Product Range
UPS SG Series 10 kVA PurePulse® 10kW
UPS SG Series 15 kVA PurePulse® 15kW
UPS SG Series 20kVA PurePulse®
20kW
UPS SG Series 30kVA PurePulse®
30kW
UPS SG Series 40kVA PurePulse®
40kW
CE Marked, 3x380/400/415V In & Out, 50/60Hz
Page 2
GE Critical Power
SG 10-40 kVA Presentation – 2013
UPS Configuration
Double conversion technology
Designed for Mission Critical Applications
True On-Line Double Conversion
VFI technology
Voltage and Frequency Independent
Inverter output transformer for load
galvanic separation
SG CE classification: VFI – SSS – 111
VFI
Bypass
supply
Static bypass
Rectifier
Rectifier
supply
AC
Inverter
DC
Load
AC
DC
Battery bank
Voltage & Frequency Independent
Frequency Converter operation available
Class 1
SS
Output voltage THD < 8% for all loads
THDv < 2%
linear loads
THDv < 3%
non-linear loads
111
Class 1 performance
Exceeding Class 1
‘’Best in Class’’ dynamic response:
+/- 3% at load step: 0-100%-0
+/- 2% at load step: 0-50%-0
SG Series
Page 4
GE Critical Power
SG 10-40 kVA Presentation – 2013
UPS configuration
Double conversion with inverter output isolation transformer
Q2
MANUAL BYPASS
SSM
K6
RECTIFIER
INVERTER
Q1
CB4
K7
LOADS
INPUT MAINS
AUTOMATIC BYPASS
INVERTER
TRANSFORMER
CB3
BATTERY
Double conversion (VFI) technology with output isolation transformer
Automatic bypass for overloads, short circuit and UPS disturbances conditions
Manual bypass for UPS maintenance operations without load interruption
Protection safety devices integrated
- back feed protection K6 standard
Page 5
- battery disconnect CB3 standard
GE Critical Power
SG 10-40 kVA Presentation – 2013
Backfeed protection
IEC 62040-1 : ……“For fixed installation UPS, backfeed protection may be provided
internally or externally to the UPS in the a.c. input line”
Standard feature inside UPS cabinet
No additional cost required
No addition installation required
Fully compliant with IEC 62040-1
Compliance to UPS installation safety
requirements
Backfeed contactor
static bypass
Input
mains
Rectifier
Inverter
DC
AC
DC
Safer operating condition
Safer operation for end users and
service engineers
Load
AC
Battery bank
preventing feedback to the mains from the
inverter in case of mains failure and a fault
in the bypass circuit
Page 6
GE Critical Power
SG 10-40 kVA Presentation – 2013
UPS configuration
Advantages - Output Isolation Transformer
No DC component in output (galvanic isolation by transformer)
Transformer less UPS – DC components are controlled
electronically
Lower DC voltage – less number of batteries per string (30-32
blocks)
Less cost for same type of batteries and back up time
Transformer less UPS – More battery blocks, connections etc
Better short circuit capability in battery mode (bypass not available)
Transformer based UPS – 2.7 X Nominal current Ph-Ph
- 4 X Nominal current Ph-N / G
Transformer less UPS – 2.2 X Nominal current
No neutral current back to the mains in case of unbalanced load in Double
conversion mode
Better management of unbalanced load.
A Zig-Zag transformer will share an unbalanced load on the three inverter bridges
Transformer less UPS – inverter legs may see unbalanced load ( different leg
operates at different load % - Components stress level are different) improves
battery lifetime through less ripple
Better management of non linear load (low level harmonics are short-circuited)
Page 7
GE Critical Power
SG 10-40 kVA Presentation – 2013
Input performance
IGBT technology for clean input
Pure Pulse® configuration for highest input performances
PurePulse® technology for IGBT rectifier
UPS input performances
Total Current Harmonic Distortion THDi=2%
@ 100% load and 5% @ 50% load
UPS input power factor: 0.99
Constant behavior at all loads
Negligible harmonics contents at full and
partial loads
Total Input Harmonic Distortion
5%
4%
THDi
Benefit on input mains
Saving in the sizing of upfront equipment's
e.g. GenSet, cablings, circuit breakers, …
No disturbances to nearby equipment
Saving cost due to additional filters
3%
2%
1%
0%
0%
20%
40%
60%
Load
80%
100%
Page 9
GE Critical Power
SG 10-40 kVA Presentation – 2013
Input rectifier performances
Wide input window to preserve battery autonomy and lifetime
Input window
+10%
Input
frequency
Wide input voltage and frequency
windows
Limited use of battery
Preserve battery autonomy for real
input mains failures
Increase battery lifetime
50 Hz
-10%
-15%
400V
+15%
Input voltage
Soft start
Rectifier can be activated gradually,
controlling the input current
Preventing instable situation for GenSet
Avoids false trip of upfront protection
devices
Sequential softstart for parallel UPS
Soft start
UPS input current
UPS 1
100%
UPS 2
0%
time
Page 10
GE Critical Power
SG 10-40 kVA Presentation – 2013
Perfect integration with GenSet
No GenSet oversizing required
GenSet integration
Compatible with GenSet design
Saving GenSet size
(suggested GenSet vs. UPS ratio ~ 1.1)
Reducing GenSet installation space
Saving GenSet investment
GenSet system integration
GenSet integration via Customer Interface
(dedicated auxiliary contact)
Programmable functions based on GenSet
working condition (Gen on/off)
Page 11
GE Critical Power
SG 10-40 kVA Presentation – 2013
Output performance
Highest UPS output power capability
Capability to supply Inductive, Resistive and Capacitive loads
Full range power capability
Designed to supply real power for any
type of application
- inductive loads
- resistive loads
- capacitive loads
I.e. SG-CE 20kVA load capabilities:
Inductive load PF=0.9
18 kW / 20 kVA
Resistive load PF=1
20 kW / 20 kVA
Capacitive load PF=0.9
18 kW / 20 kVA
No over-sizing required to supply
resistive and capacitive loads
Suitable for modern power supply
application with unit or capacitive
power factor (e.g. new servers
generation), crest factor up to 3:1
Page 13
GE Critical Power
SG 10-40 kVA Presentation – 2013
No output voltage distortion
Best in class inoutput dynamic stiffness
Output voltage with linear + non-linear
load
No output voltage distortion with linear and
non-linear loads
Voltage distortion
- linear loads:
THDv < 2%
- non-linear loads:
THDv < 3%
Enhanced customer productivity
Improved quality of application, reducing
stress for loads supplied
Increased uptime and MTBF of customer
Reduced service intervention
output voltage
current
Output voltage with non-linear load
output voltage
current
Page 14
GE Critical Power
SG 10-40 kVA Presentation – 2013
Output Dynamic Stiffness
Best in class inoutput dynamic stiffness
Medical scanner - dynamic current
absorbtion
Best in class in output voltage variation with
load steps:
Static
: < + 1%
Dynamic at load steps 0-50-0%
: < + 2%
Dynamic at load steps 0-100-0% : < + 3%
Enhanced customer unit productivity
Improved quality of application
(i.e. medical images)
Capability to supply critical loads with high and
fast loads steps (pulsating loads)
Increased uptime and MTBF of customer
Reduced service intervention
1
ms
Voltage variation at 0–100% load step
load step 0-100%
output voltage
Page 15
GE Critical Power
SG 10-40 kVA Presentation – 2013
High Efficiency at all loads
Reduced customer operation costs and cost saving in air conditioning design
High efficiency performances
High efficiency > 92% at full and partial
loads for real benefit in operating
conditions
Energy cost saving
Reduced cost of customer equipment
operation at all loads
Air conditioning cost saving
Reducing size and cost of air condition
system
Reducing consumption and related
operating cost
Higher backup time
Page 16
GE Critical Power
SG 10-40 kVA Presentation – 2013
Superior Battery Management
Safe and protected battery management to preserve investment and UPS reliability
Charging voltage = f (battery temperature)
2.36
2.33
Volt per cell
Flexible applications
Different battery technologies applicable:
PB sealed (VRLA) - PB vented – NiCd
Wide autonomy range: few minutes …...
hours
2.30
2.27
2.24
2.21
User friendly information
Prediction of true back-up time, based
on load status
Alarm for “stop operation” to prevent
any unknown shut-down
Monitoring and control
Battery test (programmable or manual) ;
preserve UPS system reliability
Battery earth fault detection; safer
operation
for service engineer & end
user
2.18
0
5
10
15
20
25
30
35
40
Battery tem perature [°C]
Voltage temperature compensation
V
Page 17
GE Critical Power
SG 10-40 kVA Presentation – 2013
Improved serviceability
High Reliability
Improved diagnostic, High Reliability
SG Series – Improved diagnostic, High reliability
Front access (including battery)
Wave form capture capability
Fan failure detection
AC Capacitor health monitoring
Component life time counters
Dedicated supply path for bypass logic
Regulated power supply
Page 19
GE Critical Power
SG 10-40 kVA Presentation – 2013
Improved diagnostic, High Reliability
SG Series – Improved diagnostic, High reliability
Robust RPA communication (Manchester coded)
Simplified design through reduction of PCBA &
connections
Output filter capacitors – PCBA mounted, easy to
replace
Input & battery circuit breaker instead of
contactor
Robust rectifier control with input mains
diagnostic
Page 20
GE Critical Power
SG 10-40 kVA Presentation – 2013
New FLEX DSP board
Improved diagnostic capabilities
•
•
Extended modularity
Enhanced connectivity
•
Black box -> Waveform Capture
capability improved diagnostic
Higher computing capability -> more
ability to manage data
•
New digital communication – 3X
bandwidth
Faster connectivity -> up to 10x with
connectivity devices hardware
upgrade
Waveform capture
Improved reliability
•
•
•
•
•
Dedicated supply for bypass logic
Dedicated supply for connectivity channels
Redundant logic for emergency bypass
activation
Main-board integrated RPA control: RPA
board contains only interface hardware
More robust RPA communication
(Manchester coded)
Common platform
Page 21
GE Critical Power
SG 10-40 kVA Presentation – 2013
New FLEX DSP board: the black-box - Option
•
•
•
•
Waveform capture, diagnostic and trend analysis
Simultaneous acquisition of 32 channels
Sampling frequency up to 10kHz
Smart trigger capability with up to 16 indipendent trigger sources to
record only specific events with pre/post trigger data acquisition
• Buffer depth of 1000 samples per channel: each event is recorded
for 100ms @ s.f. 10kHz
• 8 buffers to record up to 8 events without losing older events – can
be extended with external USB mass storage devices
WAVEFORMS
•
Inverter voltages
•
Bypass voltages
•
Input mains voltages
•
Output voltages:
•
Output current Phases:
•
Input capacitors “Cin” voltages:
•
Inverter primary current:
•
Input current:
•
IDC current:
•
Battery current:
•
Bypass current:
•
UDC
•
Communication status RPA
•
Auxiliary status
•
SSM status
•
Fuses status
•
Phase error slave master.
Page 22
GE Critical Power
SG 10-40 kVA Presentation – 2013
EMC - Immunity
Immunity
SG-CE products design exceed IEC 62040-2 C3 level for
immunity, i.e. can withstand possible disturbances and noise
without affecting standard working conditions
IEC 62040-2 C2 – SG Series 10kVA
Immunity
SG-CE
immunity level
IEC requirements
ESD
8kV (air)
4kV (contact)
8kV (air)
4kV (contact)
Surge
2kV line to line
4kV line to earth
1kV line to line
2kV line to earth
Burst
4kV @5kHz
2kV @5kHz
RF common mode (1kHz)
10V
10V
Page 23
GE Critical Power
SG 10-40 kVA Presentation – 2013
Redundant Parallel Architecture
True redundancy with no single point of failure
Modular design
Future system expansion
Saving investment
True redundancy
No single point of failure
Decentralized bypass
Distributed parallel management
system
Redundancy loss alarm
Increased system reliability
Safe and reliable power supply for
“mission critical applications”
Increase productivity
True redundancy with no single point
of failure
Input mains
rectifier
AC
bypass
rectifier
bypass
AC
DC
battery
DC
battery
DC
DC
AC
AC
critical load
Page 24
GE Critical Power
SG 10-40 kVA Presentation – 2013
Control panel
Easy and intuitive interface
Back lit Graphic Display (LCD)
Multilanguage communication interface:
English, German, Italian, Spanish, French,
Finnish, Polish, Portuguese, Czech,
Slovakian, Chinese, Swedish, Russian and
Dutch
Synoptic diagram indicating UPS status
Command keys and parameters setting
UPS status control LED
LED - red
Stop Operation
LED - yellow
Alarm
LED - green
Operation
Page 25
GE Critical Power
SG 10-40 kVA Presentation – 2013
Customer interface
Easy integration with Building Management System (BMS)
UPS supervision capability
1x RS232 Serial Communication Port
6 programmable potential free alarm
contacts:
- D plug
- Terminals blocks
1x Emergency Power OFF contact
1x Gen-ON Input contact
1x Control Input contact
Additional interface:
SNMP Interface Card
(10/100Mbps auto-select)
MODBUS RTU Interface (RS232 or RS485)
Page 26
GE Critical Power
SG 10-40 kVA Presentation – 2013
Installation flexibility - Product options
Product Options
• Empty Battery cabinets:
• Rectifier, Bypass transformer
• RPA card, SNMP card, Modbus RTU
• iUPSGuard (Remote monitoring)
• Black – box capability
• 24V DC Power supply
• EMC filter class A (40 kVA) the 40kVA is class C2 standard as well (adding
4x ferrites)
• Customer connection kit
Page 27
GE Critical Power
SG 10-40 kVA Presentation – 2013
Product Comparison
Product Comparison
Site pro 10-40 kVA
SG Series 10-40 kVA
•
•
Rectifier topology – Thyristor based
Rectifier topology – IGBT
• Input power factor – 0.8
• Input power factor – 0.99
• Input THDi – 30%
• Input THDi – 2%
• Efficiency – Low at part load
• Robust control
• Filter Capacitor – overhang mounting
• Efficiency – Improved by 1-1.5%
• Service access – Side for battery
• Filter Capacitor – PCBA mounting
• Customer interface – Separate card
• Service access – Front/Top only
• Customer interface – embedded card
Page 29
GE Critical Power
SG 10-40 kVA Presentation – 2013
Product Comparison
Site pro 10-40 kVA
SG Series 10-40 kVA
• Power supply – not regulated AC power
• Power supply –regulated AC/DC power
• Battery disconnect – Optional
• Battery disconnect – Standard CB3
• Cooling system – One blower
• Cooling system – Fans
• No Fan failure detection
• Fan failure detection
• No Cooling redundancy
• Partial Cooling redundancy
• Enhance diagnostic capability – No
• Enhance diagnostic capability
• Galvanic isolation
• Galvanic isolation
• No Capacitor monitoring
• Capacitor monitoring
Page 30
GE Critical Power
SG 10-40 kVA Presentation – 2013
Product Comparison
Site pro 10-40 kVA
Cable connection
SG Series 10-40 kVA
• Cable kit extension available to replace Sitepro
without changing cable connections.
Page 31
GE Critical Power
SG 10-40 kVA Presentation – 2013
New SG Series.... high performances
UPS
- Increased reliability
- Better short circuit cap
Output isolation
transformer
Saving in the sizing
-Input Breaker
-Input cables
High Efficiency > 92%
Output pf –1.0
(lead to lag)
- More Output power
Clean Input < 5% THDi
Input pf – 0.99
Wide input voltage
-Inbuilt back feed
protection
Saving in the sizing
-Genset
Output V THDv <2%
- Reduce stress on load
- Stiff bus for pulsed loads
-Enhance battery life
Low Total Cost of Ownership
Page 32
GE Critical Power
SG 10-40 kVA Presentation – June 2013
SG 10-40 kVA - Applications
Process industries
Large railway organizations
Control systems
Healthcare
33
© 2012 General Electric Company
Page 34
GE Critical Power
SG 10-40 kVA Presentation – 2013
Competitive Comparison
Technology
Power range
Input PF
Input THDi
Output PF
Efficiency
IP degree of protection
Input/output
Back-feed
Foot Print
Serviciability
GE
Socomec
Riello
Riello
SG 10-40 kVA
Masterysy
Master MPS
Multisentry
NXC
Tx less with internal option
10-40 (upto 120)
0.99
<3%
0.9
up to 94% ?
20 (31 option)
3/3 & 3/1 (20 kVA)
Optional
440 x 850 x 1320
Tx less with internal option
10-40
0.99
< 4%
0.9
92.5% (with Tx)
20
3/3 & 3/1 (20 kVA)
Tx based
10-40
0.99
< 3%
1
92%
20
3/3
Standard
680 x 800 x 1450 mm
Tx based
Tx based
10-40 (up to 80)
10-800
0.99
0.92
< 3%
< 5-7%
0.9/0.8
0.9
?
92 ?
31
20
3/3 & 3/1
3/3 & 3/1
Optional
Optional
600 x 800 x 1400 mm
555 x 740 x 1400
1000 x 835 x 1400 mm (40kVA) Internal Batt upto 20kVA
Internal battery upto 40 kVA
Internal Batt upto 30kVA
Front access
Front access
Front access
Liebert
Front and back access
500 x 860 x 1240
600 x 850 x 1600 (30-40 kVA)
Front access
Page 35
GE Critical Power
SG 10-40 kVA Presentation – 2013