MV Fuses
ABB PTMV Poland
2003 -
ABB PTMV Division
Factory in Przasnysz
Fuses in ABB - General Presentation
HV Current Limiting Fuses
1) Back-up fuses
Fuses capable of breaking, under specified conditions of use and behavior, all currents
from the rated maximum breaking current down to the rated minimum breaking
current.
Suitable for application in switch/fuse combinations.
2) General purpose fuse
Fuses capable of breaking, under specified conditions of use and behavior, all currents
from the rated maximum breaking current down to the current that causes melting
of the fuse element in 1 hour or more.
ABB PTMV Poland
3) Full range fuse
Fuses capable of breaking, under specified conditions of use and behavior, all currents
that causes melting of the fuse element (s) up to its rated maximum breaking current.
Fuses in ABB - General Presentation
HV Non-Current Limiting Fuses
1Expulsion fuses
Outdoor fuses for protection of overhead lines and distribution transformers. They
comprise a tin or copper fuse element in series with a flexible braid in a tube.
ABB PTMV Poland
2) Liquid fuses
Based on early non-current limiting fuses that use liquids ( mostly hydrocarbon)
to quench the arc.
Fuses in ABB - General Presentation
MV fuses portfolio -
MV DIN HRC fuses
Back-up fuses
Competitors offer
ABB offer
3,6 - 7,2 kV
(6,3 - 200A), 192, 292, 442 mm
(6 - 100A) 192 mm, (6 - 200A) 292 mm
6 - 12 kV
(6,3 - 200A), 192, 292, 442, 537 mm
(6 - 100A) 292 mm, (6 - 200A) 442 mm
10 - 17,5 kV
(6,3 - 200A), 292, 367, 442 mm
(6 - 63A) 292, 367, 442 mm,
(80 - 125A) 442 mm
10 - 24 kV
ABB PTMV Poland
(6,3 - 200A), 292, 442, 537 mm
(6 - 125A) 442 mm, (80 - 125A) 537 mm
20 - 36 kV
(6,3 - 63A), 537 mm
(6,3 - 40A), 537 mm
Product Overview Fuses
type CEF
High Rupturing Capacity Fuses
Features:
ABB PTMV Poland
High rupturing capacity
Indoor/Outdoor
Low minimum breaking current
Low power losses /suitable in compact switchgear
Low arc-voltage
High breaking capacity
High current limitation
Dimensions acc.to DIN/IEC & BS Standards
rated voltage 3,6 - 36 kV
rated current 6,3 - 200 A
Product Overview Fuses
type WBP / BRT
Fuses for Voltage Transformers
Features:
Unlimited breaking capacity
Short-circuit current limiting
Small dimensions
Intended for protection of circuits
powered by voltage transformer
Intended for ABB voltage transformers
Type WBP - Indoor design.
Rated voltages 7.2, 12, 24, 36 kV.
Rated current 0,4 - 0,8 A.
ABB PTMV Poland
Type BRT - Outdoor design.
Rated voltages 7.2; 12; 17.5; 24; 36 kV.
Rated current 0,8 A.
Product Overview Fuses
type CMF
Fuses for MOTOR circuit applications
Features:
High voltage current limiting
Low power losses
Low minimum breaking current
High breaking capacity
Short circuit current limitation
Dimensions acc.to DIN/IEC & BS Standards
ABB PTMV Poland
rated voltage 3,6 - 12 kV
rated current 63 - 315 A
Product Overview Fuses
type WBT / BWT
Fuses for RAILWAY TRACTION
Features:
High rupturing capacity
Short circuit current limiting
Low switching voltages
Type: WBT...,
Nominal voltage 1.5 - 4 kV DC.
Nominal current In 0,6 - 100 A
Breaking current up to 50kA
Type: BWT
ABB PTMV Poland
Rated voltage Un 3 kV DC
Rated current In 3.15 - 250 A
Minimum breaking current Imin 4 x In
‘Specifica Generale per la Fornitura di Valvole Fusibili A.T. per Circuiti C.C’.
Trenitalia (Italian Railways)
Product Overview Fuses
type CEF/CMF
ABB PTMV Poland
Automated Production Line of ABB fuse link
HV Fuses
ABB PTMV Poland
EUROPE: WE+CEE
AUSTRIA
BELGIUM
BELARUS
BULGARIA
CROATIA
CZECH REP.
DENMARK
ESTONIA
FINLAND
FRANCE
GERMANY
GREAT BRITAIN
GREECE
HUNGARY
ICELAND
IRELAND
ITALY
LATVIA
LITHUANIA
LUXEMBOURG
NORWAY
NETHERLANDS
POLAND
PORTUGAL
ROMANIA
SLOVAKIA
SPAIN
SWEDEN
SWITZERLAND
ASIA:
AUSTRALIA
CHINA
HONG KONG
INDIA
INDONESIA
JAPAN
KOREA
NEW ZEALAND
MALAYSIA
PHILIPPINES
SINGAPORE
TAIWAN
THAILAND
VIETNAM
SOUTH&NORTH AMERICA:
ARGENTINA
BRAZIL
CANADA
CHILE
COLOMBIA
ECUADOR
MEXICO
PANAMA
PERU
USA
VENEZUELA
MIDDLE EAST:
EGYPT
ISRAEL
JORDAN
KUWAIT
LEBANON
SAUDI ARABIA
SYRIA
TUNISIA
TURKEY
UNITED ARAB
EMIRATES
AFRICA:
SOUTH AFRICA
TANZANIA
HV fuses – normal operating conditions
ABB PTMV Poland
•Maximum ambient temperature +400C
•Minimum ambient temperature is -250C
•The altitude does not exceed 1000m (3300ft)
•The ambient air is not excessively polluted by dust, smoke,
corrosive or flammable gases, vapour or salt
•Vibrations due to causes external to fuses or earth tremors are
negligible
•Typical condition of humidity for indoor installations are fulfilled
HV fuses – Standards
ABB PTMV Poland
•IEC 60282-1 High Voltage Fuses
•IEC 60549 High Voltage Fuses for external protection of shunt
Power capacitor
•IEC 60644 Specification for high voltage fuse links for motor
circuit applications
•IEC 60787 Application guide for selection of fuse links of high
voltage fuses for transformers circuit applications
ABB PTMV Poland
HV fuses – design
ABB PTMV Poland
HV fuses – general rules
HV fuses – Fuse parameters
ABB PTMV Poland
Dimensions
HV fuses – Fuse parameters
Nameplate
ABB PTMV Poland
Fuse types:
CEF:
indoor
CEF-BS: with tags
CEF-U: outdoor
CMF:
motor
CMF-BS: with tags
ABB PTMV Poland
HV fuses – Graphic definition of currents
ABB PTMV Poland
HV fuses – Fuse operation
ABB PTMV Poland
HV fuses – general rules
ABB PTMV Poland
HV fuses – Graphic definition of currents
HV fuses – general rules
ABB PTMV Poland
Minimum breaking current
HV fuses – general rules
ABB PTMV Poland
Minimum breaking current
ABB PTMV Poland
HV fuses – general rules
Minimum Melting Time
Total Clearing Time
ABB PTMV Poland
HV fuses – Cut off current
ABB PTMV Poland
HV fuses – Cut off current - ANSI
ABB PTMV Poland
HV fuses – Transformer protection
ABB PTMV Poland
HV fuses – Transformer protection
ABB PTMV Poland
HV fuses – general rules
ABB PTMV Poland
HV fuses – Transformer protection
ABB PTMV Poland
HV fuses – Coordination current limiting fuses/cut-outs
ABB PTMV Poland
HV fuses – Coordination current limiting fuses/cut-outs
ABB PTMV Poland
HV fuses – Your questions
ABB
PTMVPoland
© BAPTMV
– Page41