(Note: All the mentioned tables in this course refer to, unless otherwise specified, Low
Voltage Electrical Installation Handbook, by Johnny C.F. Wong, Edition 2004)
Chapter 2
Electrical Installation II
1
Introduction
Before detailed design and installation work of an
electrical installation commences, considerations
should be given to:
– purpose for which the installation is intended to be used, its
general structure, and its supplies;
– external influences
– compatibility of its equipment
– maintainability of the installation
Electrical Installation II
2
General Assessment
Purpose of installation
Supplies and structure of an electrical installation
–
–
–
–
–
maximum demand
diversity of installation
supply and earthing arrangement
nature of supply
circuit arrangement
Electrical Installation II
3
Maximum Demand & Diversity
Definition
– sum of all connected loads multiplied by a percentage of
loads that is likely to be used at the same time. The
percentage is known as diversity factor, i.e.
Maximum Demand = Connected Load x Diversity Factor
Electrical Installation II
4
Maximum Demand & Diversity
There is no standard methods and values for diversity
factor for every type of electrical installations. The
allowance for diversity figures given in Table 2.2 may
need increasing or decreasing as decided by the
registered electrical worker responsible for the design
of the installation.
Electrical Installation II
5
Maximum Demand & Diversity
For current demand under 400A, refer to Tables 2.1
and 2.2
For current demand over 400A, reference can be made
to Tables 2.3, 2.4 and 2.5
Electrical Installation II
6
Supply Characteristics
– Type of earthing arrangement
• TT, TN-S, or combination of both
– Nominal voltage, nature of current and frequency
– Prospective short-circuit current at the origin of the
installation
– Earth fault loop impedance external to the installation
– Supply suitability for installation, including maximum
demand
– Type and rating of the over-current protective device at the
origin of installation
– Supplies for safety services and standby purposes
Electrical Installation II
7
Types of earthing arrangements
EWR and CoP stipulate that the earthing arrangement
in Hong Kong is a TT system
However in order to minimize the rise of potential
difference between the supply company’s exposed
conductive parts and the consumer’s exposed and
extraneous conductive parts, there is a bonding
conductor connecting the electricity company’s
transformer earth point to the consumer’s main
earthing terminal.
Electrical Installation II
8
Types of earthing arrangements
Technically, this is a combination of TT and TN-S
earthing system.
However, the CoP further requires that the installation
earthing be effective even if the bonding conductor is
disconnected
Electrical Installation II
9
Nominal voltage, current and
frequency
The declared limits of the supply voltage and
frequency are:
– Low voltage: 220V+6%, 220/380V+6%
– High voltage: 11kV and 132kV – plus 10% or minus 2.5%
– Frequency: 50Hz ±2%.
Electrical Installation II
10
Prospective short-circuit current
at the origin of the installation
It is not possible for the electricity supply companies
to give an accurate value of prospective short-circuit
current as its magnitude varies with changes in infeed
cable network.
The max. prospective short-circuit current is declared
to be 40kA at low voltage side for the following
supply arrangements:
i) Feeding from a transformer provided and installed
by CLP Power or HEC
ii) Feeding from LV underground cables when
supplied by HEC
Electrical Installation II
11
Earth fault loop impedance
external to the installation
To be covered in Chapter 7
Electrical Installation II
12
External Influences
External influences
– Environmental conditions
– Utilisation of premises
– Type of building construction
Electrical Installation II
13
Compatibility
The following need to be considered carefully:
To minimised harmful effects to the supply
Transient overvoltages
Fluctuating loads
Starting currents
Harmonic currents
Additional connections to earth - Clean Earth
Electrical Installation II
14
Maintainability
To ensure CONTINUAL SAFETY
Electrical Installation II