Transcript One Goal

Systems Solution Centre Europe & Africa
v2c – S&S EaA
Internal 11-Apr-2006
The JC solution for
small buildings
and flat LON systems
Johnson Controls confidential discussion draft. For internal use only
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Positioning
• Demand on Small Systems Solutions is increasing
• HVAC, Electrical, Fire, CCTV
• Integration, Standard Protocols Support
• Security or Alarm Monitoring or Fire Station
• Some competitors offer simple solutions:
• without network controllers
• no need for web servers and applications
• less performances versus a full BMS
Johnson Controls confidential discussion draft. For internal use only
2
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
A solution for small buildings
• Competitive, flexible and scalable solution to
be proposed where no web access, demand
limiting and interactions are requested
• Simple solution when specifications or
Customers are only considering SCADA
oriented systems, including Fire&Security
Supervision.
• Based on M-Series graphic style
• Serial connectivity N2 and MODBUS, BACnet
MSTP via router to IP, LON, EIBus, M-Bus
using gateways or direct link to PC
• Available TCP/IP like MODBUS IP and
BACnet over IP; others on request
• IP tunnelling available on N2 and MODBUS
Johnson Controls confidential discussion draft. For internal use only
3
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Features
•
Visualization and management for BMS and F&S
•
Graphic, Alarm, Trend
• Read and write single and multiple points
• Time stamp and report
• Time Scheduler
• Enhanced Notification (ESPA,SMS, SNMP)
NO WEB, NO interaction, NO demand limiting!
Johnson Controls confidential discussion draft. For internal use only
4
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Graphics
M-Graphics
• Base on M-Series
• Graphic with animation
• Status and command
• Multiple commands
•
i.e. Zone Set point
•
Function Mode Command
Johnson Controls confidential discussion draft. For internal use only
5
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Data Automation and Integration
EDE
(Extended Data Engine)
• Core of M3i solution
• N2 and MODBUS devices
integration
• OPC connection with data
exchange (bridging)
• Capability of simple processes
Johnson Controls confidential discussion draft. For internal use only
6
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Extended Scheduler
ESX
• Enhanced Schedule Extension
• Easy Scheduler tool creation
• Send commands to JC and 3rd
party devices
• Multiple Command features
Johnson Controls confidential discussion draft. For internal use only
7
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Alarms Handling
M-Alarm
• Alarm visualization for
(HVAC, Electric, Fire, CCTV
ACS and Intrusion)
• Alarm tracking
• Alarm acknowledgement
Johnson Controls confidential discussion draft. For internal use only
8
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Collecting Trends
M-Trend
• Graphic and table Trend
visualization
• Multiple trend points
• Zoom function for details
Johnson Controls confidential discussion draft. For internal use only
9
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Option: The Reports Generator
Metastore
• Historical data report
(temperature, humidity,
pressure etc) energy
consumption for energy
management
• Report on Quick-Report and
Excel file (custom template);
direct on printer local/network
• Set up for report generation
(daily, weekly, monthly);
Johnson Controls confidential discussion draft. For internal use only
10
v2c – S&S EaA
Internal 11-Apr-2006
Option: Advanced Notification
One Company – One Team – One Goal
SMS
ANX
• Message Management for Alarms to Analog & GSM modems
• ESPA Protocol (es. PABX)
• Messages tracking
• Alarm Query
Johnson Controls confidential discussion draft. For internal use only
11
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Option: Supervisioning simultaneous Screens
Multiple screen
•
multiple SVGA video card
•
multiple screen : alarms, TVCC (Site Manager), topography and site maps
Johnson Controls confidential discussion draft. For internal use only
12
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
N2 bus connectivity,
System 9100, N2OPEN, MIG,VND and 3-party devices
• DX9100, DC9100
• TC91xx, SC9100, XT9100, XTM105
• Facility Explorer line
IU9100
N2 bus
N2 bus
XT/XP
DX9100
• 3rd party Devices using N2 (VND) protocols
• Configuration:
MIG
• Expandable to 4 serial bus trunks
TC910x
3-party
Emergency
Remote I/O
Operation
Other
Vendors
Meter
• MIG300 Integrator with all available drivers
Variable
Speed
Drivers
Extension Modules: Connectivity to other field buses, applicable when few devices or datapoints
have to be reported on M3i Available for LONworks, Eibus, WILO, GRUNFOSS, KSB and M-bus
Johnson Controls confidential discussion draft. For internal use only
13
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
N2 bus connectivity: FX devices
IU9100
•
FX Line devices
•
System 9100 devices
•
3rd party Devices using N2 VND
•
MIG300 Integrator
•
Configuration:
N2 bus
Expandable to 4 serial bus trunks
FX15
Master Display
Master Controller
FX15
FX15
FX15
FX05
FX14
FX05
MIG
FX06
FX14
MIG
FX06
Other
Vendors
Meter
Meter
Other
Vendors
Extension Modules: Connectivity to other field buses, applicable when few devices or datapoin
have to be reported on M3i Available for LONworks, Eibus, WILO, GRUNFOSS, KSB and M-b
Johnson Controls confidential discussion draft. For internal use only
14
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
N2 and MODBUS connectivity
• All N2 devices
IU9100
IU9100
N2 bus
Modbus
• MODBUS 3rd party devices (Chillers &
Rooftop, PLC, Meters, Others) having
same bus protocol (RTU or ASCII),
same speed and unique addresses
• N2 and MODBUS on separate buses
XT/XP
3-party
Emergency
Remote I/O
Operation
Multimeter
MIG
FX06
Other
Vendors
Multimeter
3-party
Emergency
Remote I/O
Variable
Speed
Drivers
DX9100
PLC
Variable
Speed
Drivers
Extension Modules: Connectivity to other field buses, applicable when few devices or datapoints
have to be reported on M3i Available for LONworks, Eibus, WILO, GRUNFOSS, KSB and M-bus
Johnson Controls confidential discussion draft. For internal use only
15
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
N2E (DX9121) connectivity
• N2 devices
• N2E devices: max 20 DX
9121 per INT-DX-LON01
IU9100
N2 bus
XT/XP
INT-DX-LON01
DX9100
DX9121
MIG
3-party
Emergency
Remote I/O
Operation
DX9121
FX06
Other
Vendors
Variable
Speed
Drivers
DX9121
Multimeter
3-party
Emergency
Remote I/O
Operation
Johnson Controls confidential discussion draft. For internal use only
16
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
The appropriate SCADA-like Workstation for LonWorks
(A simple network using MIP interface, 5000 SNVTs)
FTT10 LonWorks
-
Meter
Fan Split
Systems
LON
+
IRC Solution
PLC
LN product line
This version allows connection to devices having
MIP interface (up to 4096 variables SNVTs)
like VRV systems, PLC, LON gateways
FTT10 network with repeaters and FTT/FTT routers are supported.
LNS Binding Tool is needed (it has not to be a LNS Turbo Edition Version)
LOnworks devices plug-ins can be used at OWS level
Johnson Controls confidential discussion draft. For internal use only
17
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
The appropriate SCADA-like Workstation for LonWorks
(VNI interface, LNS Turbo Edition, 5000 or 32000 SNVTs)
It allows connection to devices having
MIP interface (up to 4096 variables SNVTs)
like VRV systems, PLC, LON gateways
Zone Display
FTT10 LonWorks
(*)
Router
-
Meter
+
IRC Solution
Fan Split
Systems
LON
LN product line
Zone Display
FTT10 LonWorks
(*)
Router
-
FX06
Other
LONWORKS
Compatible
devices
+
IRC Solution
Variable
Speed
Drivers
PLC
FX15
(*) TCP-IP/FTT10 Routing is supported. A LNS TE server and binding tool is required
LOnworks devices plug-ins can be used at OWS level
Johnson Controls confidential discussion draft. For internal use only
18
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
The appropriate SCADA-like Workstation for LonWorks
M3i LN the appropriate SCADA-like OWS for LN series
Zone Display
FTT10 LonWorks
(*)
Router
Zone Display
(*)
FTT10 LonWorks
Router
(*) TCP-IP/FTT10 Routing is supported. A LNS TE server and binding tool is required
LOnworks devices plug-ins can be used at OWS level
Johnson Controls confidential discussion draft. For internal use only
19
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
M3i LN Workstation and FX devices using LON
Facility Explorer FX devices equipped with LON card
Zone Display
FTT10 LonWorks
Router
FX06
FX15
FX15
FTT10 LonWorks
FX14
LON Meter
Zone Display
Router
FX06
FX15
FX15
Johnson Controls confidential discussion draft. For internal use only
FX14
LON Meter
20
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
M-bus connectivity – Energy metering
RS232
M-Bus converter
N2 bus
•
RS232- M-bus converters to link large
amount of M-bus devices (max 255 per bus)
•
N2 M-Bus modules connecting up to 8 meters
•
MIG to have a share distributed devices
•
Metastore can be used to generate Custom
reports
•
Expandable to 4 serial bus for N2 and /or
MODBUS
•
Heat meters as N2 devices are available and
covering the billing needs
MIG
N2 to
M-bus
RS232 to
M-bus
any M-Bus Meter
Up to 8 M-Bus Meter
any M-Bus Meter
Johnson Controls confidential discussion draft. For internal use only
21
N2 RS485
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
EIB/KNX connectivity – Electrical points & Lighting
•
RS232/EIB interface or IP/EIB interface.
•
N2-EIB modules are usable in case of need with particular reference to small
points or distributed EIBus networks
•
Various EIB solutions for lightings may be applicable using JC IRC devices
IU9100
Ethernet TCP/IP
EIB
EIB
EIB devices properly configured in the EIB network
Johnson Controls confidential discussion draft. For internal use only
EIB devices properly configured in the EIB network
22
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Fire connectivity
•
FIRE Panel
FIRE Panel
Johnson Controls confidential discussion draft. For internal use only
•
Esser IFC-8000
•
Notifier AM-6000
•
Data point automatically
configured from Fire Panel
database files to optimize
commissioning time.
•
Other connections on request, the
next are
• Notifier Other Panels
• Schrack
• Any other available on SIS
Europe list
Serial or Ethernet
Integrations
N2 + MODBUS
Fire:
23
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Intrusion connectivity
•
Intrusion:
•
•
•
CCTV :
•
Intrusion
Pelco MATRIX CM6800
•
Data point automatically
configured from Intrusion Panel
database files to optimize
commissioning time.
•
•
•
Other connections on request,
Any other available on SIS Europe list
Planned DVN connection
Integrations
N2 + MODBUS
Serial or Ethernet
Aritech MASTER ATS
Ademco Galaxy
Intrusion
Johnson Controls confidential discussion draft. For internal use only
24
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
BACnet connectivity
•
System integration as:
MSTP
Over IP
P2000
Thick Client
P2000 ACS
•
Split Systems (VRV, VRF,..)
•
Equipment (chillers, meters,.)
•
PLCs
•
Fire panels
•
Competitors
•
Others…
Fan Split
Systems
BACnet
IP
•
BACnet connectivity must be validated
by SIS Europe
•
BACnet validated routers planned in
FY06 Q3.
Field Bus
connectivit
y
•
Fan Coils,HVAC
Meters
Variable Speed Drivers
Other 3-party controllers
Johnson Controls confidential discussion draft. For internal use only
25
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
P2000 connectivity details using BACnet IP
• P2000 Alarms and Events - M3i OWS can receive P2000 alarms and events,
allowing the workstation operator to acknowledge them. During an alarm, the
Metasys system can perform a pre-defined action (e.g. the system turns on the
lights to a room if a door open alarm has been reported for that area).
• Access Hardware and Status Information - P2000 hardware configuration
and status information can be accessed from an M3i.
• Create Action Interlocks - The P2000 software can be configured to cause
actions to occur within the Metasys system when access is granted.
• Door Commands and Output Points - The Metasys M3i workstation operator
has the ability to initiate a door-open command or trigger a security output
point, all managed from a single seat operation.
Johnson Controls confidential discussion draft. For internal use only
26
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Tunneling Connectivity
TCP/IP
Network
• JC N2 Ethernet devices
• MODBUS TCP/IP 3rd party
devices connection
• Needs a converter
RS485/Ethernet for the BUS
Ethernet
Modbus
TCP/IP
XT/XP
(LANTRONIX UDS-10, JCI SECVT,...)
PLC
DX9100
MS-SECVT-0
MIG
Serial
Integration
LANTRONIX UDS-10
TC910x
Fire
Intrusion
Multimeter
CCTV
Johnson Controls confidential discussion draft. For internal use only
27
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
IT management connectivity
• Using ANX
PABX
•
SMS to mobile,
•
ESPA to PABX
• SNMP to NMS “trap” from UPS
ESPA
Ethernet
SNMP
SMS
TRAP SNMP
SMS=Short Messages
ESPA=European Selective Paging Association
Serial
Integration
PABX=Private Automatic Branch Exchange
UPS
Johnson Controls confidential discussion draft. For internal use only
SNMP=Simple Network Management Protocol
28
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Future connectivity
Future Connections or Special Applications
•
According with Release to Sales Note
•
Contact SIS Europe which can provide several solutions
•
Available MIG integrations can be moved to M3i
platform, contact SIS Europe
Johnson Controls confidential discussion draft. For internal use only
29
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
System Capability
(standard configuration limits to be applied,
for projects with different needs, please contact SIS Europe)
BUS N2
Up to 100 N2 Devices
Example:
 Max 80 TC91xx/FX06
 Max 20 others
 DX91xx/FX15
 MIG300
 VND (ex. IME)
BUS MODBUS
Up to 100 MODBUS Devices
Example :
 10 Circuit Breaker
 2 PLC
 78 Multimeters
 10 CDZ Liebert Hiross
BUS Intrusion
More devices with the same
protocol.
Example :
 MAX 8 Aritech ATS
MASTER or 8
ADEMCO Galaxy
MAX 4 connections, MAX 5000 mappable items points
BUS Fire
More devices with the same
protocol
Example :
 Max 8 Fire Centrals
o Up to 5000 detectors
Ethernet TCP/IP
More devices with different
protocol(Tunnelling)
Example :
 5 plc MODBUS TCP/IP
 1 Aritech ATS Master
Central
 1 PELCO CCTV
Johnson Controls confidential discussion draft. For internal use only
LON
Up to 100 device Lonworks
devices, 5000 TAGs
(SNVT’s)
Flat LON, 32000 Tags, LON
network design skills are
required.
BACNet IP
Up to 4000 objects
30
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Networked Workstations
Ethernet TCP-IP
IU9100
IU9100
N2 bus
INT-DX-LON01
DX9100
DX9121
XT/XP
MIG
DX9121
FX06
• Up to 4 Workstations
• Field busses can be connected
to each OWS, having access
from each Workstation to each
bus trunk
meter
DX9121
Other
Vendors
3-party
Emergency
Remote I/O
Operation
3-party
Emergency
Remote I/O
Operation
Johnson Controls confidential discussion draft. For internal use only
31
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Touch Screen as Workstation
Ethernet TCP/IP
M3i running on PC Panel Touch Screen
Display having various sizes and fully localizable.
All connectivity's available as per standard M3i on PC
RS485
N2 bus
XT/XP
DX9100
Touch screens are in evaluation and test.
Availability planned end FY06 Q4.
SSC Europe to announce the Touch Panel products
range in separate deployment, support and
coordination activity.
MIG
TC910x
Meter
Other
Vendors
3-party
Emergency
Remote I/O
Operation
Johnson Controls confidential discussion draft. For internal use only
32
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Touch Screen as HMI (Human Machine Interface)
M3i connecting Local HMI Touch Screens having N2, Eibus and/or Modbus
(various sizes, display types and fully localizable).
Touchscreen are under evaluation and test, availability planned end
FY06 Q4. SSC Europe to announce the Touch Panel products range in
separate deployment, support and coordination activity.
Ethernet TCP-IP
RS485 N2bus
XT/XP
RS485
N2 bus
RS485
Modbus
DX9100
KNX
EIbus
3-party
Emergency
Remote I/O
Operation
Meter
MIG
RS485 N2bus”
XT/XP
FX15
EIB Multimeter
MIG
TC910x
FX06
3-party
Emergency
Remote I/O
Operation
Other
Vendors
Meter
PLC
Eibus Lighting
or I/O system
Other
Vendors
Meter
Extension Modules Connectivity to other field buses, applicable when few devices or datapoints
have to be reported to M3i. Available for LONworks, Eibus, WILO, GRUNFOSS, KSB and M-bus
Johnson Controls confidential discussion draft. For internal use only
33
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Interaction with other systems
• Links to documents as PDF, excel,…..)
• P2000
•
Via BACnet,reading status and doors alarm
and send command of manual open doors
•
Using Internet Explorer (P2000 V.3.4) it’s
possible manage and insert new account
(Web Based)
• Fire IFC-8000
•
Alarm and trouble sensors,
•
Get the status of the central
Johnson Controls confidential discussion draft. For internal use only
34
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Interaction with other systems
• ARITECH ATS MASTER or ADEMCO GALAXY
•
•
Alarm receiving and sensor trouble detection
•
Area and central status
•
It’s allows the partial &/or total insertion of the protection and the alarm reset
PELCO MATRIX CM6800
•
Visualization on TVC or monitor
•
Different sequence selection
•
To do the camera Preset on Dome
devices
•
Interaction between Intrusion and
TVCC using PC
Johnson Controls confidential discussion draft. For internal use only
35
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Interaction with other systems
• JC DVN Series
• Ethernet connection
• From Graphics map clicking on TV
Camera: a pop-up with the image will
appear
• To alarm the DVN is needed an direct
interaction with the antintrusion central
Johnson Controls confidential discussion draft. For internal use only
36
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Interaction with other systems
•
In case :
•
•
•
No HW (hardwired) interaction
No field device interactions
No PC h24 controlled
•
When interaction is a critical M3i mission, UPS is strongly
suggested.
•
Peer to peer communication at field level could be an
alternative solution (LON, EIB, Modbus over IP,
BACnet,....)
Johnson Controls confidential discussion draft. For internal use only
37
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
EDE Sharing value + calculation
MIG
TC-9102
PLC Integration with VCT
Johnson Controls confidential discussion draft. For internal use only
38
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
EDE Calculation Engine:
Sources calculation
EDE operators
EDE Function
EDE can combine multiple sources in a single equation using mathematical
operators and functions. Available sources are, OPC/DDE Tags and field
Network variables/Items. Equations does not allow managing runtime
calculations, load shedding or load rolling. All these applications should be
managed by field devices like DX9100 for runtime calculation.
Johnson Controls confidential discussion draft. For internal use only
39
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
EDE calculation Engine
EDE is able to send calculation value to
multiple destinations and assign each
destination a different value using equations
with mathematical operators and functions.
Available sources are, OPC/DDE Tags and
field Network variables/Items. Equations does
not allow managing runtime calculations, load
shedding or load rolling.
All these applications should be managed by
field devices like DX9100 for runtime
calculation.
@ = Source Equation result.
Johnson Controls confidential discussion draft. For internal use only
40
One Company – One Team – One Goal
v2c – S&S EaA
Internal 11-Apr-2006
Considerations
Questions & Answers
THANKS !
Johnson Controls confidential discussion draft. For internal use only
41