bonded - MacMate

Download Report

Transcript bonded - MacMate

ADT490
Panel Theory
System Power Supply Grounding
‣ Circuit separates positive / negative from
Ground
‣ Ground fault - resistance to ground ≤ 10 kΩ
‣ System power supply
‣ Line - black
‣ Neutral - white (return)
‣ Ground - green
‣ Exterior components bonded to Ground
2
Power Supply
‣ Output 27 to 30 Vdc
3
Power Supply Fault Analysis
‣ Power on - how do we know?
‣ Disconnect or breaker station - looking for?
4
Power Supply Checklist
5
Power Supply Checklist 2
6
Battery Charger Concepts
‣
‣
‣
‣
‣
‣
‣
‣
2 x 12 V or 4 x 6 V batteries
To charge requires 27.4 to 28 V
must be recharged to 70% within 12 hours (ULC)
5 to 35 mA - float Charge
Fast Charge - larger
Battery Condition Monitor
Ammeter in Series to check the Charge rate (A)
Can check power supply with DC & AC Voltage
Measurements
7
Battery Charger Concepts
8
Electrical Supervision
‣
‣
‣
small current though an EOL Resistor
no current though an EOL Capacitor
Power resistors
‣
‣
‣
approximately 200 Ω
1 volt each
about 2 W
9
Electrical Supervision
10
Detection - Open Circuit
11
EOL Resistor Function
‣ Limits current through wiring
‣ Regulates the voltage in the circuit
12
EOL Capacitor Function
‣
‣
‣
‣
Siemens System 3 or MXL
EOL Capacitor
Blocks DC
Smooths ripple voltage
13
Detection Circuit with EOL
Capacitor
14
EOL Capacitor Waveform
15
EOL Capacitor Waveform
16
Locating Faults
‣ Voltage on open EOL Capacitor circuit is 20.5V
(System 3) & 21.5V (MXL)
‣ Voltage before the break
‣ 0 V after the break
17
EOL Relays
‣ Mostly used on security systems or
‣ 4 wire devices
18
EOL Relays
19
Wiring Architectures
‣
‣
‣
‣
Class B
Class A
Split Class B
Tee-Tapped
20
Class B Wiring - Placement or
Location Supervised (87%)
21
Class A Wiring - Placement or
Location Supervised (8%)
22
Class A Wiring - Greater Reliability
23
Class B Wiring with Tee-Taps
‣ Tap is unsupervised
‣ Reason each device is checked for open - S537
‣ Some vendor use twice EOL size for main run and
single tap
24
Class B Wiring with Tee-Taps
25
Addressable Loop - no EOL
‣ A fault cannot disable more than 1 Zone
26
Signal Circuit Supervision
‣ Terminal may indicate polarity in alarm - not always
‣ 24 VDC can be as low as a few volts
‣ Shorts causes a circuit Trouble
27
Signal Circuit Alarm Operation
‣ Device could be reverses - rings supervision not alarm
‣ Don’t exceed 85% of Current - Why?
28
Class A Signal Circuits
‣ Class A good for opens
‣ Not good for shorts - Why?
29
Speaker Circuits - Supervision
30
Speaker Circuits - Alarm
31
Speaker Circuits - Alarm
‣ 25 Vrms 20 and 40 mA for speaker + 5 mA for EOL
‣ 70.7 Vrms 7.1 and 14.1 mA for speaker + 7.1 mA for
EOL (equivalent to 1/2 W Speaker)
32
Split Speaker Circuits
33
Split Speaker Circuits
34
Telephone Circuits
35
Improperly Connected Signals
36
end
of
Presentation
37