 2016 | Slide 84
D1
REB500 - Numerical Busbar
and Breaker Failure Protection
ABB Network Partner AG
REB 500
C
E
Distributed installation
ABB Network Partner AG
REB 500
ABB Network Partner AG
C
E
Bay Unit
Central Unit
REB 500
ABB Network Partner AG
REB 500
C
E
Bay Unit
C
E
Bay Unit
REB 500
C
E
Bay Unit
E
© ABB Group
April 4, 2016 | Slide 85
ABB Network Partner AG
E
Advantages of medium/ Low impedance relays
© ABB Group
April 4, 2016 | Slide 86
Free from any need for Identical CT ratios or matched CTs
Other relays can be included in the same CT core
Increasing fault levels have no impact
1000/5
200/5
500/5
5A
3.5 A
5/1
500 A
200 A
700 A
5/0.5
5/0.2
0.7 A
0.2 A
Diff. relay
RADSS IN SINGLE BUS
© ABB Group
April 4, 2016 | Slide 87
5A
0.5 A
REQUIREMENTS ON THE ISOLATOR AUXILIARY CONTACTS
Isolator Aux. Contact ‘a’ should
close before the primary contact
a
b
closes and
Aux contact’ b’ closes after the
primary contact opens.
O
C Throw-over relay
0%
Main
contact
Aux.
Contact
a
Aux.
Contact
b
© ABB Group
April 4, 2016 | Slide 88
100%
DOUBLE BUSBAR SYSTEM WITH TRANSFER BUS
BUS - A
BUS - B
AUX. BUS
© ABB Group
April 4, 2016 | Slide 89
1½- BREAKER SYSTEM
RADSS - A
L1
L3
L5
L2
L4
L6
BUS - A
BUS - B
RADSS - B
© ABB Group
April 4, 2016 | Slide 90
Busbar Protection REB670
© ABB Group
April 2009
Slide 91
© ABB Group
April 4, 2016 | Slide 92
History - Circuit breaker development
Example: 420 kV
Air Blast
…around 1960
© ABB Group
April 4, 2016 | Slide 93
Oil Minimum
SF6 Gas
…around 1980
…today’s
technology
Interrupters
Interrupter design
© ABB Group
April 4, 2016 | Slide 94
+
Relay back-up
RELAY
SYSTEM
CHANNEL
52
50
-
52a
52 52a
RELAY
SYSTEM
CHANNEL
+
© ABB Group
April 4, 2016 | Slide 95
Breaker back-up
5
1
6
2
Z<
7
8
3
4
For uncleared fault shown CB’s to be tripped are 1, 3, 4 & 6
© ABB Group
April 4, 2016 | Slide 96
Classical CBFP
Breaker Failure Protection
I>
I>
I>
I>
+
if trip
from
relay
© ABB Group
April 4, 2016 | Slide 97
t
trip
© ABB Group
April 4, 2016 | Slide 98
Introduction
Majority faults are earth faults
Earth fault protection depends on type of earthing
© ABB Group
April 4, 2016 | Slide 99
Effectively earthed
Reactance earthed
High resistance earthed
Resonance earthed
Measurement of earth fault current
© ABB Group
April 4, 2016 | Slide 100
Measurement of zero sequence voltage
L1
L2
L3
U0>
Earth fault protection in solidly earthed
systems
IDMT earth fault relays
are used to detect earth
faults in effectively earthed
system
© ABB Group
April 4, 2016 | Slide 102
Directional Earth Fault Relay
© ABB Group
April 4, 2016 | Slide 103
Directional earth fault relays are
used
Can use communication link
Inrush current stabilization may
be required for sensitive settings
Directional earth fault relay for High
resistance earthed system
Directional earth fault relay used when in feed
of capacitive current from an object is higher
than 60% of required sensitivity
Measures active component of fault current
© ABB Group
April 4, 2016 | Slide 104
Earth fault in resonance earthed network
A B C
ΣI01
C0
ΣI02
L
RL
U0
Ief
R0
Earth fault in isolated network
A B C
ΣI01
C0
U0
ΣI02
Ief
R0
Directional earth fault relay
© ABB Group
April 4, 2016 | Slide 107
Restricted earth fault relay
© ABB Group
April 4, 2016 | Slide 108
© ABB Group
April 4, 2016 | Slide 109
What is Substation Automation ?
A combination of:
© ABB Group
April 4, 2016 | Slide 110
Protection
Monitoring
Control
Communication
What is Substation Automation ?
Substitution for conventional control panels
Substitution for other sub systems
A more efficient way of controlling your substation
© ABB Group
April 4, 2016 | Slide 111
8
The conventional way
Control Board
Telecontrol
RTU
Alarming
Synchronization
Busbar
Protection
MARSHALING RACK
Local
ControlTELE-
© ABB Group
April 4, 2016 | Slide 112
Interlocking
ALARMING
Measuring
NISATION
Bay
BUSBAR
Protection
PROTECTION
System Engineering Tool
The New Way
Station
Monitoring
System
Station HMI
Gateway
Station Clock
Communication only
during engineering
IED Tool
Station bus
Bay
Control
Web Client
Object
Protection
Control &
Protection
Multi Object
Protection
IEDs
Process bus
Merging Unit
© ABB Group
April 4, 2016 | Slide 113
Merging Unit
Multi Bay
Control
Conventional Control & Protection
Fault
Recording
Station Level
ABB
225kV LIGNE ABOBO 1
125VDC Distributuion Battery A
=D04+R01
125VDC Distributuion Battery B
Bay Protection
ABB
225kV LIGNE ABOBO 1
125VDC Distributuion Battery A
Busbar Protection
ABB
=D04+R01
ABB
=D04+R01
225kV LIGNE ABOBO 1
125VDC Distributuion Battery A
125VDC Distributuion Battery B
125VDC Distributuion Battery B
Event
Recording
=D04+R01
ABB
225kV LIGNE ABOBO 1
125VDC Distributuion Battery A
=D04+R01
125VDC Distributuion Battery B
ABB
RTU 200IN 1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 OUT
1
056 citcadnI
056 citcadnI
056 citcadnI
Network Partner
9114
24351678ABB
10
11
13
15
162REL316*4
=W1
=W2
12345678-Q1
9111
12
13
14
15
160eriosn
V
4.2b
FERMER
cABB
Network Partner
912REL316*4
2435678111
10
13
14
15
16
REB500
ABB
Network Partner
ON/OFF
BAY CONTROL RELAY REC316*4
LOCAL CONTROL
RTU 200IN 1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 OUT
ON/OFF
38
Indactic650
650
Indactic
METERING
ABB
RTU 200IN 1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 OUT
ON/OFF
Indactic650
650
Indactic
LINE PROTECTION RELAY REL316*4
ABB
BUSBAR PROTECTION REB500
ABB
225kV LIGNE ABOBO 1
ABB
Bay Level
225kV LIGNE ABOBO 1
125VDC Distributuion Battery A
125VDC Distributuion Battery B
SCADA
RTU
For each function a
dedicated device
and separate Panel
Control
Panel
ABB
=D04+R01
ABB
=W1
=W2
-Q1
SEL
-Q2
SEL
-Q0
SEL
TESTE
LAMPE
Extensive station wide cabling
OUVRIRFERMER
ABB
ESC
EXE
Local
Control
DISTANCE
LOC
Process Level
Marshalling
Extensive bay cabling
GIS or AIS
Switchgear
-Q2
-Q0
-Q1
-Q9
-Q8
Substitution of Conventional Technology
Bay Control/Protection Cubicles
Fällanden
Steuerung / Schutz
Fällanden
Steuerung / Schutz
MicroSCADA
=AD17-KB2
=AD17-KB2
Feldsteuergerät REC216 mit Messung und Synchrocheck
Feldsteuergerät REC216 mit Messung und Synchrocheck
Interbay bus
Ethernet Switches
d gi ta l
LEITUNGSHAUPTSCHUTZ REL316*4
I
0
I
0
STUFENVERL. WE-BLOCK
LEITUNGSHAUPTSCHUTZ REL316*4
I
0
I
0
STUFENVERL. WE-BLOCK
PRÜFSTECKER
Reset
AUS
I
0
di gi tal
SCHUTZ EIN/AUS
PRÜFSTECKER
Reset
AUS
I
0
SCHUTZ EIN/AUS
-Q2
-Q1
COM 581
ABB
Power Automation AG
COM581
NCC / RCC
Communication
Converter
-Q0
Marshalling
-Q9
C
Control Cubicle
Relays for control / logic
Transducers, Meters
Switches, Lamps
Annunciators, Terminals
-Q8
Protection Cubicle
SER / Fault Recorder
SCADA RTU
NCC / RCC
Modern Substation Automation (SA)
Bay Control/Protection Cubicles
Fällanden
Steuerung / Schutz
Fällanden
Steuerung / Schutz
=AD17-KB2
MicroSCADA
=AD17-KB2
220VDC SPANNUNG SYS 1 220VDC SPANNUNG SYS 2
220VDC SPANNUNG SYS 1 220VDC SPANNUNG SYS 2
Feldsteuergerät REC216 mit Messung und Synchrocheck
I
0
VERRIEGELUNG
Feldsteuergerät REC216 mit Messung und Synchrocheck
Interbay bus
Ethernet Switches
I
d gi ta l
0
VERRIEGELUNG
LEITUNGSHAUPTSCHUTZ REL316*4
I
I
0
0
STUFENVERL. WE-BLOCK
LEITUNGSHAUPTSCHUTZ REL316*4
I
I
0
-Q2
-Q1
0
AUS
AUS
RESERVESCHUTZ
I
-X1
SYNCHRONISIERUNG HAND
AUS
0
I
AUS
0
SCHUTZ EIN/AUS
2 x 220/24V DC/DC SPANNUNGSVERSORGUNG
2 x 220/24V DC/DC SPANNUNGSVERSORGUNG
-Q0
-Q8
ABB
Power Automation AG
COM581
NCC / RCC
Communication
Converter
C
E
Marshalling
-Q9
COM 581
SCHUTZ EIN/AUS
RESERVESCHUTZ
-X1
SYNCHRONISIERUNG HAND
di gi tal
SCHUTZ EIN/AUS
I
0
SCHUTZ EIN/AUS
SAMMELSCHIENENSCHUTZ REB500
SAMMELSCHIENENSCHUTZ REB500
I
0
PRÜFSTECKER
Reset
STUFENVERL. WE-BLOCK
PRÜFSTECKER
Reset
Still extensive bay cabling
Modern SA Architecture
Station Level
Network Control
Center NCC
ABB Network Partner AG
C
-Q2
-Q0
-Q1
-Q9
-Q8
Features and Benefits
Basic Functionality
E
Bay Level
Process Level
COM581
Implementation of Intelligent Technology
Intelligent Primary Equipment
MicroSCADA
Interbay bus
Ethernet Switches
M M
-Q2
di gi tal
-Q2
-Q1
-Q51
-Q0
Drive control &
monitoring
circuitry
PISA
A
PISA
A
PISA
B
-Q8
-Q9
-Q8
i it l
COM 581
ABB
Power Automation AG
COM581
Communication
Converter
NCC / RCC
C
-Q0
-T1
-Q9
LOCAL SET
REMOTEOPERATION
PISA
Feeder Marshalling
-Q1
t
d gi tal
M
?
Sampling
AD-Conversion
Signal Processing
Signal Filtering
Process
Bus
Station Level
Intelligent SA Architecture
Network Control
Center NCC
C
Basic Functionality
E
Bay Level
M M
M
?
LOCAL SET
REMOTEOPERATION
-Q2
-Q0
-Q1
-Q51
PISA
A
PISA
B
PISA
A
PISA
Process Level
COM581
-T1
-Q9
-Q8
FEATURES AND BENEFITS
ABB Network Partner AG
Functional Structure of Modern SA
Station Level
Functions Allocation
Network Control
Center NCC
ABB Network Partner AG
C
E
Bay Level
Process Level
COM581
Scalable System Extensions
SCADA
Remote Communication
Fault evaluation
Monitoring
Events and alarms
Supervision & Control
Data Exchange
Monitoring
GIS or AIS Switchgear
Instrument Transformers
Power Transformers
Surge Arresters
-Q2
-Q0
-Q1
-Q9
-Q8
Intelligent Substation Automation
Functional Structure
Station Level
Network Control
Center NCC
ABB Network Partner AG
COM581
C
E
Bay Level
Scalable System
Extensions
SCADA
Remote Communication
Fault evaluation
Monitoring
Events and alarms
Supervision & Control
Data Exchange
M M
Monitoring
M
?
LOCAL SET
REMOTEOPERATION
-Q2
-Q0
-Q1
-Q51
PISA
A
PISA
B
PISA
A
PISA
Process Level
Functions Allocation
-T1
-Q9
-Q8
Intelligent or “smart”
AIS / GIS Switchgear
Data acquisition
Sensors & Actuators
Power Transformers
Surge Arrestors
Intelligent SA: Control, Protection and Sensors
ABB
Actuator
for
isolator &
earthing
switch
control
PISA PISA
PISA
PISA
Line Protection 1 I
Abgangsschutz
M
M
Bay Controller
Feldleitgerät
M
Switches
Actuator for
circuit breaker
control
?
LOCAL
SET
REMOTE
OPERATION
PISA
A
Line Protection 2 II
Abgangsschutz
PISA
A
PISA
B
Busbar Protection
Sensors for
current &
voltage
measurement
Process Bus
Interbay bus 1
Interbay bus 2
Monitoring via IEDs for Protection
Advanced analysis
tools
Alarm Classes
Automatic printing
Summary report
GPS
User friendly
visualization
Universal Time
synchronization
CONCISE / FAST
Distance to Fault
Mo 12. 11. 96
GMT 17:02.43.305
Ayer Rajah & Labrador
Feeder One
Sequence of Events
ABB Network Partner AG
IED Parameter
# Of trips
C
E
ABB Network Partner AG
REL 316*4
ABB Network Partner AG
REL 316*4
ABB Network Partner AG
1
9
1
9
2
10
2
10
1
9
3
11
3
11
2
10
4
12
4
12
3
11
5
13
5
13
4
12
6
14
6
14
5
13
7
15
7
15
6
14
8
16
8
16
7
15
8
16
C
C
E
E
REL 316*4
C
E
Station level supervision
Single Line Diagram:
Diagnostic: Fault Recording and Evaluation
Automatic
fault location
printout
Remote Control via Network Control Centre (NCC)
The goal of the IEC 61850 standard
Interoperability
The ability for IED’s from one or several manufacturer
to exchange information and use the information for the
their own functions.
Free Configuration The standard shall support different philosophies and
allow a free allocation of functions e.g. it will work
equally well for centralized (RTU like) or decentralized
(SCS like) systems.
Long Term Stability The standard shall be future proof, i.e. it must be able
to follow the progress in communication technology as
well as evolving system requirements.
© ABB Group
April 4, 2016 | Slide 127
© ABB Group
April 4, 2016 | Slide 128