DISTRIBUTED GENERATION ISLANDING
Download
Report
Transcript DISTRIBUTED GENERATION ISLANDING
DISTRIBUTED GENERATION ISLANDING - IMPLICATIONS ON
POWER SYSTEM DYNAMIC PERFORMANCE
Sandhya P Prabhu
April 19, 2006
What is islanding ?
Figure 1 Typical distributed system with DG’s [2]
Figure 1 Typical distributed system with DG’s [2]
Implications of unintentional islanding
• Hazard to utility line workers and public
• Damage to customer equipment if the voltage and
frequency provided by the DG is not regulated
• Damage to the DG’s in the island when island is
reconnected to the grid
Out - Phase – Reclosing
• What is reclosing / out – of – phase reclosing?
• Produces transients which are potentially damaging to utility &
customer equipments
Figure 2 Phase voltages on source and DG side for a simulation of 180º
out-of-phase reclosing [1]
• Unusually high inrush currents in transformers
Active Anti - Islanding
1)Communication based schemes
2)Local detection schemes
1a) Transfer Trip Scheme
1b) Power Line Signaling Scheme
[2]
2a) Method of impedance measurement
[2]
Dynamic Impact of Anti-Islanding Measures
Under voltage trip sensitivity
Undervoltages due to faults can lead to unnecessary DG
tripping
With extensive DG penetration, simultaneous DG
tripping due a fault can cause voltage collapse in the
local system (voltage regulation equipment takes time to
react)
Positive sequence voltage magnitude for simulations of a system with 45% DG
penetration, comparing results for sensitive DG undervoltage tripping to results
with less sensitive tripping and no tripping. [1]
Active Anti-Islanding Impact
Degradation of power quality and system stability as DG
penetration becomes higher
Currently the local islanding detection methods virtually
guarantee that the DG will be unable to provide grid
support or improve grid stability when the grid is stressed
anti-islanding protection disconnects the DG when it detects voltage
and frequency excursions on the grid.
Because of the reclosing practice, anti-islanding
techniques must trip DG’s within about 200 milliseconds
before the breaker is reclosed.
Failure to do so will lead to out-of-phase re-energization of the DG.
Conclusion
DG penetration levels are not sufficient to cause the problems
discussed above.
With the growth of DG, these system issues will be
confronted in the future.
The dynamic performance impact needs to be addressed.
Inadvertent islanding detection schemes not having an undesirable
impact on interconnected system performance would be a highly
desirable development.
References
[1] Distributed Generation Islanding – Implications on Power System
Dynamic Performance. R. A. Walling, Senior Member, IEEE, and N.
W. Miller, Fellow, IEEE
[2] An Assessment of DG Islanding Detection Methods and Issues for
Canada July, 2004
CETC-Varennes 2004-074 (TR) 411-INVERT
[3] Islanding Detection Method of Distributed Generation Units
Connected To Power Distribution System. J.E.Kim, Member IEEE,
J.S.Hwang
Questions / Comments ?