7847i Training - Ameritech Systems

Download Report

Transcript 7847i Training - Ameritech Systems

7847i Internet
Communication
Module
 Honeywell.com
Agenda
•
•
•
•
•
•
•
•
•
2
7847i
Introduction
Overview of the 7847i / 7847iE Communication Path
Features
Summary of connections
Before You Leave the Shop
Network Connectivity
Programming the Device
Registering the Device
Updating Code
Honeywell Proprietary
 Honeywell.com
Introduction
The 7847i delivers highly secure, reliable, Internet communication
of alarm data while the 7847i-E is suitable for enterprise private
network applications using local LAN or point to point connections.
3
7847i
Honeywell Proprietary
 Honeywell.com
Applications
•
•
•
•
•
•
4
7847i
Banking Institutions
Jewelry Industry
Federal Government
Medical
Industrial
Residential
Honeywell Proprietary
 Honeywell.com
Features
•Secure IP Reporting
•Dialer Capture Ready
•Universal Control Panel Compatibility
•Full Contact ID or ADEMCO High
Speed Reporting
•Six Input Zones
•Tamper Protected Enclosure
•Remote Services Capability*
•Network Friendly
•Ease of installation
•Upload/Download
5
7847i
Honeywell Proprietary
 Honeywell.com
Wiring the 7847i/7847i-E
Wiring for ECP, 4204 and Two-4204 Modes
Connect the 7847i/7847i-E to a
compatible Honeywell VISTA
control panel's ECP terminals,
in parallel with keypads and
other peripheral devices
6
7847i
Wiring connections for ECP or 4204 modes
Honeywell Proprietary
 Honeywell.com
Wiring the 7847i/7847i-E
Wiring a LynxR-I for ECP Mode
To trip the zone on the
7847i/7847i-E in V+ trigger
mode, the positive triggering
voltage from
the control panel must be
within 2.0V-14V.
To trip the zone on the
7847i/7847i-E in V- trigger
mode, the negative
triggering voltage
must be less than 1.0V.
Note:
•Trigger levels above this range may cause permanent damage to the unit.
•Trigger levels below this range result in unreliable operation.
7
7847i
Honeywell Proprietary
 Honeywell.com
Wiring the 7847i/7847i-E
Wiring for Zone Trigger Mode
To trip the zone on the
7847i/7847i-E in V+ trigger mode,
the positive triggering voltage from
the control panel must be within
2.0V-14V.
To trip the zone on the 7847i/7847iE in V- trigger mode, the negative
triggering voltage must be less
than 1.0V.
Note:
•Trigger levels above this range may cause permanent damage to the unit.
•Trigger levels below this range result in unreliable operation.
8
7847i
Honeywell Proprietary
 Honeywell.com
Wiring the 7847i/7847i-E
Primary power for the 7847i/7847i-E is
provided by the auxiliary power output
of the control panel 9.6V –13.8V,
typical, or other external power source.
Zone 1 Input to a LynxR Trigger Output
Zone 1 Input for EOL Supervised N.O./N.C. Triggers
9
7847i
Honeywell Proprietary
 Honeywell.com
Select Programming Option
From AlarmNet Direct
• If the device is already in
service go to:
• If the device is new,
choose the appropriate
selection:
10
7847i
Honeywell Proprietary
 Honeywell.com
Enabling Remote Services
For A new account
enter the following:
•
•
•
•
•
•
Primary City ID
Primary CSID
Primary subscriber
Supervision rate
MAC ID
MAC CRC
Then select:
• Enable remote services
• Advanced programming
Remember to enable here if using Total Connect
11
7847i
Honeywell Proprietary
 Honeywell.com
Edit Mode
• Status of the device is displayed.
• With Edit displayed in the Actions box Click GO.
12
7847i
Honeywell Proprietary
 Honeywell.com
Select Mode and Options
Select Operation Mode
ECP – 4204 Emulation –
2-4204s Emulation – Zone
Select Options
•
•
•
•
•
Old Alarm Time
IP Fault Time
Fault Relay Normally On
Tamper Report
Use DHCP
–
–
–
–
NIC IP Address
Subnet Mask
Gateway IP Address
DNS Server IP Address
• Enable Power Save
13
7847i
Honeywell Proprietary
 Honeywell.com
AlarmNet Direct Programming
ECP Mode
• Enable Direct Wire Downloading
– Keypad Address
• Total Connect Features
–
–
–
–
Remote Access
Keypad Address/Type
Multimode
Multimode Address
• Zone 6 and 7
–
–
–
–
14
7847i
EOLR, V+ or VInvert Zone
Zone Restore
Zone Delay
Honeywell Proprietary
 Honeywell.com
AlarmNet Direct Programming
Zone Mode
• Trip Inputs 1 or 2 w/Bell out
– Increases Trip Voltage to 5V
for V+ mode
•
•
•
•
Lynx Panic
Telco Zone
Open/Close Zone
Multimode
– Total Connect
•
•
•
•
•
15
7847i
Trigger Type
Invert Zone
Zone Restore
Zone Delay
Zone Report On Arm
Honeywell Proprietary
 Honeywell.com
AlarmNet Direct Programming
4204 Emulation Modes
•
•
•
•
Fault Relay Normally On
Telco Zone
Open/Close Zone
Enable Direct Wire Downloading
– Keypad Address
• Total Connect Feature
– Remote Access
– Keypad Address/Type
– Set Multi Partition View
• Zone Restore
• Zone Delay
• Zone Report On Arm
– Zone 4 or Zone 8 Arms
16
7847i
Honeywell Proprietary
 Honeywell.com
AlarmNet Direct Programming
If the device is powered
and connected to the
Internet:
• Save And Transfer
Data to Device
If the device is not
powered or connected
to the Internet:
• Click “Save”
• Click “Exit”
Return to Show Program
Devices page.
17
7847i
Honeywell Proprietary
 Honeywell.com
7720 Programming Tool
•The device can also be programmed
using a 7720P Programmer.
•This 7720P allows access to Useful
Diagnostic Tools.
18
7847i
Honeywell Proprietary
 Honeywell.com
7720P Programming
Strt Prog Mode?
(Y/N)_
Enter Password
Enters programming mode.
Change Password?
(Y/N)_
If a password has been previously assigned, this
prompt appears.
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).
The next prompt appears.
Program Device?
(Y/N)_
NOTE: The central station can remotely block access to local device
programming. If this has been done, the following prompt appears:
Access to Prog
Mode Denied
19
7847i
Honeywell Proprietary
 Honeywell.com
Programming
Device Mode
(ECP)_
Press the [space] key to scroll through the
modes of operation. Press [ENTER] to
select ECP mode.
•
•
•
•
Device Address
(03)_
20
7847i
ECP
Zone Triggers
4204 Emu
Two 4204s
In ECP mode, the 7847i/7847i-E communicates with
the panel as a Long Range Radio (LRR) device. Enter
the appropriate ECP device address. For controls, see
the control panel’s Installation and Setup Guide.
Honeywell Proprietary
 Honeywell.com
Programming
21
7847i
Primary City ID?
(??)_
Enter the 2-digit primary city ID, 01-99 (decimal).
Primary CS ID?
(??)_
Enter the 2-digit primary central station
ID number, 01-FE (HEX).
Primary Sub ID?
(????)_
Enter the 4-digit subscriber account number for
the primary central station, 0001-9999 (decimal).
2ND CS Y/N?
(N)_
Applicable only if control supports Central Station
#1and #2 Category Enable reporting for the LRR
device(e.g., VISTA-128BP, FA1660C, etc.).
2ND City ID?
(??)_
Enter the 2-digit secondary city ID, 01-99 (decimal).
2ND CS ID?
(??)_
Enter the 2-digit second central station's ID number,01-FE (HEX).
2ND Sub ID?
(????)_
Enter the 4-digit subscriber account number for the second
central station, 0001-9999.
Honeywell Proprietary
 Honeywell.com
Programming
Remote Access Y/N
(N)_
Press [Y] to allow the end user to access their
system via a website.
Select "4204 Sourced" to send up to four events
or "2-4204 Sourced" to send eight events. Disable
for normal alarm processing and go to Prompt21:
"Primary City ID".
Multi Mode
(Disabled)_
Multi Mode Addr
(12)_
Device address must be unique from
the normal LRR Device Address (Prompt 28), and
the Keypad Address used for Remote Access or
Direct Wire downloading.
Multi-Mode (email notification) is intended as a
convenience for the user, and does not replace Central
Station reporting of critical events (alarms, troubles, etc.).
22
7847i
Honeywell Proprietary
 Honeywell.com
Programming
Direct Wire Y/N
(N)_
Applies only to VISTA-128BP/250BP and FBP Series
controls, and FA1600C and FA1700C Series controls.
Keypad Address
(28)_
Must be programmed if using either the Remote
Access feature or Direct Wire downloading. Enter the
appropriate device address.
Supervision
(24 Hours)_
The AlarmNet network must hear at least one
supervisory message from the module during this
supervision period; otherwise, AlarmNet notifies the
central station that a communication failure has
occurred. 24 Hours
• 1 Hour
• US UL Line (6 Min)
• CN UL Line Lvl 3 (3 Min)
• US UL Line (90 Sec)
• CN UL Line Lvl 4 (90 Sec)
• CN UL Line Lvl 5 (75 Sec)
• None
• 30 Day
23
7847i
Honeywell Proprietary
 Honeywell.com
Programming
Old Alarm Time
(10 Minutes)_
Sets how long an undeliverable alarm is retried for
delivery to the central station.
UL NOTE: Must be 10 Minutes
IP Flt Time
(60 mins)_
24
7847i
Enter the time delay (01-99) in minutes before the
7847i/7847i-E notifies the control panel that there is
loss of contact with the network.
Flt Rel ON Y/N
(N)_
The fault open collector output is normally
energized to ground, and de-energizes (open
circuit) in the event of a module fault.
Tamper Rpt Y/N
(Y)_
Allows the Cover Tamper to be disabled/enabled.
Honeywell Proprietary
 Honeywell.com
Programming Mode
Use DHCP Y/N
(Y) _
If using DHCP the screens below will not be shown. It will skip to
the “PWR Save Mode” question.
25
7847i
NIC IP Address:
255.255.255.255_
Subnet Mask:
255.255.255.255_
Gateway IP Addr:
255.255.255.255_
DNS Serv IP Addr:
255.255.255.255_
Honeywell Proprietary
 Honeywell.com
Programming Mode
Enable Zn 6 (Y/N)
(N)
Zn 6 Trigger Type
(V+)
Invert Zn 6 (Y/N)
(N)
V+
2V to 13V Trips Zone
V0V Ground Trips Zone
EOLR Loss of 2k EOLR Trips
No - Normal Zone Activation
Yes - Faulted Zone sends normal report.
- Normal Zone sends alarm report.
Delay Zn 6 (secs)
(00)
Restore Zn 6 Y/N
(Y)
Yes - Zone sends Restore report.
No - Zone will not send Restore report.
• Zone can be Delayed from 1 to 15 seconds
• Zone must remain faulted for the full extent
of delay to send report.
Repeat for zone 7 if required
26
7847i
Honeywell Proprietary
 Honeywell.com
Programming Mode
Pwr Save Mode (Y/N)
(Y) _
• When Power Save Mode is enabled, the Network Interface Card (NIC) powers
up, Pings a Redir, and turn back off.
• This process takes about 3 seconds and the process repeats every 20 seconds.
• Some Routers may see this as being “under attack” and shut down the Port on
the router.
Devices connected to routers that shut down the port may try using Static IP
Addressing, before disabling the Power Save Mode feature. Power cycle the
Router to reset the port, and determine if this was the problem.
NOTE: If this feature is disabled, the device will not meet the UL Requirement for
Battery Backup. It will reduce the backup time to 18 hours.
27
7847i
Honeywell Proprietary
 Honeywell.com
Programming Mode
Review?
Y/N
Press Enter to Continue and Exit
Create Password?
Y/N
Press Enter to Continue and Exit
Exit Prog Mode?
Y/N
Press Shift Y then Enter to Continue and Exit
Updating Root
File \
28
7847i
DONE
Resetting………
Honeywell Proprietary
Zone Mode Setup
 Honeywell.com
Programming Zone Mode
Lynx Panic
(N)
Y/N
With a LynxR/R-EN Panel, enable Lynx Panic
• Temporal Pulse = Zone 1 Report
–FIRE
• Constant or Steady = Zone 2 Report
–BURG
• Single 3 second Pulse = Zone 3 Report
–Silent Panic, Medical, Duress
Always program Zone 1/2 as a negative trip (V-) and install a
2k EOLR across the zone input and ground.
30
7847i
Honeywell Proprietary
 Honeywell.com
Programming Zone Mode
Trip Inputs 1 or 2
w/Bell Out (N)
Enabling this option will change the required trip voltage on
zones 1, 2 and 3, as described below.
• Positive Trip – Always enable for Positive Trip.
– Disabled – 2V
– Enabled – 5V
• Negative Trip
– Disabled – 0V ground potential
– Enabled – 0V to 5V will trip. Must be greater than 5V to be normal.
This field also affects the zone 3 input.
31
7847i
Honeywell Proprietary
 Honeywell.com
Programming Zone Mode
Telco Zone
(0)
Enabling this option will cause the specified zone input to
send the High Speed Telco Report to Central Station.
• Available for zones 3 through 7.
• Telco Fault
5555 5155 6
• Telco Restore
5555 5355 6
32
7847i
Honeywell Proprietary
 Honeywell.com
Programming Zone Mode
Open/Close Zone
(0)
Enabling this option will cause the specified zone to send a
High Speed Open or Close report to central station, in the
zone that was indicated.
Example uses zone 3 to indicate Open/Close
• Available for zones 3 through 7.
• Arming
5545 5555 7 – Restore Report
• Disarming
5525 5555 7 – Alarm Report
Note: If your trigger activates for Arming, you will need to
enable INVERT for the zone. (Invert option will be discussed later.)
33
7847i
Honeywell Proprietary
 Honeywell.com
Programming Zone Mode
Multi-mode
(N)
• Enabling this option will cause the specified zone ONLY
attempt to generate an email message via Total Connect
Remote Services.
• When enabled, only device Supervisory Messages will be
sent to Central Station, i.e. Low Batt, AC Loss, Swinger
Suppression, etc. (Not Tamper)
NOTE: This option should only be enabled when using Remote
Services and Alarm Reports are not desired to be received by Central
Station.
34
7847i
Honeywell Proprietary
 Honeywell.com
Programming Zone Mode
Zn x Trigger Type
(V+)
V+
2V to 13V Trips Zone
V0V Ground Trips Zone
EOLR Loss of 2k EOLR Trips
Restore Zn x Y/N
(Y)
Yes - Zone sends Restore report.
No - Zone will not send Restore report.
35
7847i
Invert Zn x (Y/N)
(N)
No - Normal Zone Activation
Yes - Faulted Zone sends normal report.
- Normal Zone sends alarm report.
Delay Zn x (secs)
(00)
• Zone can be Delayed from 1 to 15 seconds
• Zone must remain faulted for the full extent
of delay to send report.
Honeywell Proprietary
 Honeywell.com
Exiting Program Mode Correctly
• NEVER disconnect the programmer while in program mode.
• ALWAYS exit program mode AND leave the programmer
connected until the screen displays “DONE”.
If you didn’t exit correctly…
Plug the programmer back in and…
• Press enter then exit as normal.
- or • Power cycle the 7845GSM radio.
36
7847i
Honeywell Proprietary
 Honeywell.com
Registering…
Shift
Registering…
Registration
Successful
37
7847i
Honeywell Proprietary
 Honeywell.com
Registering…PIN Replacement
• When registering the GSM radio press
PIN: _
– Enter PIN
Registering…
– Wait for acknowledgement
Registration
SUCCESS
38
7847i
Honeywell Proprietary
 Honeywell.com
Status Codes
The 7847i sends status messages to the control panel for tamper
and network communication failures. When using Honeywell’s
VISTA-10P, VISTA-15P, Vista 20P series control panels, the status
is displayed on the control panel’s keypad as “Check 103 LRR”
followed by a 4-digit code).
STATUS CODE
39
7847i
DESCRIPTION
0000
Control Panel lost communication with panel
0880
7847i tamper detected (cover removed)
0005
7847i has lost contact with AlarmNet
000F
7847i is not registered; radio account not activated
0400
7847i Power On Reset
0C80
7847i Power On Reset & Tamper detected
0C8F
7847i Power On Reset, Tamper detected & Not
Registered
Honeywell Proprietary
 Honeywell.com
Status Display LEDs
40
7847i
Honeywell Proprietary
 Honeywell.com
Mode & Status LEDs
Press and hold the Mode & Status button to view.
The two Yellow LEDs
indicate which mode the
device is programmed in.
The first Green LED indicates
the status of the Internet or
Web connection.
41
7847i
Honeywell Proprietary
 Honeywell.com
Network Connectivity LEDs
42
7847i
Honeywell Proprietary
 Honeywell.com
Central Station Messages
43
7847i
Honeywell Proprietary
7720P Programmer
Diagnostic Commands
 Honeywell.com
Programmer Keyboard Commands
The 7720P Programmer is an invaluable tool for troubleshooting the
device and network connection. Section 5 of the Installation
Instructions provides details of each command.
45
7847i
[A]
INTERNAL IP/GSM
x.x.xx
mm/dd/yy
Software Revision
[B]
MAC xxxxxxxxxxxx
MAC CRC
yyyy
MAC Address
[C]
Mon 01 Jan 2001
05:48:39 am
GMT Time and Date
Honeywell Proprietary
 Honeywell.com
Programmer Keyboard Commands
For more information on Network Diagnostics, see Section 6 of the Installation Instructions.
[D]
Physical Link
Good
Network Diagnostics Display
[ * ] to go to NIC IP Address
NIC IP Address
xxx.xxx.xxx.xxx
[ * ] to go to Subnet Mask
Subnet Mask
xxx.xxx.xxx.xxx
[ * ] to go to Gateway IP Address
Gateway IP Addr
xxx.xxx.xxx.xxx
If using DHCP, this
information is assigned by
the Gateway/Router.
If not using DHCP, this
information must match the
information provided by the
site Network Administrator.
[ * ] to go to DNS Server IP
46
7847i
Honeywell Proprietary
 Honeywell.com
Programmer Keyboard Commands
Network Diagnostics Display Continued
DNS Serv IP
xxx.xxx.xxx.xxx
[ * ] to go to encryption test
If using DHCP, this
information is assigned by
the Gateway/Router.
If not using DHCP, this
information must match the
information provided by the
site Network Administrator.
Encryption Test
AES Passed!
[ * ] to go to DHCP Status
[F]
47
7847i
DHCP
OK
If using DHCP
Testing Gateway
Redir 1
Run Network Diagnostic
Tests
Honeywell Proprietary
 Honeywell.com
Programmer Keyboard Commands
[S]
ECP 67 TmPB Flt
xx 5 ++ OK
Status Display for ECP Mode
[ * ] = next field, [BS] = previous field
12345678 TmPB Flt
5555555x 5 ++ OK
Status Display for 4204 Emulation Mode
[ * ] = next field, [BS] = previous field
1234 67 TmPB Flt
5555 xx 5 ++ OK
[ * ] = next field, [BS] = previous field
1234567 TmPB Flt
5555555 5 ++ OK
Status Display for 2-4204
Emulation Mode
Status Display for Zone Trigger Mode
[ * ] = next field, [BS] = previous field
Bat NLd: x.xxV
Bat Ld: x.xxV
Battery Voltage Status Display
[ * ] = next field, [BS] = previous field
48
7847i
Honeywell Proprietary
 Honeywell.com
Programmer Keyboard Commands
[S]
ECP 67 TmPB Flt
xx 5 ++ OK
Status Display for ECP Mode
[ * ] = next field, [BS] = previous field
12345678 TmPB Flt
5555555x 5 ++ OK
Status Display for 4204 Emulation Mode
[ * ] = next field, [BS] = previous field
1234 67 TmPB Flt
5555 xx 5 ++ OK
[ * ] = next field, [BS] = previous field
1234567 TmPB Flt
5555555 5 ++ OK
Status Display for 2-4204
Emulation Mode
Status Display for Zone Trigger Mode
[ * ] = next field, [BS] = previous field
Bat NLd: x.xxV
Bat Ld: x.xxV
Battery Voltage Status Display
[ * ] = next field, [BS] = previous field
49
7847i
Honeywell Proprietary
 Honeywell.com
Programmer Keyboard Commands
[ S ] Continued
Battery Charger
OK
Battery Charger Status Display
[ * ] = next field, [BS] = previous field
[T]
Line Voltage
xx.xxV
Line Voltage Status Display
Test Msg Sent
Send Test Alarm
[ * ] = next field, [BS] = previous field
[X]
Reset CPU Y/N
Reset the 7847i
[ * ] = next field, [BS] = previous field
50
7847i
Honeywell Proprietary
 Honeywell.com
Programmer Keyboard Commands
[0]
Force Server Update?
Y/N
Force Upload of Configuration File
Note: If the Internet is not available or if the module cannot communicate with
AlarmNet, the following screen will be displayed after entering this command.
Cannot Upload
Try Later!_
51
7847i
Path for Data Transmission Not Available.
Honeywell Proprietary
http://www.security.honeywell.com/hsc/
and click on MyWebTech
User name: honeywell
Password: support99
Honeywell Security support email: [email protected]
AlarmNet Support (800) 222-6525