TFD Installation and Setup
• Steve LeMay
– Field Service Advisor
Gustave A Larson Company
13200 10th Avenue North
Plymouth, Minnesota 55441
– 800-827-9508 ext 346
– 612-656-4346 (Direct)
Agenda
•
•
•
•
Installation
Set up
Fault code retrieval
Cleaning
How it works
• 24 volt power supply
• Internal bridge
rectifier
• High voltage output of
8.0 KVDC to 9.6 KVDC
• Field adjustable high
voltage output
• Collector cells coated
with conductive Ink
Pre Filter
• Stops large air born
particles
• Easy to clean by
vacuuming or washing
Field Charger
• The field charger
electrically charges
air born particles
• Cleaning by
authorized service
personnel only
Field Charger Pins
Collector Cells
• Collector cells trap
very small air born
particles
• Easily cleaned by
vacuuming or washing
with low pressure
water
• Detergents should
not be applied to the
collector cells
Collector Cells
Filter guide channel
• Easy to install
Filter Guide
Channel
Collector cell cut away
Conductive ink stops
Collector cell
section
Conductive ink
Conductive ink to
end
Collector cell internal wiring
+
-
Power Door
• Houses the electronics
• Provides access to the
pre filter, field charger
and collector cells
• Status bar LED’s, power
button, reset button,
and pre filter LED are
located on the front
Installation
• Do not install filter in discharge air stream
• Do not install filter where it can be exposed
to UV light
• Atomizing/bypass humidifiers must be
installed downstream of the air cleaner
• 28 inches clearance in front of the air cleaner
is required for service
• Turning vanes or long radius elbows are
required in the return drop to the air cleaner
Installation
• No Silicon caulk (out gassing)
• 21 & 24 inch models require a transition
between the furnace and air cleaner
• Bottom returns the furnace must be
supported( don’t set the furnace
directly on the air cleaner)
• Install the 50 VA transformer provided
with the air cleaner
• Be aware of the static pressure drops
Electrical Connections
• Replace indoor unit
transformer
• Power is supplied to air
cleaner by the indoor
unit transformer
• 10 feet of cable with a 6
pin connector is
provided
• The 6 pin connector
plugs into the power
door of the air cleaner
Wall Mount Transformer
• Wall mounted
transformer is
recommended for indoor
units other than Trane
Kit #baytrans12024a
• Voltage check is
necessary when wall
mounted transformer is
applied
Set Up Mode
• In the Set Up Mode
you can:
– Set the cleaning
interval for the pre
filter
– Set the cleaning
interval for the
collector cells
– Set the power level
Pre
Filter
Dirty
Clean
R3
Collector Cells
Dirty
R3
Power Level
Dirty
R3
R2
R2
R2
R1
R1
R1
Y4
Y4
Y4
Y3
Y3
Y3
Y2
Y2
Y2
Y1
Y1
Y1
G3
G3
G3
G2
G2
G1
Clean
G1
Clean
G2
G1
Set-Up Mode
• Enter the set up mode
by pressing and holding
power and reset buttons
for 5 seconds
• The display will indicate
how the unit is
programmed
• The factory settings
are displayed
• To change settings
press power button once
Dirty
R3
R2
R1
Factory
Settings
Y4
Y3
Y2
Y1
G3
G2
Clean
G1
Set-Up Mode
• Scroll through the
settings by repeatedly
pressing reset button
• To save the settings and
advance to the next
setting press the power
button once
• Exit the set up mode by
pressing and holding
power and reset buttons
for 5 seconds
Pre-Filter
Collection Cells
Power Level
3 Months
9 Months
9.6 KVDC
R3
R3
R3
R2
R2
R2
R1
R1
R1
Y4
Y4
Y4
Y3
Y3
Y3
Y2
Y2
Y2
Y1
Y1
Y1
G3
G3
G3
G2
G2
G2
G1
G1
G1
Dirty
Clean
Time Delays
• 10 second time delay on a call for cooling
• 90 second time delay on a call for heating
• 10 minute time delay anytime the power to
the air cleaner is turned off and on.
Pow er On Delay
100
700
90
80
600
Time in Seconds
Time in Seconds
Thermostat Call Delay
70
60
50
40
30
20
10
500
400
300
200
100
0
0
1
2
1
Normal Operation
• During normal
operation the green
LED #1 with flash
slowly when the
blower is operating
• There may be some
other LED’s on based
upon time to clean
intervals
R3
R2
R1
Y4
Y3
Y2
Y1
G3
G2
G1
Need for Service
• Three yellow flashing
LED’s indicates the
controls have detected
10 consecutive high
voltage shut downs
• Three red flashing
LED’s indicates the
controls have detected
the same fault 3 times
in a row after a high
voltage shut down
R3
R2
R1
Y4
Y3
Y2
Y1
G3
G2
G1
Fault Code Retrieval
• To enter the fault code
log
– Go into the set up mode
(press and hold power and
reset for 5 seconds)
– Press and hold reset for
10 seconds
• Display goes out
• Green LED #1 and a
combination of yellow
and red LED’s indicate
the first recorded fault
in the log
R3
R2
R1
Y4
Y3
Y2
Y1
G3
G2
G1
Fault Code Log
• Matching the pattern of LED flashes will give an indication of
what fault has been posted to the fault code log
• The column on the right of the chart will provide the
recommended service procedure for that fault
• An example is service procedure #5 is for repetitive arcing. The
service procedure is to clean collection cell and field charger
and check for arcing through plastic frame to cabinet
Fault Code Log
Power Door Test
Caution high voltage is present
for this test
• Turn the air cleaner on and
enter the set up mode
• Adjust the power setting for
normal (9.6 KVDC)
• Exit the set-up mode and
wait for green LED #1 to
begin to flash
• Connect the high voltage
probe per manufacture
instructions
• Touch the center contact of
the power door
• The voltage should read
9.6KVDC +/- 600 volts
Power Door Test
• Using a screwdriver,
jumper wire, and dry
paper
• Tape a piece of paper to
the screwdriver
extending ½” beyond the
end
• Connect the jumper wire
from the screwdriver
shaft to the ground
contact of the power
door
Cleaning
• Pre-filter cleaning
– The pre-filter may be vacuumed or washed
– It should be completely dry before reinstalling
• Collection cell cleaning
– The collection cells may be vacuumed or
washed
– Vacuum both sides
– Wash using low pressure sprayer. Warm
water will remove some residue
Cleaning
• Do Not
– Use soap or detergents on collection cells
– Immerse collection cells completely in water
– Place collection cells into a dishwasher
• If water is used in cleaning collection cells
– Slightly tap the collection cell to remove water
– The collection cell must be dry before re-installing
• Reset filter timers
– Reset pre-filter timer: press and hold the reset
button until pre-filter LED goes out (1 to 2
seconds)
– Reset collection cell timer: press and hold reset
button until collection cell LED’s go out (4 to 5
seconds)
Cleaning
• Cleaning field charger
– Field charger should be
cleaned annually
• Turn air cleaner off and
remove power door
• Bend field charge
locking tab down and
remove field charger
• Wipe face plate with
dry shop towel or
vacuum
Field charger locking tab
Cleaning
• Caution field charger
pins are sharp
– Do not bend pins
– Wear gloves
• Use a block of foam to
clean the pins
– Push the foam block over
the pin
– Rotate the foam block
– Use the foam block to
clean faceplate opening
edges
• Reinstall field charger
and bend one locking tab
Trouble Shooting
• Air Passing Through the Cleaner Emits a
Slight Sound
– Select Lower “Power Setting” in the “Set
Up” Mode to Reduce
– Minimal Impact on Cleaning Efficiency
ACCE’s Update
• Power door improvements
• Missing and incorrect components
ACCE’s Update
• Power door improvements
– New contacts are in
production
– Latch handles shorten
– Door hinge clips angle change
New contacts 1”
diameter
Door hinge clip angle change
• Task team reviewing all
aspects of door fit
– Field visits being made
– More latch improvements
– Cabinet deflection being
investigated
Latch handles shortened
Questions?