Micrologic P fonctionnement - Denmark Engineering web site
Download
Report
Transcript Micrologic P fonctionnement - Denmark Engineering web site
Understanding Micrologic
Contents
Range
Protection against overloads
Protection against short-circuits
Protection against insulation faults
Hardware
Metering
Others functions
Monitoring and/or protection of loads
Load shedding and reconnection
Programmable controller
Harmonic
Asic and microprocessor self-protection
Micrologic
Range
Micrologic 6. 0 P
Measurement type
version
Current protection type
Measurement type
Current protection type
Without
A
P
H
2 : Distribution L, I
2.0
2.0 A
5 : Selective L, S, I
5.0
5.0 A
5.0 P
5.0 H
6: Selective and ground fault
L, S, I, G
6.0 A
6.0 P
6.0 H
7 : Selective and earth leakage
L, S, I, V
7.0 A
7.0 P
7.0 H
Understanding Micrologic P- 14/03- DBTP218EN
Return to contents
3
Protection against overloads
phases
LT setting
Long-time protection (i²t) of the phases and the neutral
Protect against premature ageing of cables
Adjustable setting range using rating plugs
standard : 0.4 - 1, low : 0.4 - 0.8, High : 0.8 - 1, plug OFF
Setting to within one Amp with keypad or
via Communication
Protection against risk of fire
8
Understanding Micrologic P- 14/03- DBTP218EN
4
Protection against overloads
neutral conductor
Neutral protection
Adjustment :
by three position dial on the 4th pole : 4P 3D, 3D+N/2, 4P 4D
by keypad : OFF, 1/2, Full, 1.6 (3 pole breaker only)
Settings :
N/2 : IrN = 1/2 IrP, IsdN = 1/2 IsdP, IiN = IiP, IgN = IgP
1.6N : IrN = 1.6 IrP, IsdN = 1.6 IsdP, IiN = IiP, IgN = IgP
Oversized neutral protection
protection against 3rd-order harmonics summed up in the neutral conductor
3Pole breaker only
Understanding Micrologic P- 14/03- DBTP218EN
5
Protection against overloads
3rd harmonic in neutral conductor
Understanding Micrologic P- 14/03- DBTP218EN
6
Protection against overloads
IDMTL
Long-time protection of the phases IDMTL type
(Inverse definite minimum time lag)
High voltage fuse
Extremely inverse time
Very inverse time
Standard inverse time
Definite time
Improvement of discrimination with HV fuses
Better protection of switchgears
Understanding Micrologic P- 14/03- DBTP218EN
Return to contents
7
Protection against short-circuits
ST pick-up
ST delay
Inst.
pickup
Short-time protection
For low impedance short-circuits (80% of faults)
I²t ON to improve discrimination with downstream protection, inverse time
protection up to 10Ir
Instantaneous protection
For solid short-circuits
N1 and H1 breaker : OFF position inhibits the instantaneous protection
H2, H3 and L1 breaker : OFF postion = DIN value (shown on screen)
RMS measurement with 20ms fixed time delay
Protection against risk of damage
Understanding Micrologic P- 14/03- DBTP218EN
8
Protection against short-circuits
Zone selective interlocking (ZSI)
Principle :
ZSI enables the control units to
communicate with each other. The system is
able to locate the short circuit or ground fault
and clear it.
Functionning :
ZSI allows the circuit breaker to ignore its
preset delay when necessary. The fault is
cleared by the nearest upstream circuit
breaker with no intentional time delay.
Advantages :
Faster tripping time without sacrificing
coordination
Limitation of system stress by reducing
amount of let through energy.
Maximum : 100 circuit breakers interconnected
whatever the configuration
Understanding Micrologic P- 14/03- DBTP218EN
Return to contents
9
Protection against insulation faults
Ground fault
Ground fault protection
Micrologic 6.0P
Made mandatory by NEC
Residual current
Source Ground Return
Ig
Prevent risk of fire
Understanding Micrologic P- 14/03- DBTP218EN
10
Protection against insulation faults
Earth leakage
New
Earth-leakage protection
Understanding Micrologic P- 14/03- DBTP218EN
Micrologic 7.0P
Mandatory per standards NFC 15100 and IEC 364
In a TT system, protects property against low level fault currents
In a TNS system, protects installations where long cables are installed
Return to contents
11
Hardware
Principle and power supply
ZSI
M2C/M6C
ASIC
Mitop
Basic
protection L S I G V
Synchronous
Exchange data
Air CT
Isolation
Plugs :
Calibre/
perform.
Opto
Com
Iron CT
Trip unit
power supply
Standard Internal voltage sensor <690v
or
optional external voltage sensor for
µP power supply and measurement
Understanding Micrologic P- 14/03- DBTP218EN
COM
Module
Microprocessor
Additional functions
(monitoring, measurement,
analyses...)
Optical
coupling
Power supply
Surplus
Optional external 24V DC power supply for :
programmable contact power supply and
when breaker is open :
•Powers display,
•Identification, adjustments through “Com” module
Test
kit
24V DC
BUS
power
supply
Return to contents
12
Metering
Principle
Samples
Refresh
2 500,0
2 000,0
Sampling
1 500,0
1 000,0
Samples @ 625 µs
544µs
0,0
-500,0
-1 000,0
-1 500,0
-2 000,0
-2 500,0
0,0000
0,0020
0,0040
0,0060
0,0080
0,0100
0,0120
0,0140
0,0160
0,0180
0,0200
t (sec)
1s
Samples of 6 cycles (32 points per cycle)
2 500,0
2 000,0
1 500,0
1 000,0
500,0
I (Amps)
I (Amps)
500,0
0,0
-500,0
-1 000,0
-1 500,0
-2 000,0
-2 500,0
0,0000
0,0200
0,0400
0,0600
t (sec)
0,0800
0,1000
0,1200
1s Integration
Instant. data
15 s (sliding)
5 to 60 min Integration
Demand data
5..60 min (fixed)
Understanding Micrologic P- 14/03- DBTP218EN
Return to contents
13
RMS measurement
Sampling frequency :
1838Hz
One measurement point every
544µs
36 points per cycle
10ms
RMS value calculation
20ms
36
RMS
( X ²)
1
36
Understanding Micrologic P- 14/03- DBTP218EN
14
Others functions
Principle
Meter
Instant. data
Demand
Monitor
IRMS
P Q S
EP EQ
Iavg
Pavg
Min / Max
Thresholds
(pickup & dropout)
Max I1
:
Min f17
Programmable
Controller
Logging:
Data Logs
Historical Data
Maintenance Data
Relay Activation
M2C/M6C
Breaker trip
Mitop
Understanding Micrologic P- 14/03- DBTP218EN
Return to contents
15
Demand measurements
fixed or sliding window
fixed window
Measurement of active reactive and
apparent power
time intervals programmable
between 5mn and 1h
values are refreshed at the end of
the time interval
Sliding window
Measurement of current and active
reactive and apparent power
time intervals programmable
between 5mn and 1h
values are refreshed every
15 sec
sliding
fixed
5mn to 1h
t
15s
Understanding Micrologic P- 14/03- DBTP218EN
16
Power factor PF
Power factor
PF = P/S
P: active power
S: apparent power
apparent
power S
reactive power
Q
kVA
kvar
active
power P
kW
Nota : cos ф= P1/S1
P1 : Fundamental active power
S1 : Fundamental apparent power
Understanding Micrologic P- 14/03- DBTP218EN
17
Power factor PF
Sign convention
Reactive Power
Reactive Power
Reactive Power
Watts -
Watts +
Watts -
Watts +
Watts -
Watts +
VArs +
VArs +
VArs +
VArs +
VArs +
VArs +
P.F +
P.F -
P.F +
P.F +
P.F -
P.F +
Active Power
Active Power
Active Power
Watts -
Watts +
Watts -
Watts +
Watts -
Watts +
VArs -
VArs -
VArs -
VArs -
VArs -
VArs -
P.F -
P.F +
P.F +
P.F -
P.F -
P.F +
IEEE :
IEEE altenate :
IEC :
PF sign = - Q sign(P/S)
PF sign = Q sign(P/S)
PF sign = sign(P/S)
Understanding Micrologic P- 14/03- DBTP218EN
18
Monitoring and/or protection of loads
based on current, voltage, power, frequency
• Current and voltage unbalance
• Maximum current (per phases & neutral)
• Minimum / maximum voltage
•
Minimum / maximum frequency
• Reverse power
• Phases rotation
Understanding Micrologic P- 14/03- DBTP218EN
19
Monitoring and/or protection of loads
Principle of operation
variable
T1
Activation
threshold
T2
Deactivation
threshold
t
Alarm generated
by Micrologic
Understanding Micrologic P- 14/03- DBTP218EN
20
Monitoring and/or protection of loads
Current unbalance ANSI 46
Application
Protect rotating machines (motors,
generators) operating on balanced threephase supplies against ageing and slowing
Balance single-phase loads on threephase distribution systems
Detect phase loss
Principle
the function compares the current
unbalance to the threshold previously set
by the user, for a time greater than the
time delay
Example
I1 = 2500A I2 = 4000A I 3 = 3400A
Iaverage. = 3300A
Emax = I1 - Iave. = 800A
DI = Emax /Iaverage = 24%
I average
E max
I1
activation
threshold
activation time
delay
deactivation
threshold
deactivation
time delay
I2
I3
setting range
adjustment steps
accuracy
5% to 60% of I
average
1%
-10% to 0%
1 to 40s
1s
-20% to 0%
5% to activation
thresold
1%
-10% to 0%
10 to 3600s
1s
-20% to 0%
Understanding Micrologic P- 14/03- DBTP218EN
21
Monitoring and/or protection of loads
Maximum current per phase and N
Application
Obtain the maximum current
demand in the presence of major
load fluctuations (welding machines,
crushers, hoists)
Principle
This function calculates the
maximum demand value of the
current in each Ph and Neutral over
a sliding time interval.
The interval can be adjusted
between five minutes and one hour.
The value is refreshed every 15s
I max
demand
t1
t2
setting range
adjustment steps
accuracy
0.2In to In
1A
+/- 6.6%
15s to 1500s
15s
-20% to 10%
deactivation
threshold
0.2 In to activation
thresold
1A
+/- 6.6%'
deactivation
time delay
15s to 3000s
15s
-20% to 10%
activation
threshold
activation time
delay
Understanding Micrologic P- 14/03- DBTP218EN
22
Monitoring and/or protection of loads
Voltage unbalance ANSI 47
Application
Protect loads against vibrations,
temperature rise and premature
ageing
Principle
The function compares the voltage
unbalance to the threshold
previously set by the user, for a time
greater than the time delay.
Example
U12 = 330v
U23 = 390v
U31 = 10V
U average. = 243v
Emax = U31 - U average. =233v
DU = Emax /U average. = 96%
U average
E max
U12
activation
threshold
activation time
delay
deactivation
threshold
deactivation
time delay
U23
U31
setting range
adjustment steps
accuracy
2% to 30% of U
average
1%
-20% to 0%
1s to 40s
1s
-20% to 0%
2% to activation
threshold
1%
-20% to 0%
10s to 360s
1s
-20% to 0%
Understanding Micrologic P- 14/03- DBTP218EN
23
Monitoring and/or protection of loads
Minimum voltage ANSI 27
Application
Protect motors against voltage drops
resulting in loss of torque and a
major increase in the current drawn
by the motor
Check the output voltage of a
generator…
Principle
The function is activated when one
of the phase to phase voltages is
below the threshold set by the user,
for a time greater than the time
delay.
The function is desactivated when all
3 phase are above the threshold.
U12 U23 U31
Activation threshold
U min
U12 U23 U31
dectivation threshold
U min
setting range
adjustment steps
accuracy
100V to Umax
activation
threshold
5V
- 5% to 0%
activation time
delay
1.2s to 5s
0.1s
0 to 20%
deactivation
threshold
Activation
thresold to Umax
activation
threshold
5V
'- 5% to 0%
deactivation
time delay
1.2s to 36s
0.1s
0 to 20%
activation
threshold
Understanding Micrologic P- 14/03- DBTP218EN
24
Monitoring and/or protection of loads
Minimum voltage ANSI 27
U
U max activation threshold
(maxi 1200V)
U min deactivation threshold
U min activation threshold
(mini 100V)
T2
T1
100V
Alarm
t
Understanding Micrologic P- 14/03- DBTP218EN
25
Monitoring and/or protection of loads
Maximun voltage ANSI 59
Application
Protect loads (motor and
transformer) against abnormally high
voltages that can result in
irreversible damage
Avoid saturation of transformers
Principle
The function is activated when one
of the phase to phase voltages is
above the threshold set by the user,
for a time greater than the time delay
The function is desactivated when all
3 phases are under the threshold
U12 U23 U31
Activation threshold
U max
activation
threshold
U12 U23 U31
deativation threshold
U max
setting range
adjustment steps
accuracy
Umin activation
threshold to 1200V
5V
-0% to +5%
0.1s
0% to +20%
5V
-0% to 5%
0.1s
0% to +20%
activation time
1.2s to 5s
delay
deactivation
100V to activation
threshold
threshold
deactivation
1.2s to 36s
time delay
Understanding Micrologic P- 14/03- DBTP218EN
26
Monitoring and/or protection of loads
Maximum voltage ANSI 27
U
1200V
T1
U max activation threshold
(maxi 1200V)
T2
Deactivation threshold
U min activation threshold
(mini 100V)
Alarm
t
Understanding Micrologic P- 14/03- DBTP218EN
27
Monitoring and/or protection of loads
Reverse power ANSI 32P
t
Application
Protect diesel engines from generators
operating as motors
marine applications, generator
sets…
Avoid power transfers between two
parallel-connected sources
Principle
The function is activated when the active
power flowing in the direction opposite set
by the user is greater than the activation
threshold for a time greater than the time
delay.
Activation
Reconnection
Deactivation
Load
shedding
Reverse power
P kW
setting range
activation
5kW to 500kW
threshold
activation time
0.2s to 20s
delay
deactivation
5kW to activation
threshold
threshold
deactivation
1s to 360s
time delay
adjustment steps
accuracy
5kW
+/-2.5%
0.1s
0% to 20%
5kW
+/-2.5%
0.1s
0% to 20%
Understanding Micrologic P- 14/03- DBTP218EN
28
Monitoring and/or protection of loads
Minimum frequency ANSI 81
Application
Check the frequency of a generator
Check the frequency across the
terminals of a motor
Avoid saturation of transformers
following a drop in frequency
Principle
The function is activated when the
frequency exceeds the set threshold
for a time greater than the time delay
setting range
adjustment steps
accuracy
activation
threshold
45 to Fmax
activation
threshold
0.5Hz
+/-0.5Hz
activation time
delay
1.2s to 5 sec
0.1s
0% to 20%
deactivation
threshold
activation
threshold to Fmax
activation
threshold
0.5Hz
+/-0.5Hz
deactivation
time delay
1.2 to 36s
0.1s
0% to 20%
Understanding Micrologic P- 14/03- DBTP218EN
29
Monitoring and/or protection of loads
Minimum frequency ANSI 81
F
F max activation threshold
(maxi 540Hz)
T2
F min deactivation threshold
T1
F min activation threshold
(mini 45Hz)
45Hz
Alarm
t
Understanding Micrologic P- 14/03- DBTP218EN
30
Monitoring and/or protection of loads
Maximum frequency ANSI 81
Application
Check the frequency of a generator
Check the frequency across the
terminals of a motor
Principle
The function is activated when the
frequency exceeds the set threshold
for a time greater than the time delay
setting range
adjustment steps
accuracy
activation
threshold
Fmax activation
threshold to 540Hz
0.5Hz
+/-0.5Hz
activation time
delay
1.2s to 5 sec
0.1s
deactivation
threshold
45Hz to activation
threshold
0.5Hz
deactivation
time delay
1.2 to 36s
0.1s
0% to 20%
+/-0.5Hz
0% to 20%
Understanding Micrologic P- 14/03- DBTP218EN
31
Monitoring and/or protection of loads
Maximum frequency ANSI 81
F
540Hz
T1
F max activation threshold
(maxi 540Hz)
T2
F max deactivation threshold
F min activation threshold
(mini 45Hz)
Alarm
Understanding Micrologic P- 14/03- DBTP218EN
32
Monitoring and/or protection of loads
Phase rotation
Application
Avoid reversed rotation of motors
Check on coupling between generator and
distribution system (phase sequence)
Principle
The function compares the actual phase
sequence with the selected sequence
Alarm only
Not available if the 400 Hz frequency is set
F2
F1
F3
Range of adjustment
D F
activation time
delay
deactivation
time delay
F1,F2, F3 or F1 , F3 , F2
0.3s
0.3s
Understanding Micrologic P- 14/03- DBTP218EN
33
Load shedding and reconnection
based on current
t
Application
Ensure the continuity of service of
priority circuits by disconnecting nonpriority loads
reconnection
Principle
The function is activated when the
current exceeds the set threshold for
a time greater than the time delay
shedding
I
setting range
adjustment steps
accuracy
50 to 100% of Ir
1%
+/-6%
20% to 80% of Tr
1%
-20%+0%
deactivation
threshold
30%Ir to activation
threshold
1%
+/-6%
deactivation
time delay
10s to 600s
1s
-20%+0%
activation
threshold
activation time
delay
Understanding Micrologic P- 14/03- DBTP218EN
34
Load shedding and reconnection
based on power
P kW
Application
Ensure the continuity of service
of priority circuits by
disconnecting non-priority loads
10MW
Principle
The function is activated when
the power exceeds the set
threshold for a time greater
than the time delay
100 kW
Activation
Deactivation
t
Alarm
shedding
reconnection
setting range
adjustment steps
accuracy
200kW to 10MW
50kW
+/-2.5%
10s to 3600s
10s
-20%+0%
deactivation
threshold
100kW to
activation
threshold
50kW
+/-2.5%
deactivation
time delay
10s to 3600s
10s
-20%+0%
activation
threshold
activation time
delay
Understanding Micrologic P- 14/03- DBTP218EN
35
Programmable controller
Alarms and relay outputs with distinct thresholds
Alarm
on supervisor via Com module
activation and desactivation after a
programmable time delay
M2C or M6C relay outputs
without latching ==> follows the
state of the alarm
with temporary latching
programmable from 1s to
6mn
with permanent latching ==> needs
a resetting
Activation
T1
Deactivation
T2
t
Alarm
Relays without latching
Relays with temporary
latching
Relays with permanent
latching
from 1s to 360s
possible Resetting
Reset
Understanding Micrologic P- 14/03- DBTP218EN
36
Programmable controller
Alarms and relay outputs with identical thresholds
Alarm
on supervisor via Com module
activation and desactivation after a
programmable time delay
M2C or M6C relay outputs
without latching ==> follows the
state of the alarm
with temporary latching
programmable from 1s to
6mn
with permanent latching ==> needs
to be reset
Activation/
T1
T2
Deactivation
Alarm
Relays without latching
Relays with temporary
latching
Relays with permanent
latching
from 1s to 360s
possible resetting
Reset
Understanding Micrologic P- 14/03- DBTP218EN
37
Harmonic
Definition
A periodic signal is a combination of :
The original sinusoidal signal at the
fundamental frequency
Other sinusoidal signals (the harmonics)
with frequencies that are whole-number
multiples of the fundamental frequency
A DC component, where applicable
Understanding Micrologic P- 14/03- DBTP218EN
Return to contents
38
Harmonic
Origin and effects
Origin
Harmonics are caused by non linear loads such as :
Welding machines
arc/induction furnaces
Variable speed drive
office equipment (computer, copy machine, neon lighting…)
Effects
The flow of harmonics in distribution systems can cause serious problems such as :
Increased currents (oversized neutral)
Additional losses and premature aging
Disturbances to loads due to voltage harmonics
Disturbances in communication networks
Understanding Micrologic P- 14/03- DBTP218EN
Return to contents
39
Harmonic
Quality indicators
These indicators are the indispensable tools used to determine any required corrective action :
Measurement of the fundamental
Phase displacement of the fundamental
Harmonic distorsion THD
cos ф, power factor
K factor, crest factor
Distorsion power, distorsion factor
Amplitude spectrum up to order 31 st
Displacement spectrum
Understanding Micrologic P- 14/03- DBTP218EN
Return to contents
40
Harmonic
Total Harmonic Distortion
Current THD%
Current per phase
Neutral current
Voltage THD%
Phase to phase voltage
Phase - Neutral voltage
Understanding Micrologic P- 14/03- DBTP218EN
41
Harmonic
Fast Fourier Transfert
Current harmonics
each phase plus neutral
up to 31st order
Voltage harmonics
phase to phase
phase to Neutral
up to 31st order
Understanding Micrologic P- 14/03- DBTP218EN
Return to contents
42
Harmonic
Waveform capture (WFC)
Triggered manually
4 cycles
magnitude I : [ 0- 1.5 In]
magnitude V: [0- 690V]
64 points /cycle
Triggered on event (alarm > 1s)
4 cycles (on supervisor)
magnitude I : [ 0- 1.5 In]
magnitude V: [0- 690V]
64 points /cycle
triggered by a fault
11/13 cycles (50/60 Hz)
magnitude I : [ 0- 20 In]
magnitude V: [0- 690V]
18/15 points /cycle (50/60 Hz)
WFC available through the COM option only
Understanding Micrologic P- 14/03- DBTP218EN
43
Asic and microprocessor self-protection
ASIC
Self protection :
- temperature
- power supply
deficiency
µPro
Data
exchange
reading
Asic
watchdog
Auto-test
µPro &
automatic
reset
Maintenance log
time recording :
Asic maxi temperature
ASIC error code
Understanding Micrologic P- 14/03- DBTP218EN
44
Asic and microprocessor self-protection
ASIC self protection
resulting in a circuit breaker tripping :
excessive temperature >120°
ASIC power supply deficiency (overvoltage)
Indication :
LED Ap « ON »
display of error code on LCD screen
Events log recording ===>supervisor
µP self protection
never trip the circuit-breaker
Memory check sum
Time-out
Detection by the µPro of a serial link failure between µP and the ASIC
Indication :
Events log recording ===>supervisor (if communication still healthy)
Understanding Micrologic P- 14/03- DBTP218EN
45
That ‘s all for today !
Understanding Micrologic P- 14/03- DBTP218EN
46