Introduction
Download
Report
Transcript Introduction
Review
1
Review of Phasors
Goal of phasor analysis is to simplify the analysis of constant frequency ac
systems:
v(t) = Vmax cos(wt + qv),
i(t) = Imax cos(wt + qI),
where:
• v(t) and i(t) are the instantaneous voltage and current as a function of
time t,
• w is the angular frequency (2πf, with f the frequency in Hertz),
• Vmax and Imax are the magnitudes of voltage and current sinusoids,
• qv and qI are angular offsets of the peaks of sinusoids from a reference
waveform.
Root Mean Square (RMS) voltage of sinusoid:
T
Vmax
1
2
V
v (t ) dt
, so Vmax 2 V .
T0
2
2
Phasor Representation
The RMS, cosine-referenced voltage phasor is:
V
V e jqV V qV ,
v (t )
Re 2 V e jwt e jqV ,
V
V cosqV j V sin qV ,
I
I cosq I j I sin q I .
3
Phasor Analysis
Device
Resistor
Time Analysis
v (t ) Ri (t )
di (t )
v (t ) L
dt
Inductor
Phasor
V RI
V jw LI
t
1
v (t ) i (t )dt v (0)
C0
Capacitor
1
V
I
jwC
Z = Impedance R jX Z ,
(Note: Z is a
complex number but
not a phasor).
R = Resistance,
X = Reactance,
Z =
R X ,
2
2
X
=arctan
R
.
4
Complex Power
Instantaneous Power :
p (t ) v(t ) i (t ),
v(t ) = Vmax cos(w t qV ),
i (t)
= I max cos(w t q I ),
1
cos cos [cos( ) cos( )],
2
1
p (t ) Vmax I max [cos(qV q I )
2
cos(2w t qV q I )].
5
Complex Power, cont’d
Instantaneous Power is sum of average and varying terms :
1
p (t ) Vmax I max [cos(qV q I ) cos(2w t qV q I )],
2
T
Pavg
1
p (t )dt ,
T0
1
Vmax I max cos(qV q I ),
2
V I cos(qV q I ),
Power Factor Angle = =qV q I .
6
Complex Power
S V I cos(qV q I ) j sin(qV q I ) ,
P jQ,
V I *,
(Note: S is a complex number but not a phasor.)
P = Real Power (W, kW, MW),
Q = Reactive Power (VAr, kVAr, MVAr),
= magnitude of power into electric and magnetic fields,
S = Complex power (VA, kVA, MVA),
Power Factor (pf) = cos ,
If current leads voltage then pf is leading,
7
If current lags voltage then pf is lagging.
Complex Power, cont’d
Relationships between real, reactive, and complex power:
P S cos ,
Q S sin
S 1 pf 2 ,
Example: A load draws 100 kW with a leading pf of 0.85.
What are (power factor angle), Q and S ?
cos1 0.85 31.8,
100kW
S
117.6 kVA,
0.85
Q 117.6sin( 31.8) 62.0 kVAr.
8
example
ZL=jwL=j*1000*1*10^-3 =j
9
10
Example
Power flowing from
source to load at bus
Earlier we found
I = 20-6.9 amps
S V I * 10030 206.9 200036.9 VA,
= 1600W + j1200VAr
36.9 pf = 0.8 lagging,
S R VR I ( RI ) I 4 20 6.9 206.9,
*
*
2
PR 1600W I R
(QR 0),
S L VL I * ( jXI ) I * 3 j 20 6.9 206.9,
QL 1200VA r
2
I X,
(PL 0).
11
Power Consumption in Devices
Resistors only consume real power:
2
PResistor I Resistor R,
Inductors only "consume" reactive power:
2
QInductor I Inductor X L ,
Capacitors only "generate" reactive power:
2
QCapacitor I Capacitor X C
QCapacitor
VCapacitor
XC
1
XC
.
wC
2
. (Note-some define X C negative.)
12
Example
I
First solve
basic circuit
400000 V
I
4000 Amps
1000
V 400000 (5 j 40) 4000
42000 j16000 44.920.8 kV
S V I * 44.9k20.8 4000
17.9820.8 MVA 16.8 j 6.4 MVA
13
Example, cont’d
Now add additional
reactive power load
and re-solve, assuming
that load voltage is
maintained at 40 kV.
Z Load 70.7
pf 0.7 lagging
I 564 45 Amps
V 59.713.6 kV
S 33.758.6 MVA 17.6 j 28.8 MVA
14
Power System Notation
Power system components are usually shown as
“one-line diagrams.” Previous circuit redrawn.
17.6 MW
16.0 MW
28.8 MVR
-16.0 MVR
59.7 kV
17.6 MW
28.8 MVR
Generators are
shown as circles
40.0 kV
16.0 MW
16.0 MVR
Transmission lines are shown as
a single line
Arrows are
used to
show loads
15
Reactive Compensation
Key idea of reactive compensation is to supply reactive
power locally. In the previous example this can
be done by adding a 16 MVAr capacitor at the load.
16.8 MW
16.0 MW
6.4 MVR
0.0 MVR
44.94 kV
16.8 MW
6.4 MVR
40.0 kV
16.0 MW
16.0 MVR
16.0 MVR
Compensated circuit is identical to first example with just real power load.
Supply voltage magnitude and line current is lower with compensation.
16
Reactive Compensation, cont’d
Reactive compensation decreased the line flow
from 564 Amps to 400 Amps. This has
advantages:
– Lines losses, which are equal to I2 R, decrease,
– Lower current allows use of smaller wires, or
alternatively, supply more load over the same wires,
– Voltage drop on the line is less.
Reactive compensation is used extensively
throughout transmission and distribution
systems.
Capacitors can be used to “correct” a load’s
power factor to an arbitrary value.
17
Power Factor Correction Example
Assume we have 100 kVA load with pf=0.8 lagging,
and would like to correct the pf to 0.95 lagging
S 80 j 60 kVA
cos 1 0.8 36.9
PF of 0.95 requires desired
cos 1 0.95 18.2
Snew 80 j (60 Qcap )
60 - Qcap
80
Qcap
tan18.2 60 Qcap 26.3 kVAr
33.7 kVAr
18
Distribution System Capacitors
19
Balanced 3 Phase () Systems
A balanced 3 phase () system has:
– three voltage sources with equal magnitude, but
with an angle shift of 120,
– equal loads on each phase,
– equal impedance on the lines connecting the
generators to the loads.
Bulk power systems are almost exclusively 3.
Single phase is used primarily only in low
voltage, low power settings, such as residential
and some commercial.
Single phase transmission used for electric
trains in Europe.
20
Balanced 3 -- Zero Neutral Current
In Ia Ib Ic
V
In
(10 1 1
Z
S Van I a* Vbn I b* Vcn I c* 3 Van I a*
Note: Vxy means voltage at point x with respect to point y.
21
Advantages of 3 Power
Can transmit more power for same amount of
wire (twice as much as single phase).
Total torque produced by 3 machines is
constant, so less vibration.
Three phase machines start more easily than
single phase machines.
22
Three Phase - Wye Connection
There are two ways to connect 3 systems:
– Wye (Y), and
– Delta ().
Wye Connection Voltages
Van
V
Vbn
V
Vcn
V
23
Wye Connection Line Voltages
Vcn
Vab
Vca
-Vbn
Van
Vbn
(α = 0 in this case)
Vbc
Vab
Vbc
Vca
Van Vbn V (1 1 120
3 V 30
3 V 90
Line to line
voltages are
also balanced.
3 V 150
24
Wye Connection, cont’d
We call the voltage across each element of a
wye connected device the “phase” voltage.
We call the current through each element of a
wye connected device the “phase” current.
Call the voltage across lines the “line-to-line” or
just the “line” voltage.
Call the current through lines the “line” current.
VLine 3 VPhase 130 3 VPhase e
j
6
I Line I Phase
S3
*
3 VPhase I Phase
25
Delta Connection
For Delta connection,
voltages across elements
equals line voltages
Ica
For currents
I a I ab I ca
Ic
Ib
Ibc
Iab
Ia
3 I ab
I b I bc I ab
I c I ca I bc
*
S3 3 VPhase I Phase
26
Three Phase Example
Assume a -connected load, with each leg Z =
10020, is supplied from a 3 13.8 kV (L-L) source
Vab 13.80 kV
Vbc 13.8 0 kV
Vca 13.80 kV
13.80 kV
I ab
138 20 amps
I bc 138 140 amps
I ca 1380 amps
27
Three Phase Example, cont’d
I a I ab I ca 138 20 1380
239 50 amps
I b 239 170 amps I c 2390 amps
*
S 3 Vab I ab
3 13.80kV 138 amps
5.7 MVA
5.37 j1.95 MVA
pf cos 20 lagging
28
Delta-Wye Transformation
To simplify analysis of balanced 3 systems:
1) Δ-connected loads can be replaced by
1
Y-connected loads with Z Y Z
3
2) Δ-connected sources can be replaced by
VLine
Y-connected sources with Vphase
330
29
Delta-Wye Transformation Proof
-
+
Suppose the two sides have identical terminal behavior.
For the side we get
Vab Vca
Vab Vca
Ia
Z Z
Z
Hence
Z
Vab Vca
Ia
30
Delta-Wye Transformation, cont’d
For the Y side we get
Vab
ZY ( I a I b )
Vca ZY ( I c I a )
Vab Vca ZY (2 I a I b I c )
Ia Ib Ic 0 Ia Ib Ic
Since
Vab Vca 3 ZY I a
Hence
3 ZY
Vab Vca
Z
Ia
Therefore
ZY
1
Z
3
31
3 phase power calculation
32