FP5000 Feeder Protection

Download Report

Transcript FP5000 Feeder Protection

FP5000
Refer to www.eatonelectrical.com for the latest information on this constantly evolving product
FP5000 Product Overview
• Microprocessor design
combines protection,
metering and control into a
single compact package
• Flexible configuration and
programmable logic
control for custom
applications
• Easy navigation keys and
menu structure make it
simple and safe to use
• Meets ANSI, UL and CUL
standards
FP5000 Product Overview
• User Interface
– Latching cover and Password protection for security
– 4 x 20 character vacuum fluorescent display for improved
readability
– 18 status LED’s for trip, alarm, breaker status and display
mode indication
• Battery backed up trip LED for target indication even if
station is dead
– Direct access to monitoring, view settings, logs and
status/control screens
– Breaker open/close buttons can provide direct breaker
control when enabled
FP5000 Product Overview
• Hardware
– Advanced 32 bit Microprocessor design
– Compact drawout case design for easy
installation and removal
– Four currents inputs (1A or 5A)
• Measured three phase and ground currents
• Calculated residual ground current
– Four voltage inputs
• Three phase plus fourth auxiliary voltage
measurement
FP5000 Product Overview
• Hardware
– 8 optically isolated contact inputs
– 5 trip rated “a” contact outputs
• 2 outputs with circuit continuity monitoring
– 2 form c alarm contacts
• One is for relay healthy alarm
– C-H Zone Interlocking Circuitry
– Inputs and outputs are user configurable
FP5000 Protection Features
One-line Drawing
FP5000 Protection Features
• Three phase and ground overcurrent (50P-1,
50P-2, 50P-3, 51P and 50R-1, 50R-2,50R-3,51R,
50X-1,50X-2,50X-3,51X)
– Measured (X) and calculated (R) ground currents
• Negative sequence overcurrent (46-1, 46-2)
• Three phase over and under voltage protection
(27M-1, 59M-1, 27M-2, 59M-2)
• Single phase over and under voltage protection
(27A-1, 27A-2, 59A-1, 59A-2)
• Over and under frequency protection (81U-1,
81U-2, 81O-1, 81O-2)
FP5000 Protection Features
• Negative sequence over voltage
protection (47-1,47-2)
• Breaker failure (50BF)
– Internal Breaker Failure Initiation
– External Breaker failure Initiation
• Apparent and Displacement Power
factor (55A,55D)
• Four setting groups available
FP5000 Protection Features
• Zone Interlocking
– Faster fault clearing times with better zone
coordination
– Stuck breaker (breaker failure) accelerated
remote fault clearing
– Phase and ground selectable
– Extended range up to 1000’
– Works with DT3000
FP5000 Protection Features
•Zone Interlocking
•Fault @ Location 2
•Relay @ CB2 sees fault & sends
interlocking signal to upstream devices
at CB1
•Upstream devices continues to operate
on normal set time for remote backup
protection
•CB2 fast trips to interrupt fault
•If CB2 fails to interrupt fault in 10
cycles remote clearing of CB1 occurs
•Fault @ Location 1
•Relay @ CB2 does not see the fault no signal is sent to relay @ CB1
•Relay @ CB1 sees fault but does not
receive interlocking signal - Fast Trips
CB1
Zone 1
Fault 1
CB2
Zone 2
Fault 2
FP-5000 Metering Features
• RMS Load Values
–
–
–
–
–
–
Currents - Ia, Ib, Ic, IX, IR, I Average
Voltages - LL, LN, VX, LL Average, LN Average
System Power - Watts, vars, VA
Power Factor, Frequency
% THD Voltage and Current
Magnitude THD Voltage and Currents
• Current accuracy ±0.5% or ±0.025 A
• Voltage accuracy ±0.5% or ±0.02 V
• Power accuracy ±1.5% worse case
FP5000 Metering Features
• Fundamental phasor measurements
– Magnitude and phase angle of voltages
and currents
– Magnitude and phase angle of positive,
negative and zero sequence voltages and
currents
– Percent voltage unbalance and phase
rotation (%V2/V1)
– Percent current unbalance and phase
rotation (%I2/I1)
FP-5000 Metering Features
• Energy Measurements
–
–
–
–
System Watt Hours - Forward, Reverse, Net
System var Hours - Forward, Reverse, Net
System VA Hours
Start Date & Time for Energy Accumulation
• Minimum & maximum values
–
–
–
–
–
–
Phase and Ground Currents
Voltages - LL and LN
System Power
Frequency
Power Factor
time and date stamp
FP-5000 Monitoring Features
• Relay self-diagnostics and Relay Healthy
Alarm Output (failsafe operation)
– Memory and setting checks
– Calibration and A/D monitoring
– Power supply monitoring
– Watchdog timer
• Trip circuit monitoring and alarming
• Close circuit monitoring and alarming
FP-5000 Monitoring Features
• Circuit breaker monitoring and Alarming
– Breaker open/close state and indication
– Operation counter and alarm
– Breaker wear alarm (accumulated
interrupted current per phase)
– 52 auxiliary contact monitoring with 52a and
52b contact inputs connected
– Sluggish breaker operation monitoring
– Loss of Vacuum monitoring
– Stuck breaker (breaker failure)
Breaker Monitoring Logic
FP-5000 Logic & Control Features
• Breaker open and close logic with front
panel open/close control
• Power factor monitoring and cap bank
switching control
• Output contact logic gate control
• Overcurrent blocking gates
• Multiple setting group selection and
control
• Main-tie-main transfer schemes
FP-5000 Logic & Control Features
• Programmable logic control function
– Six programmable logic gates
• AND OR, NAND, NOR
• 4 programmable inputs
– Six programmable timers
• Pick up time delay
• Drop out time delay
– Two Latching logic gates
– Use internal or external signals
LOGIC_LGxState, LOGIC_TGxState
Logic Data Store:
LOGIC_BlkState
LOGIC_LGxState,
LOGIC_TGxState
LOGIC
IN1
IN2
IN3
IN4
LOGIC
PROT Data Store:
Pickup Flags
Trip Flags
PROT
Block
50z#
(9)
IN1
IN2
IN3
IN4
Block
51z
(3)
Recl
Logic
Gate
(6)
IN1
IN2
IN3
IN4
Direction
Logic Data Store:
LOGIC_LGxState
LOGIC_TGxState
LOGIC_OGxState
LG1 - LG6
CNTRL Data Store:
RecloseFlags
Sync Flags
DirectionFlags
Timer Gate
(6)
IN
RECL
LOGIC_OGxState
TG1 - TG6
On Delay
DIR
Off Delay
Cin1
Cin2
Cin3
Cin4
Cin5
Cin6
Cin7
Cin8
Zin
CIN
Input Data Store:
CinState - Cin1-8, Zin
CinBkr - 52a, 52b, BFI
RemOpen, RemClose
Reset
Set
Latch
(2)
Reset
Q1 - Q2
Relay
Test
COUT
Disarm
Comm Open/Close Bkr
Open/Close Bkr PB
BKR
TRIP1, TRIP2 Monitor In
MNTR
COMM
Breaker Data Store:
Bkr State
Bkr Operations
Bkr Accum I
System Alarm Flags
Comm Logic Flags
COUT Data Store:
Relay States
Comm Trip / Alarm Indicators
LED States
IN1
IN2
IN3
IN4
Output
Gate
(7)
OG1 - OG7
TRIP1
TRIP2
K3
K4
K5
ALM1
ALM2
Zout
FP-5000 Data Logging Features
• Event log records 100 events with date and
time stamp ( 1 ms resolution)
– Event Types
• General
–
–
–
–
Control power on/off
Breaker open/close
Reset demand, min/max, energy
Change settings
• Trip, alarm, pickup, dropout
• Input / output state change
• Self-test warning
FP-5000 Data Logging Features
• Trip log records last 16 trips
– Date & time stamp (1 ms resolution)
– Fault type, status
– Trip counter, event number, osc buffer
– Time to trip (51 elements)
– Phase currents & voltages (rms. and phasor)
– Frequency
– I/O and logic states
FP-5000 Data Logging Features
• History log records accumulated values
– Number of operating hours
– Number of trips
– Number of breaker operations
– Accumulated interrupted amps per phase
– Times powered up
– Number of setting changes
– Date and time stamp of last reset
FP-5000 Data Logging Features
• Data logger
– 1024 records in 128 blocks
– Each block: timestamp & 8 records
– Log 8 quantities in each record
• Default configuration logs currents & voltages
• Select from V, I, Power, PF, Freq, %THD, Demand, Contact
inputs/outputs
– Select logging interval from 1 s to 1 hour
– Select continuous or single pass logging
– Trigger: auto, Cin, Logic, PB, Comm.
FP-5000 Data Logging Features
• Waveform Capture
– 256 cycles of data storage
– Select Trigger: Pickup, Trip, Cin, dV/dI, Logic, PB,
Comm.
– Number of pre-trigger cycles is configurable
– Stored Parameters
– 32 samples per cycle: 4 Currents, 4 Voltages
– Once a cycle:
•
•
•
•
rms and phasor Voltages & Currents
Frequency, Fault Type
Input & Output States
Pickup, Trip, Alarm, & Logic States
FP-5000 Change Setpoints
• Protection
Setting
Group 1
Overview
FP-5000 Change Setpoints
• Phase
Overcurren
t Settings
– 51P ITOC
– 50P-1 IOC
– 50P-2 IOC
FP-5000 Change Setpoints
• Current &
Voltage
Unbalance
• Under &
Over Voltage
Protection
FP-5000 Change Setpoints
• Breaker
Failure
• Power Factor
• Over & Under
Frequency
Protection
FP-5000 Change Setpoints
• Trip 1
Output
Relay
Settings
FP-5000 Change Setpoints
• Indicator
Settings
FP-5000 Monitoring
• Metering
Overview
FP-5000 Control
• Relay Control
• Reset
Functions
• Active Setting
Group Control