Stylitis-Power full presentation

Download Report

Transcript Stylitis-Power full presentation

STYLITIS-POWER
…designed for in‐coming and out‐coming power/energy analysis
1. MAIN FEATURES
•
Measurement inputs:
-
•
•
•
•
•
•
•
•
•
4 differential voltage inputs. (or 1 3-phase line+ neutral).
Voltage input range: 0~280VAC
40 differential voltage inputs for connection to voltage‐output current transformers (CT) (or 10 3phase lines + neutral).
Current input range is software configurable to cater for various CTs: 0,29 to 1,45 full scale VRMS for
0 to 6000A.
Measurements: Voltage, Frequency, Current, Power Factor, Active, Reactive and Apparent
Power and Energy
All inputs sampled simultaneously at 2 kHz sample rate.
True RMS value calculation based on full cycles within a 0.5 second interval.
Averaging Interval selectable from 0.5 second to 1 hour in steps of 0.5 seconds.
Recording in internal 4MB Flash memory.
1 serial communication port (DTE).
Built-in Ethernet module.
Optional: Built-in GSM/GPRS modem.
Power supply may come from first voltage phase connection or separate socket.
2. PHYSICAL FORM
Stylitis-Power features:
• Control
-
•
•
•
•
•
•
Touch-screen LCD graphic display, brief operation
Total control via our Opton software
Com Ports: 1 serial communication port (DTE)
INPUT CONNECTORS: Removable screw terminal strips on front panel
ENCLOSURE:
ΙΡ67 sealed with carrying handle.
DIMENSIONS: 27 x 24.6 x 17,4 cm, WEIGHT: 3kg
CONNECTORS: Removable circular connectors on left and right side
3. SCREEN AND KEYBOARD
Stylitis-Power has an LCD touch screen graphic display. Most operations are performed via Opton,
its free operating software. However, via the screen, you can:
•
•
•
•
•
•
•
View instantaneous channel values.
View logger time and recording interval.
Display instant channel values (voltage, current, power and power factor) for all channels in
tabular or bar graph form.
Change the acquisition status (ON/OFF).
Activate or deactivate the internal modem if there is one (activate either the modem or the
serial port).
View the internal modem’s signal strength (if there is one, and if it is in GSM data mode).
To display instruction pages and general information about the instrument.
4. CHANNELS/MEASUREMENTS AND CT TYPES
•
Input channels (measurements) supported:
-
Voltage (0~280VRMS): 4 channels or 1 3-phase one.
Frequency of the first Voltage channel.
Current, via Current Transformers: 40 channels or 10 3-phase ones.
To save CTs, you can select for the neutral phase’s current to be computed, or, if you do not use
neutral, for the third phase’s current to be computed.
Calculated for each current channel:
-
-
•
Power factor.
Active, Reactive and Apparent Power.
Active, Reactive and Apparent Energy, during each recording interval.
The types of Current Transformers (Voltage Output ones) supported are:
-
0~1.000 VRMS output
0~0.500 VRMS output
0~0.333 VRMS output
1 mV/A output (1 VRMS max)
5. STYLITIS-POWER MODELS (VERSIONS)
The datalogger is available either as standard model (with built-in Ethernet and RS-232 DTE port) or
with an additional built-in modem. Therefore, its versions are:
•
•
Standard Stylitis-Power. The logger features a built-in Ethernet port and an RS-232 DTE port.
Stylitis-Power+GSM. The logger features an additional built-in GSM/GPRS modem.
Each Stylitis-Power version is suitable for specific communication methods. These methods are
presented in the next chapters.
6. COMMUNICATION METHODS
Communicate with the datalogger via Opton, its operating software, in various ways, according to
the model used:
A. Standard Stylitis-Power
1. Locally
2. Via Ethernet (local network or a static IP internet connection)
3. Via a dynamic IP internet connection (via Symmetron’s Diameson Server)
B. Stylitis-Power+GSM
1. Via a GSM data call.
2. Via GPRS, using a cheap Dynamic IP SIM Card (via Symmetron’s Diameson Server)
7. LOCAL COMMUNICATION
1. Locally
RS-232
Stylitis-Power
•
Connect via a null modem serial cable your computer COM port to the logger’s RS-232 DTE port.
8. STATIC IP ETHERNET COMMUNICATION
2. Via Ethernet (local network or a static IP internet connection)
Stylitis-Power
•
•
ADSL Router
LAN/ internet
Connect the datalogger to a LAN or to the internet
An ADSL connection (a static IP) for the logger is required only to connect the logger to the
internet.
9. DYNAMIC IP ETHERNET COMMUNICATION
3. Via a dynamic IP internet connection (via Symmetron’s Diameson Server)
Stylitis-Power
•
•
Dynamic IP
ADSL
Router
Diameson
Gateway
Internet
Connect the datalogger to the internet.
By using Diameson Gateway, Symmetron’s server software, you do not need a static IP ADSL
connection.
10. GSM COMMUNICATION
4. Via a GSM data call
RS-232
Stylitis-Power+GSM
•
•
GSM modem
Connect a GSM modem to a computer COM port.
Call the logger’s modem, provided that both modems’ SIM cards support GSM data calls.
11. GPRS COMMUNICATION (VIA DYNAMIC IP SIM)
5.
Via GPRS, using a cheap Dynamic IP SIM Card (via Symmetron’s Diameson Server)
Virtual COM
Stylitis-Power+GSM
•
•
•
•
•
Diameson Gateway
Internet
Neither ADSL (static IP) connection is required for the logger nor expensive static IP SIM cards.
A cheap dynamic IP GPRS SIM card is required.
Low operation cost: The datalogger is permanently online, but only data exchange is charged.
Devices (Dataloggers and Sym-o-nets) and Computers are connected as clients to Diameson
Gateway, Symmetron’s server software.
Symmetron’s Diameson is available for connections, but you can use your own Diameson, to
manage your own dataloggers.
12. OPTON: STARTING UP AND VIEW
Opton is Stylitis-Power’s free operating software.
•
Start up with Opton, by creating Site folders and Connections.
-
Create one unique site folder for each datalogger.
In each site folder, multiple (different types of) connections can be created for the logger. The
different connection types correspond to the communication methods, discussed before.
The connections created are saved as windows files, which are recognized by Opton in a folder
interface, along with the compressed and decompressed data files (see Chapter 14), and setup files,
ie logger settings (see next Chapter) saved in a file.
Refer to the corresponding screen shot in Chapter 16.
•
After achieving a connection, you can communicate with the logger. Besides changing its
settings and download data, you can view some features, and specifically:
-
-
-
View the logger’s status: Instant parameters, such as the date and time, the current data file being
recorded, the recording time remaining, etc.
Refer to the corresponding screen shot in Chapter 16.
View the instant channel values.
Refer to the corresponding screen shot in Chapter 16.
View an Online plot of the selected channels’ values. Samples are plotted every second.
Besides the channel, you can also select the measurement (current, power factor, active energy, etc).
Refer to the corresponding screen shot in Chapter 17.
•
•
•
•
13. OPTON: SETUP
Connect to the datalogger, via Opton, via one of the connections you created and modify its
setup. The main settings to be adjusted are the channel settings.
VOLTAGE CHANNEL SETTINGS
The Voltage Channel refers either to one 3-phase line (+neutral) or to 4 independent 1-phase
lines.
The only parameter to be set is each line’s slope. There is a default one, but you can also type a
more exact calibrated one.
CURRENT CHANNEL SETTINGS
The Current Channels refer either to 10 3-phase lines (+neutral) or to 40 independent 1-phase
lines. The settings of a current channels can be changed in two ways:
-
Change each phase’s Slope manually. There are default Slopes, but you can also type a more exact
calibrated one.
Select a specific Current Transformer Type, along with its full scale current. This way, the Slopes will be
calculated automatically. The CT types (correspond to their full scale output voltage) are:
1.000VRMS, 0.500VRMS, 0.333VRMS, 1mV/A RMS (1VRMS max).
•
In 3-phase measurements, you can also save CTs, by selecting for the neutral current to be
computed, or if you do not use neutral, by selecting for the 3rd phase current to be computed.
Refer to the corresponding screen shots in Chapter 16.
REMAINING SETTINGS
• Other settings to be adjusted are:
–
–
–
–
The averaging recording interval (selectable from 0.5 sec to 1 hour).
The logger’s site name.
The GPRS settings of Symmetron’s Diameson server (IP and remote port).
Only for the GSM version: the GPRS settings of the SIM card (APN, User Name, Password).
14. OPTON: ACQUISITION AND DOWNLOAD
•
•
•
After writing the desired setup in the datalogger, enable/ disable data acquisition to create
data files, stored in the 4MB memory. When enabling acquisition, a new file begins.
Files are stored in the logger’s memory in compressed form.
When downloaded, a compressed file is decompressed into two data files:
–
–
•
One file containing each current channel’s energy (Active, Reactive and Apparent) within the interval.
The sum of a column results in the corresponding energy of the entire file.
One file containing all the remaining measurements: Voltage, Frequency, Current, Power Factor,
Active, Reactive and Apparent Power.
The data files can be viewed via a text editor. Data are displayed either in plain text form or in
grid form (channel columns are apparent).
• Compressed and decompressed data files are stored in the logger’s site folder, as mentioned
in Chapter 12.
• Data download can be achieved either manually or automatically via AutoConnect software
(see Chapter 18).
MANUAL DOWNLOAD
There are 2 types of manual download:
• Download the most recent file. If Acquisition is ON, this is the current file. In this case, the
current file is firstly closed (the next file begins) and then downloaded.
• Download one or more consecutive previous files, by typing their number.
15. OPTON: OFFLINE DATA MANAGEMENT
After downloading the data files in the site folder, you can manage them offline. Opton offers
some useful tools for offline management and presentation:
•
•
•
•
Plot. View the selected channels’ plot, in up to 3 graph groups. Also, select specific
measurements (current, power factor, etc) for each channel. View values at a specific
moment with the channel units.
Refer to the corresponding screen shot in Chapter 17.
Data File Processing. Check the integrity of a folder’s files, ie check for missing or duplicate
records or if the interval is the same for all files.
Statistics. Statistics of the file’s data can appear per hour, per day, per month and per year.
Statistics include be the average values of the data (within the hour, day, month or year), the
max, min or sdv values, or sum of all values.
The sum of an energy channel results in the total energy of the entire file.
Statistics are presented via a bar graph or a dot plot.
Refer to the corresponding screen shot in Chapter 17.
Export to Excel/.CSV/.TAB file. Export a file’s data to an Excel, a comma delimited or a tab
delimited file.
16. OPTON: SCREEN SHOTS (PART 1)
Site folders and files interface
Channel Setup
Instant data display
Data Logger Status
17. OPTON: SCREEN SHOTS (PART 2)
Online plot
Dat a file plot
Data file statistics
18. AUTOCONNECT SOFTWARE
•
•
•
As stated before, data files can be downloaded manually, via Opton, via any connection.
However, data download, along with other actions as well, can be preformed automatically, in a
regular basis, via the additional free software AutoConnect.
The datalogger can perform a different action each weekday:
-
•
•
Download Data: All data files missing from the folder.
Download Status: Instant parameters, such as the current file,
the recording time remaining, etc.
Download Current Values. Get the instant channel values.
The selected action of a weekday can be performed once a day at a specific selected time, or infinite
connections can be made that weekday every as many minutes as you wish.
Besides editing the auto connections (like in Opton) via AutoConnect’s interface, you can:
- View a list of all your automatic connections and execute one or more manually.
- Check each connection’s latest status, ie if it succeeded, or failed and why.
- View the date and time of last connection and last successful download for each one.
19. MAIN APPLICATIONS AND CONCLUSION
Stylitis-Power could be used in:
•
•
•
•
Electric bill cost management in hotels, factories, etc professional spaces. Isolate your
consumptions and detect your intensive loads.
Green building certification.
Machine operation scheduling in factory.
Monitoring of substations network.
…and many more
Summing up, its main advantages are:
•
•
•
•
•
•
Energy/ power analysis of 40 independent lines or 10 3-phase ones.
CTs are the only additional accessories needed. Save CTs by selecting the neutral’s or the 3rd
phase’s current to be computed.
Variety of communication methods.
Standard Ethernet port included for remote communication and installation to your LAN.
Free operating and automatic connection software.
Portability.
about Symmetron
Our company was founded in 1989 by experienced engineers and evolved as a major
manufacturer of dataloggers and supplier of measurement equipment. Symmetron is certified
according to the ISO9001 quality system and we are proud to have deployed thousands of
measurement systems worldwide.
Address
1, Antikythiron Street
153 44 Gerakas
Greece
tel: +30-210-6034002
fax: +30-210-6034003
email: [email protected]