ISC Learning center
E.Lighting - Dardo Plus system
4 - Portable Testing tool: Syscon
The Syscon kit
Control device Syscon
User guide
External power supply: 230 V AC input / 9 V DC out
Strap
Cable of external connexion
Schneider Electric - LSB - Bruno MARQUET – 06-2011
2
Functioning: What can we check?
● Syscon inspection equipment:
TEST, END TEST, REST MODE, RESTORE.
● To send the TEST command: press the TEST button.
Wait a few seconds, the connected luminaires come ON.
● To see the state of the light: press ACTION and wait few seconds
● Every time you press READ, the state of the luminaire is displayed.
● With the light scan display function, check that the state envisaged
for every light point corresponds with the project details
● the light scan is completed when the two displays indicate
the “U” characters.
● To end the TEST: press END TEST and wait few seconds
> turn luminaires OFF.
Schneider Electric - LSB - Bruno MARQUET – 06-2011
3
Functioning: Indications
Autonomy: Green LED:
Indication than the luminaire
is a three-hour duration.
Green LED switch OFF: 1-hour duration.
Mains present: Yellow LED:
Indication than the luminaire detected has
the recharging power supply line present.
Yellow LED switch OFF: no recharging
power supply line not present.
Tube OFF: Red LED:
Indication if the luminaire has the tube OFF.
Red LED switch OFF: tube ON.
Red LED ON: light tube OFF
Red LED OFF: light tube ON
Yellow LED ON: light power supply line present
Yellow LED OFF: light power supply line absent
Green LED ON: Dardo circuit set up for 3 h
Green LED OFF: Dardo circuit set up for 1 h
Schneider Electric - LSB - Bruno MARQUET – 06-2011
Tens - units display:
Red tens and units displays indicate the decimal
place assigned to the luminaire detected.
Luminaires numbers range from 00 to 99
(100 numbers).
The full stop remains displayed and indicates
the presence of the display
power supply.
4
Functioning: Indications
Three-colour battery LED:
Green LED: indicates the presence
of the recharging network.
Orange LED: indicates normal battery
functioning.
Red LED: indicates that the battery
autonomy for the Syscon is low and gives the
operator advance warning to turn it OFF.
OFF: Press Off to have equipment OFF.
No effect when the recharging network is
present.
ON: Press On to have equipment in battery
mode. No effect when the recharging network
is present, the equipment stays ON.
RESET: Reset all types of command,
restoring the stand by conditions (two full
stops).
Schneider Electric - LSB - Bruno MARQUET – 06-2011
5
Functioning: Indications
ACTION:
Start the acquisition from the connected line.
Detect the luminaire data and save it in the memory.
READ:
Give the data of each luminaire reading it from
memory.
TEST:
Test the luminaires connected to the Dardo Line.
END TEST:
To end the TEST condition for the luminaire
connected to the Dardo Lines.
Restore the initial condition (two full stop).
REST MODE:
To turn OFF the luminaire if the luminaires have
the line not present condition.
RESTORE:
In the REST MODE and line absent condition,
restore the normal emergency condition
by turning ON the luminaires.
Schneider Electric - LSB - Bruno MARQUET – 06-2011
6
Connection
● Top side connection
● 6-pin M5 male connector (Dardo Line).
● Two PF1 and PF2 fuse holders.
● At the other end of the connection cable are 2 Crocodile clips.
These allow to place the Syscon tool on the bus in place
of the Dardo control unit.
Schneider Electric - LSB - Bruno MARQUET – 06-2011
7
Connection
● Bottom side connections
● At the bottom, connector for the M1 recharging power supply unit.
● A M2 2-pin male connector for an external battery.
Schneider Electric - LSB - Bruno MARQUET – 06-2011
8
Preliminary checks
Luminaires numbering
Recharging line presence or absence 230 V
State of Luminaires (ON/OFF)
Autonomy (1 hour / 3 hours)
Schneider Electric - LSB - Bruno MARQUET – 06-2011
9
Attention
● Check there are no voltage in the communication line
before connection.
● use a V AC range multimetre to check:
● no voltage:
– Between the positive on the Dardo Line and the earthing
– Between the negative on the Dardo Line and the earthing.
● no short circuit:
– between the positive and the negative on the line.
For problems: check for any incorrect connections
with the energy sources.
Schneider Electric - LSB - Bruno MARQUET – 06-2011