Square D® Power Management

Download Report

Transcript Square D® Power Management

Feeder and Main Application
PowerLogic®
PM800 Series
PM800 Series Power Meters
● Affordable, compact, and modular
● Designed for application on feeders and mains
● Easy installation
● High-visibility display
● High accuracy measurements
● Power quality analysis
● Extensive data logging, trending and forecasting
● Custom alarming with time stamping
● Expandable I/O
● Multi-port serial and Ethernet communications
Schneider Electric – Square D PowerLogic PM800 series power meter
2
Typical applications
● Power quality compliance monitoring
● Disturbance and harmonic analysis
● Energy metering, cost allocation and sub-billing
● Demand and power factor control
● Load studies and circuit optimization
● Equipment monitoring and control
● Preventive maintenance
● Integrated utility metering
Schneider Electric – Square D PowerLogic PM800 series power meter
3
PM800 series power meters
● Install into new equipment or retrofit into existing installations
● Three models satisfy a range of applications
Schneider Electric – Square D PowerLogic PM800 series power meter
4
Functionality
The PowerLogic power monitoring family
CM4000
Apply to Critical Power
CM3000
PM800
Apply to Mains and Feeders
• Comprehensive Power Metering
• Basic Power Quality
• Onboard data logging
• Compact Design
• Disturbance waveform Capture
Schneider Electric – Square D PowerLogic PM800 series power meter
Apply to Mains and
Key Feeders
• Extensive Power Quality
• Transient Detection (CM4-T)
• Wave shape fault recording
• Advanced Power Monitoring
• Variety of I/O options
• Power Quality with
disturbance detection and
100 ms event recording
• Highest revenue accuracy
• GPS time synchronization
• Onboard data logging with 8
MB of memory
• Disturbance direction
detection
5
Part of a complete solution
● Power meters are a key component in a complete PowerLogic power
monitoring and control solution that provides transparent access to all of your
intelligent devices.
● Software
●Powerlogic PowerView
●Powerlogic System Manager
●Powerlogic ION Enterprise
●Powerlogic ION EEM
● Data Communications
●EGX 100
●EGX 400
●Modems
● Intelligent Devices
●Circuit Monitors
●Power Meters
●Low Voltage breakers
●Med voltage relays
●Other Modbus devices
Schneider Electric – Square D PowerLogic PM800 series power meter
RS-485 port, RS485/RS232 port (on
optional remote display) and optional
Ethernet port all provide Modbus
communications to power management
software or easy integration into
Building Automation and SCADA
systems.
6
PowerLogic systems help you control the
cost, quality and reliability of your utilities
● Since 1989, PowerLogic systems have helped customers improve
productivity and profitability by helping them to …
Schneider Electric – Square D PowerLogic PM800 series power meter
7
… Measure and control energy costs
● Verify utility bills; participate in utility rate reduction programs
● Verify savings resulting from equipment upgrades, energy efficiency
programs, or performance contracts
● Perform demand and power factor control; reduce demand charges and
reveal energy waste
● Allocate or sub-bill energy costs
● Measure all utilities (water, air, gas, electric, etc.) and optimize energy
procurement
Save 2-4% of utility bills,
by knowing where and how
energy is being used.
Schneider Electric – Square D PowerLogic PM800 series power meter
8
… Optimize equipment use
● Prolong asset life by balancing loading, and measuring and reducing
harmonics and other factors that cause heating and shorten
equipment life
● Maximize the use of existing
capacity and avoid unnecessary
capital purchases by understanding
loading and identifying spare
capacity on existing equipment
Save 2-5% on operating costs, by optimizing
utilization and eliminating unnecessary
equipment purchases.
Schneider Electric – Square D PowerLogic PM800 series power meter
9
… Improve power quality and reliability
● Receive early warning of impending problems
● Accurately detect and capture magnitude and duration of power
quality events
● Diagnose and isolate the cause of power-quality-related equipment or
process problems
● Verify reliable operation of power distribution and mitigation equipment
● Proactively assess power quality trends and conditions to identify
vulnerabilities
● Baseline power quality conditions and verify improvements as a result
of equipment upgrades
Save up to 10% or more in productivity
and resources by improving power quality
and reducing downtime.
Schneider Electric – Square D PowerLogic PM800 series power meter
10
Summary of Key Features
PM820
PM850
PM870
n
80
1
n
n
n
31st
0.2s
n
n
n
n
800
3
n
n
n
63rd
0.2s
n
n
n
n
n
n
800
3
n
n
n
63rd
0.2s
n
n
n
Disturbance Detection/Alarms
Advanced Waveform Capture
EN50160 Evaluation
Standard Waveform Capture
Trending and Forecasting
Custom Data Logging
Size (kb)
Custom Logs
Billing Log
Shift Energy Log
Alarm Log
Individual Harmonics
Accuracy IEC 60687 Class
V, I, Energy, Demand, THD
Alarms, RS485, Option
Modules
Schneider Electric – Square D PowerLogic PM800 series power meter
11
Physical features
● Maintenance and alarm icons —
view alarm status at the meter
● Easy-to-read, backlit LCD display
● Anti-glare, scratch resistant
● Displays four values simultaneously;
view three phases and neutral
● View summary screens and bar chart
displays to see a snapshot of your
system
● Intuitive, self-guiding menus are easy
to use without training
● Multi languages support
The power meter’s three display options—
integral display, no display, or remote display—
let you purchase only what you need.
Schneider Electric – Square D PowerLogic PM800 series power meter
12
Physical features (continued)
● KY Out/Digital IN
● Control voltage
● Voltage Inputs — 600 VAC direct
connect; eliminates the need for PTs
in most cases
● Remote Display/Option Module
connector
● Current inputs — rated at 15A, able
to withstand overcurrents from CTs
● RS-485 communications,
configurable for 2-wire Modbus-RTU
or -ASCII
● Communicate to PowerLogic
software
● Integrate into BAS or SCADA
systems
● Download firmware updates to
keep up-to-date with the latest
features
Schneider Electric – Square D PowerLogic PM800 series power meter
13
Physical features (continued)
● Remote display option:
● Install the meter inside the low voltage cabinet when local regulations do not
permit over 120 V on panel doors.
● Can be used to configure meter when a permanent display is
not required.
● Provides an additional RS232/485 communications port, configurable for 2or 4-wire support.
The configurable
communications port on the
remote display lets you add the
power meter to an existing 4wire RS-485 daisy-chain
without a converter.
Schneider Electric – Square D PowerLogic PM800 series power meter
14
Physical features (continued)
● Compact design - 96 x 96 x 70mm (depth inside panel with Modbus
and 2 I/O)
● Shallow depth saves panel space
● Flush panel mount with a 92 x 92mm cutout
● International standard design
● Retro-fit existing analog meters with 4” round cutouts — no mounting
adapter required
● Din rail mounting w/o display
● Avoid voltage and current wires at panel door
Schneider Electric – Square D PowerLogic PM800 series power meter
15
Field-installable input & output modules
Two I/O modules can be installed on
the back of the power meter.
● Flexible I/O
● Monitor equipment status & critical
alarm status
● Sync with Utility demand intervals
● Monitor other utilities (water, gas, etc.)
● Standard I/O includes:
● 1 KY Digital output
● 1 Digital input
● Field-installable I/O option modules
● Digital - 6 in/ 2 out
● Digital - 2 in 2 out, Analog - 2 in and 2
out
Schneider Electric – Square D PowerLogic PM800 series power meter
16
Field-installable PM8ECC Ethernet
communications card module
● 10 MB or 100 MB Ethernet UTP
● Modbus TCP/IP protocol
● Alarm notification via e-mail
● Customizable web pages
● Supports TRE-1 functionality
● RS485 Modbus master port with
Ethernet-to-RS485 gateway
functionality; daisy-chain 31 devices
to RS485 port
Schneider Electric – Square D PowerLogic PM800 series power meter
17
PM8ECC Ethernet communications card
benefits
● Clean and efficient solution due to
space constraint
● No extra gateway or power supply
needed.
● IP based meter allows easy
integration into existing Ethernet
infrastructure
● Easy access to the PM8ECC
information by simply typing the IP
address into the web browser
● Easy retrofit ability for existing PM800
series power meter infrastructure
● Give users the ability to enhance their
existing energy monitoring system
network from serial to Ethernet
Schneider Electric – Square D PowerLogic PM800 series power meter
18
Designed with the panel builder in mind
● Single person installation
● Mounting resistance nibs hold meter
until the mounting clips are snapped
into place
● No tools required to mount the meter
● Wide range control power supply
● 115 – 415 Vac (15 vA);
125 – 250 Vdc (10 watts)
● Reduces the number of models to
order and stock
Schneider Electric – Square D PowerLogic PM800 series power meter
19
Powerful and accurate processor
● One of the most powerful microprocessors in its class
● Same processor family as the CM3000 and CM4000 meters
● 128 Samples/Cycle provides high accuracy and harmonic data
● Zero blind metering — no blind spots in data
● Meets IEC 62053-22 (Energy) and ANSI C12.20 0.2S (Active Energy)
● Meets European and USA revenue accuracy standards
Schneider Electric – Square D PowerLogic PM800 series power meter
20
Customizable Alarming
● Factory configured alarms are enabled on power-up
● Detect circuit overloading before the breaker trips
● Quickly identify the source of a problem
● Create custom alarms (PM820, PM850, PM870)
● Combine up to 4 alarms using Boolean logic (PM850,PM870)
● Voltage/current disturbance alarms for sag/swell detection (PM870)
The power meter’s alarm
summary can help identify
persistent alarm conditions that
need attention.
Alarms, stored in power
meter memory and
viewed in PowerLogic
System Manager,
provide early warning of
potential problems.
Schneider Electric – Square D PowerLogic PM800 series power meter
21
Advanced Logging
● Onboard memory for reliable
collection of historical data:
● PM850, PM870 - 800k; PM820 - 80k
standard
● Factory default logging starts as soon
as meter is powered up
● Benefits of onboard data logging:
● Reduce network traffic
● Prevent gaps in data due to network or
computer downtime
Logged data can be downloaded to
PowerLogic System Manager
software for use in historical reports
for capacity planning, energy
trending, and more.
Schneider Electric – Square D PowerLogic PM800 series power meter
22
Advanced Logging (continued)
● On board data logs include:
● Min/Max log—min/max value for each quantity since last reset
● Custom data logs with up to 96 quantities each
(One log – PM820; Three logs – PM850, PM870)
● Billing log and Shift Energy table
The power
meter’s billing log
can be uploaded
and viewed in
PowerLogic
System Manager
software.
Quantities
Logged
Minutes
Days
Months
kWh IN
kWh Total
kVARh IN
kVARh Total
kVAh Total
PF Total
kW Demand
kVar Demand
Each 15 Min for
12 days
(1152 intervals)
32 Days of Daily logs(32
intervals)
52 days - a single
register quantity
48 days - single energy
value
(4 registers)
2 years of monthly logs
(24 Intervals)
Notes
• Quantities logged are default values and are user-definable.
• Daily and monthly PF and demand values represent the last value of the day or month.
Schneider Electric – Square D PowerLogic PM800 series power meter
23
Advanced Logging (continued)
● Shift energy log tracks energy usage
and cost for up to three, userdefinable shifts
● Viewable in a System Manager table
● Register-based data is accessible by
building automation and SCADA
software
Schneider Electric – Square D PowerLogic PM800 series power meter
24
Power Quality Monitoring
● Current and voltage individual
harmonic magnitudes and angles to
the 31st harmonic (PM820), or 63rd
harmonic (PM850, PM870)
● Total harmonic resolution to the 63rd
harmonic for RMS values
Harmonic values, measured by the power meter,
can be viewed in System Manager software.
Schneider Electric – Square D PowerLogic PM800 series power meter
25
Power Quality Monitoring (continued)
● The power meter (PM850, PM870)
measures power quality according to
the EN50160 Power Quality standard.
● The EN50160 standard defines the
voltage quality a customer can expect
from the utility.
The status (pass or fail) of each evaluation
category can be viewed in a System Manager
table.
The power meter generates alarms when an
area of evaluation is outside of the range of
acceptable values.
Schneider Electric – Square D PowerLogic PM800 series power meter
26
Standard Waveform Capture (PM850)
● Waveform Capture
● Manual or Alarm initiation
● 128 samples/cycle, 3 cycles
● Waveforms give a graphical
representation of what’s happening
with your power during a particular
moment.
● Quickly isolate potential power
problems.
● Excellent for troubleshooting
problems that occur continuously.
Schneider Electric – Square D PowerLogic PM800 series power meter
27
Disturbance Detection and
Advanced Waveform Capture (PM870)
● The PM870 has the ability to detect, alarm upon, and capture voltage
and current sags and swells that can cause unwanted trips and process
interruptions, damage motors and more.
● Twelve factory configured voltage disturbance (sag/swell) alarms
provide warning and trigger a disturbance waveform capture.
● Disturbance alarms can be reconfigured for current sag and current
swell using System Manager software.
Voltage sags are often
caused by heavy loads
being started. The
PM870’s disturbance
detection features can
help isolate the source
of troublesome sags
and swells.
Schneider Electric – Square D PowerLogic PM800 series power meter
28
Disturbance Detection and Advanced
Waveform Capture (continued)
● Advanced waveform capture (PM870)
provides a detailed picture of the
disturbance event
● Configurable from 185 cycles on one
channel at 16 samples/cycle up to 3
cycles on six channels at 128
samples/cycle
Poor power quality can lead to
costly downtime. A PM870’s
disturbance waveform capture
can provide the information
needed to diagnose an event.
Schneider Electric – Square D PowerLogic PM800 series power meter
29
Trending and Forecasting
(PM850, PM870)
The power meter’s onboard trend data with
predicted values, can be viewed in System
Manager.
Schneider Electric – Square D PowerLogic PM800 series power meter
● Onboard trends include historical and
forecast values to help predict future
performance
● Min/Max and Average data available
for minutes, hours, days and months
● Forecast for hours and days
● Hourly and weekly summaries
● Trend tables for typical values (e.g.
Real Power, Current, Voltage) can be
viewed in System Manager
● Register-based trend data is
accessible by building automation and
SCADA software
30
Easy to create a system...
● Two ways to create a simple system:
● RS485 connection to EGX400 Ethernet
gateway to your PC
● Ethernet connection from meter to local area
network using PM8ECC option
● With no special software to install, use
your browser to view:
PC with Browser
EGX400 Gateway
Direct LAN
connection to
Ethernet port
of meter
Serial connection
to RS485 port ●
of meter
Schneider Electric – Square D PowerLogic PM800 series power meter
● Instantaneous current, voltage, power and
energy
● I/O status
● Alarm status and history
● Trending and forecasting charts (PM850 or
PM870)
● EN50160 Evaluation (PM850 or PM870)
For more advanced analysis use:
● PowerLogic PowerView
● PowerLogic System Manager
● PowerLogic ION Enterprise
31
Need more information
● Visit us on the web:
● www.powerlogic.com
Schneider Electric – Square D PowerLogic PM800 series power meter
32