Basics of Digital Meters
Utility Applications
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
1 of 69
Understanding the basics
• Basic Electricity
•
•
•
•
Safety
Analog or Digital
Manual or Auto-ranging
Displays
– Range and Resolution
– Icon Symbols
– Numerical System
• Basic Measurement
– DC Volts& AC Volts
– Resistance, Capacitance
– Current
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
2 of 69
Basic Electricity
• Fluid Dynamics
– How water flows
• Electrical Theory
– How electricity flows
• Types of Sources
– AC vs. DC
– Measuring AC
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
3 of 69
Fluid Dynamics to Electrical
Theory
How water flows
• Water Pressure
• Voltage (V)
– Pressure created by a pump
or stored in towers
• Flow or Current
– The amount of water
flowing through a pipe
– Pressure applied to the
conductor
• Amperes or Amp (I or A)
– Flow of electrons in the
conductor
• Impedance
–
• Impedance or resistance
Anything that impedes the
()
flow of current
© 2007 Ideal Industries
www.idealindustries.com
– Impedes or resist the flow of
electrons
Basics of Digital Meters- Utility Applications
4 of 69
AC Source
• Alternating Current (AC)
– Most common
– Produced by a generator
– Has a positive and
negative component
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
5 of 69
DC Source
• Direct Current (DC)
– Stored energy or
derived from AC with
electronic rectifier
– Positive component
only
– Used to power
electronic devices
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
6 of 69
Understanding the Basics
• Basic Electricity
• Safety
• Analog or Digital
• Manual or Auto-ranging
• Displays
– Range and Resolution
– Icon Symbols
– Numerical System
• Basic Measurement
– DC Volts& AC Volts
– Resistance, Capacitance
– Current
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
7 of 69
Why should we be
Concerned?
• An electrician
troubleshooting a live
480V motor control center
receives serious secondand third-degree burns
from an electric arc. The
cause?
– Meter was incorrectly
switched to resistance on
his multimeter instead of
voltage.
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
8 of 69
Why should we be
Concerned?
• Two electricians are severely
burned — one fatally — while
testing for voltage in a motor
starter. One held the multimeter
while the other applied the
meter's probes to energized
terminals. One electrician's
movement caused one test lead
banana plug (energized from the
circuit under test) to pull loose
from the multimeter jack.
– The plug made contact with
the starter's grounded metal
enclosure and initiated a
high-energy arc.
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
9 of 69
Common Mistakes Made
• Test Leads in the Current
input ports and user
mistakenly makes an AC
or DC Voltage
– In this example there were
two errors made by the end
user.
• AC voltage measurement
with the Test leads in the
current input.
• Improper fuse had been
used in the meter from a
past error.
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
10 of 69
Common Mistakes Made
Current
If Voltage is measured, Leads in Current input
Protection
Fuse
• Here is what happens.
– If the unit is not fused it can lead
to damage of meter or to the
operator
– Current inputs are very low
resistance. Most current inputs
are less that 1 Ω. This is like
applying a short to the line.
– For current input protection
most DMMs’ are Fused.
– The better ones use high energy
fusing.
Ideal 61-490 series gives a probe
error message and High audible
warning if this mistake to made
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
11 of 69
Common Mistakes Made
• Function Switch in wrong
function for attempted
measurement
– Most common is AC or DC
voltage measurement with meter
in the Ohms function
– Most IDEAL meters are Overload
Protected and the protected levels
are listed in the operation
manual.
Ideal 61-700, 61-760 and 61-770 series will
give you a Hi-V light and audible warning if
you make this Mistake
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
12 of 69
Common Mistakes Made
• Using a meter in an area
above its stated rating
– Example: 2,300 voltage
measurement with an
instrument rated for Low
Voltage (600V AC/DC.)
– Overload Protected can not
protect you from this Kind
of mistake.
– Most Overload protected is
rated based on instruments
highest voltage
measurement rating.
© 2007 Ideal Industries
www.idealindustries.com
There are Bold Electricians and
Old electricians, but not many
Bold-Old ones
Basics of Digital Meters- Utility Applications
13 of 69
Common Safety Hazards
• Electrical Shock from
accidental contact from
live electrical circuits or
devices
– Use double insulated rated
leads
– Shrouded input jacks with
finger guards
– Test for proper continuity
often.
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
14 of 69
Common Safety Hazards
• High Voltage transients
from lightning, large
inductive loads being
switched on and off, or
capacitive discharge.
– Select meter with the proper
UL/IEC Category rating for
the environment that user is
going to be working in.
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
15 of 69
Certified Devices and
Equipment
• Look for tools that are
Certificated by an independent
lab,
– UL , IEC, CSA.
• Pay close attention to the safety
rating on the equipment.
– Never use equipment that is not
properly rated, Check Sp
IEC Cat ratings
• Never use accessories that are not The New UL 61010 standard
recommended or rated for your incorporates features of the IEC
601010 standard. This standard has
tester or environment.
improved safety benefits over the old
UL 1244 standard
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
16 of 69
IEC Category Ratings
• If a lighting strike was to hit your
electrical service a certain amount
of energy or impulse would travel
and be dissipated by the electrical
service.
The closer to the source of the
impulse the Higher available fault
current.
• IEC 61010 defines as four
Categories:
– CAT IV “Origin of
installation”,
– CAT III Distribution Level,
– CAT II Local level,
– CAT I Signal Level,
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
17 of 69
Safety Practices
• Visually inspect the
test tool.
– Check for any contaminate on the test
leads, tester case, holsters, and
accessories.
– Never use testers that have signs of
cracked cases, or loose components.
– Never use a tester in an environment
that is beyond the capabilities
described in the specifications
– Use manufactures recommended
replacement components, like leads
and fuses.
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
18 of 69
Safety Practices
• Visually inspect Test
Leads
–
–
–
–
–
Proper Category rating
Double insulation
Shrouded connectors
Finger guards
Insulation not damaged: not melted,
cut, cracked, stretched
– Connectors: no insulation pulled away
from end connectors
– Probe tips: not loose or broken off (too
short)
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
19 of 69
Before you get Started
• Whenever possible, work on de-energized circuits.
• Use well maintained tools and appropriate safety gear
• Safety glasses, insulated tools, insulating gloves,
flash suits, insulating mats, etc.
• Follow proper safety precautions and Lockout /Tag out practices.
• Never Work alone when making measurements on live circuits.
• Always do a performance test on your tester before making a
measurement on an unknown circuit.
– Use the 3 point method. Measure a known test point , Make the unknown
measurement, then back to the known test measurement.
– Change battery when indicated
– Check test leads regularly
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
20 of 69
Before you get Started
• Quick Check of your Test Tool
–
–
–
–
•
Digital Multimeter or Digital Clamp meter
Check the Test Leads
Place the DMM in the lowest resistance range and short the Test Leads
Move the test lead at in input of the meter at the ankle of the leads. Watch that the
resistance is less than 0.5 ohms. Do the same at the leads grip and tips. If at any
time during this test the resistance exceeds 0.5 ohms the leads my need to be
replaced.
It is also a good Idea to check the DC voltage and Ac voltage with a known
source before beginning the day.
– This doesn't negate the “Three point measurement” method.
•
•
If the unit has current, check the Fuse, and remember to replace with only the
manufacturer recommended replacement part.
Remember to always be aware of your battery usage. Digital instruments will
become erratic or can give improper readings once the power drops below
normal operating levels
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
21 of 69
Know your tester
•
•
•
•
Packaging
– Material,
• Insulation rating
• Environmental rating,
Splash proof or not.
Features
– MIN/MAX, Peak, Hold
Measurement Functions
– AC Volts, DC Volts
Capacitance, etc
– Measurement range and
Maximum input
– Input protection.
Safety
– CATegory rating, UL, CE
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
22 of 69
Electrical Testers
• Analog solenoid Testers
– Very low input impedance
– AC Voltage
– Continuity testing on some
models
– Low Accuracy and resolution
• Digital Testers
–
–
–
–
Low input impedance
AC or DC Voltage
Continuity testing
Good Accuracy and Resolution
• Added Features
– NCV (Non-contact Voltage
– Current
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
23 of 69
Digital Multimeter and
ClampMeter
• Multimeter
– Full Voltage ranges
– Full Resistance ranges
– Low current measurement
through internal shunts
• ClampMeter
– One or two Voltage ranges
– Limited Resistance ranges
– High Current through the
fixed jaw (current
transformer)
The IDEAL TightSight™
ClampMeter is also a Full
functional Digital
Multimeter
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
24 of 69
Understanding the Testers
• Basic Electricity
• Safety
• Analog or Digital
• Manual or Auto-ranging
• Displays
– Range and Resolution
– Icon Symbols
– Numerical System
• Basic Measurement
– DC Volts& AC Volts
– Resistance, Capacitance
– Current
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
25 of 69
Function Switch
• Most DMMs have rotary dial to change test
functions.
• Manual ranging DMMs
– Require manual setting of the range
• Lower cost
• Forces you to “think” before testing
• Faster response time
• Auto Ranging DMMs
– Automatically chooses the range
• Simpler to use
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
26 of 69
Understanding the Testers
•
•
•
•
Basic Electricity
Safety
Analog or Digital
Manual or Auto-ranging
• Displays
– Range and Resolution
– Icon Symbols
– Numerical System
• Basic Measurement
– DC Volts& AC Volts
– Resistance, Capacitance
– Current
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
27 of 69
Display Count
Typical displays are 2000
or 4000 counts”
–Ranges
on the dial are in
series of 2’s or 4’s
–No
Function information is
displayed.
Auto ranging meters will
have function symbol
– They are also visible on
the LCD Display
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
28 of 69
Range and Resolution
• Range determines
– The maximum reading
– The number of decimal places
displayed
• Resolution determines how
many digits after the decimal
point
– Higher resolution = more
decimal places displayed
© 2007 Ideal Industries
www.idealindustries.com
200V on the 600V Range
1V Resolution
200V on the 400V Range
0.1V Resolution
Basics of Digital Meters- Utility Applications
29 of 69
Range and Resolution
If we measure a
240V supply with
a 2000 count
Meter we would
be on the 600V
range and read
240V
© 2007 Ideal Industries
www.idealindustries.com
Range
600
200
20
2
200m
Reading
600
199.9
19.99
1.999
199.9
Basics of Digital Meters- Utility Applications
Resolution
1
.1
.01
.001
.1mV
30 of 69
Range and Resolution
Measure the same
240V supply with a
4000 count Meter
you will be on the
400 Range and have
one more digit of
resolution 240.0V
© 2007 Ideal Industries
www.idealindustries.com
Range
600
400
40
4
400m
Reading
600
399.9
39.99
3.999
399.9
Basics of Digital Meters- Utility Applications
Resolution
1
.1
.01
.001
.1mV
31 of 69
Measurement Functions
V
AC Voltage
Measures amount of AC
Electrical pressure
V
DC Voltage
Measures amount of DC
Electrical pressure
mV
Milli Volts
.001V or 1/1,000 V
A
Amperes
mA
Milli Amperes
µA
Micro Amperes
© 2007 Ideal Industries
www.idealindustries.com
Measures amount of
electron flow
.001A or 1/1,000 A
.000001A or 1/1,000,000A
Basics of Digital Meters- Utility Applications
32 of 69
Measurement Functions

))))
Ohms
Measure of the resistance to
electron flow
Diode
Device used to control direction
of electron flow
Audible Continuity Audible indication of
continuity
HZ
°F
© 2007 Ideal Industries
www.idealindustries.com
Capacitance
Device used to store electrical
potential
Hertz
Measurement of Frequency or
number of cycles per/sec
Degrees Fahrenheit Temperature Measurement
Basics of Digital Meters- Utility Applications
33 of 69
Measuring AC
• Average responding meters take
a single sample to measure the
waveform.
– Only accurate where a clean 60Hz
sine wave exists
• True RMS meters take several sample
to improve accuracy of measurement
– Found in commercial and
industrial environments
– Caused by electronic lighting,
computers Equipment and Industrial
electronic control loads
– NEC recommends True RMS meters for
testing all electrical power systems
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
34 of 69
Numerical System
Term
Numerical value
Term
Numerical value
Giga
1,000,000,000
Milli
.001
Mega
1,000,000
Micro
.000001
kilo
1,000
Nano
.000000001
Term
giga mega kilo Base milli micro nano
Symbols
Expressio
n
G
M
k
m
m
n
6
3
-3
-6
X10
X10
X10
X10
X10
X10
X10
9
9
0
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
35 of 69
Understanding the Testers
•
•
•
•
•
Basic Electricity
Safety
Analog or Digital
Manual or Auto-ranging
Displays
– Range and Resolution
– Icon Symbols
– Numerical System
• Break
• Basic Measurement
– DC Volts& AC Volts
– Resistance, Capacitance
– Current
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
36 of 69
Understanding the Testers
•
•
•
•
•
Basic Electricity
Safety
Analog or Digital
Manual or Auto-ranging
Displays
– Range and Resolution
– Icon Symbols
– Numerical System
• Basic Measurement
– DC Volts& AC Volts
– Resistance, Capacitance
– Current
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
37 of 69
Primary DMM Test Functions
• Voltage (V) - measured in volts
– Pressure created by a power supply
• Current (A) - measured in amps
– The amount of electricity flowing
through a conductor
• Resistance () - measured in ohms
– Anything that impedes the flow of
current
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
38 of 69
Taking Measurements
•
•
•
•
•
•
•
•
AC Voltage
DC Voltage
AC Current
DC Current
Resistance
Continuity
Capacitance
Frequency
© 2007 Ideal Industries
www.idealindustries.com
IDEAL Test Board
Basics of Digital Meters- Utility Applications
39 of 69
The Port Panel
• Black lead always placed
in Common Port (COM)
• Red lead is placed in Red
Port for the function to be
measured
• For Voltage connect to the
– ( VΩHz) Port
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
40 of 69
DC Voltage Measurement
• DC Voltage Measurement
• Connect the leads to the
VΩHz and COM inputs
• Select VDC or
– If manual ranging select
proper range
• For 9V, Select the 20V
range
• Measure the 9 Volt battery
– If connected to the test
board look for ( +●
Battery● -) test points.
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
41 of 69
Parallel Circuit
• In a parallel circuit,
Voltage is applied
equally to each load
connected to the circuit
– This is how our
receptacles in our homes
wired.the value
Ifare
I change
of the resistor in this
circuit will it change
the voltage across the
light???
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
42 of 69
AC Voltage Measurements
• AC Voltage Measurement
• Connect leads to the
VΩHz and COM inputs
• Select VAC or
– If manual ranging select
proper range
• For 120V, Select the 200V
Range
• Measure receptacle, or
using test points on a line
splitter
© 2007 Ideal Industries
www.idealindustries.com
Never make a Voltage measurement with
the leads of the meter in the current input
ports
Basics of Digital Meters- Utility Applications
43 of 69
Single Phase 3 Wire Meter
(Common Residential)
Class 100/200 (100/200 Amp)
4 Terminal, 240 Volt
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
44 of 69
Single Phase 3 Wire Meter
(Common Residential)
Class 100/200 (100/200 Amp)
4 Terminal, 240 Volt
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
45 of 69
Single Phase 3 Wire Meter
(Common Residential)
Class 100/200 (100/200 Amp)
4 Terminal, 240 Volt
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
46 of 69
Average vs. True RMS
• True RMS responding
– The Meter calculates
the true effective
(heating) value of the
waveform.
– Average sensing
meters will not
correctly display the
effective (heating)
value on a “nonsinusoidal waveform.
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
47 of 69
True RMS
• Measures the area under
the sine wave using a root
mean square calculation
• Gives an accurate AC
measurement when
harmonics are present
• NEC recommends True
RMS meters for testing
all electrical power
systems
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
48 of 69
Current Measurements
ClampMeter or Clamp Adapter
• AC Current
–
–
–
–
–
Measures the magnetic field around a wire
Converts measurement to an amp reading
Only a single conductor can be tested
Magnetic fields of hot and neutral cancel out
Requires a line splitter in power cords
• DC Current
– DC current is measured using a Hall Effect
• An electronic device which measure the EMI of
AC and DC current.
© 2007 Ideal Industries
www.idealindustries.com
Test & Measurement
Basics of Digital Meters- Utility Applications
49 of 69
AC Current Measurement
• AC Current Measurement
– Must be made on a single
conductor.
• Plug hairdryer into line
splitter
• Plug line splitter into
receptacle
• Clamp jaws around line
splitter
• Measure the current draw of
the hairdryer
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
50 of 69
Series Current Measurement
• In a series circuit, loads within
the circuit have an effect on
the flow of electricity to the
other devices or loads
If I increase the value of the
resistor will it effect the brightness
of light.??
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
51 of 69
Current Measurements
Series Method
• Requires an open circuit
– electrician must interrupt power
– Best to us a meter with fused inputs for safety.
• 1 to 10A Max on most DMM’s
• Primarily used to measure small Currents
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
52 of 69
DC Current Measurement
4-20mA Control Loop
DC current measurement of a 4
to 20mA control loop
• A break must be made between
the transmitter and Controller.
• Place the Test leads in the
proper input ports. And select
DC mA
– 4 mA typically corresponds to
zero
– 20 mA typically corresponds to
Full scale.
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
53 of 69
Continuity Measurement
• Continuity measurement
• Connect the leads to the
VΩHz and COM input
port
• Select the continuity
function
– Touch leads together
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
54 of 69
“OL”
Customer breaker(s)
open
“Numerical
Value”
Breaker(s) closed
“0.0 to 0.8”
SHORT
on customer wiring
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
55 of 69
Resistance Measurement
• Resistance Measurement
• Connect the leads to the
VΩHz and COM input
port
• Select the Ω ohms
Function.
– If manual ranging select
proper range
• Measure the Resistor on
the Test Board
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
56 of 69
“OL”
Customer breaker(s) open
“Numerical
Value”
Breaker(s) closed
“0.0 to 0.8”
SHORT on customer wiring
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
57 of 69
“OL”
Customer breaker(s) open
“Numerical
Value”
Breaker(s) closed
“0.0 to 0.8”
SHORT on customer wiring
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
58 of 69
Diode Measurement
• Diode measurement
• Connect the leads to
the VΩHz and COM
input port
• Select the diode function
– Place Red lead on + and black
lead on – for “Forward bias”
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
59 of 69
Capacitance
• Function used in testing
capacitors
– Storage devices that give
motors an initial energy
boost
• Capacitance is the ability
of a capacitor to hold its
charge
• Measured in
microfarads (MFD)
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
60 of 69
Capacitance Measurement
• Capacitance Measurement
• Connect the leads to the
proper input posts
– On some units this isn’t the
Volt/Ohms port
• Select the Capacitance
Function
, MFD or mF
• Measure the capacitor on
the PC board
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
61 of 69
Basic Advanced Features
• Basic of Advance
features found on most
high end DMM’s and
ClampMeters
– Hold or Data Hold
– Peak Hold
• Peak Min/Max
– Min/Max
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
62 of 69
Measurement Functions
• Functions button
operation
– Primary Function
MIN/MAX press for 1
Second
– Press MIN/MAX To
cycle through Max/Min.
• Note display
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
63 of 69
Measurement Functions
• To exit a Function
– Primacy Function
• Press for 1 second toggles
function A”ON”
• Press and hold for 2
seconds toggles function
“OFF”
– Secondary Function
• Press and hold for >2
seconds toggles function
“ON” or “OFF”
• Note display
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
64 of 69
Hold Measurement Functions
• Hold or data hold is
used to lock the
current measurement
reading on the display
– While making a
measurement, press the
Hold button. Remove
test leads and observe
the displayed reading.
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
65 of 69
Measurement Functions
• Peak Hold Records the
Maximum amplitude of a
voltage waveform.
• Peak min/max Records
the maximum and
minimum amplitude of a
voltage waveform.
Peak = RMS x 1.414
Example: 169.68= 120V x 1.414
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
66 of 69
Min/Max Measurement
Functions
• Min/Max Records the minimum and maximum value
of a measurement. Each time a new min/max level is
achieved the new value will be recorded .
– Some DMM will also indicate new recorded values by an
audible beep.
This Function is
not fast enough to
capture Power
Quality Voltage
Event.
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
67 of 69
Voltage Performance
Monitor
Key Points for comparison
•
High speed Even capture
•
Only important events are logged
•
Events are sorted by Time (log)
•
Events are sorted by Type (event)
•
Waveform shape is measured for THD
© 2007 Ideal Industries
www.idealindustries.com
Basics of Digital Meters- Utility Applications
68 of 69
Clamp-On Ground Resistance
Test
• Advantage is that the
ground electrode doesn’t
need to be disconnected
from the electrical
system.
• The jaws of the clamp
must be placed in the
electrical path of the
systems grounding wire
to the ground rod