phase current - Deeteekay Community
Download
Report
Transcript phase current - Deeteekay Community
ELECTRICAL CIRCUIT
ET 201
Become familiar with the operation of a
three phase generator and the
magnitude and phase relationship.
Be able to calculate the voltages and
currents for a three phase Wye and
Delta connected generator and load.
1
THREE PHASE
SYSTEMS
2
23.1 – Introduction
If the number of coils on the rotor is increased
in a specified manner, the result is a
polyphase ac generator, which develops
more than one ac phase voltage per rotation of
the rotor
An ac generator designed to develop a single
sinusoidal voltage for each rotation of the shaft
(rotor) is referred to as a single-phase ac
generator
In general, three-phase systems are preferred
over single-phase systems for the transmission
of power for many reasons, including the
following:
3
Introduction
1. Thinner conductors can be used to transmit the same
kVA at the same voltage, which reduces the amount of
copper required (typically about 25% less) and in turn
reduces construction and maintenance costs.
2. The lighter lines are easier to install, and the
supporting structures can be less massive and farther
apart.
3. Three-phase equipment and motors have preferred
running and starting characteristics compared to
single-phase systems because of a more even flow of
power to the transducer than can be delivered with a
single-phase supply.
4. In general, most larger motors are three phase
because they are essentially self-starting and do not
require a special design or additional starting circuitry.4
Introduction
The frequency generated is determined by the
number of poles on the rotor (the rotating part
of the generator) and the speed with which the
shaft is turned.
Throughout the United States the line frequency
is 60 Hz, whereas in Europe (incl. Malaysia) the
chosen standard is 50 Hz.
On aircraft and ships the demand levels permit
the use of a 400 Hz line frequency.
The three-phase system is used by almost all
commercial electric generators.
5
Introduction
Most small emergency generators, such as the
gasoline type, are one-phased generating systems.
The two-phase system is commonly used in
servomechanisms, which are self-correcting control
systems capable of detecting and adjusting their
own operation.
Servomechanisms are used in ships and aircraft to
keep them on course automatically, or, in simpler
devices such as a thermostatic circuit, to regulate
heat output.
The number of phase voltages that can be
produced by a polyphase generator is not limited to
three. Any number of phases can be obtained by
spacing the windings for each phase at the proper
angular position around the stator.
6
23.2 – Three-Phase Generator
The three-phase generator has three induction
coils placed 120° apart on the stator.
The three coils have an equal number of turns,
the voltage induced across each coil will have the
same peak value, shape and frequency.
7
Three-Phase Generator
At any instant of time, the algebraic sum of
the three phase voltages of a three-phase
generator is zero.
8
Three-Phase Generator
The sinusoidal expression for each of the
induced voltage is:
9
Phase expression
• In phase expression:
EM
EA
0
2
EB
EM
2
120
EC
EM
2
120
• Where:
EM
: peak value
EA, EB and EC : rms value
10
Connection in Three Phase System
•
A 3-phase system is equivalent to three
single phase circuit
• Two possible configurations in three
phase system:
1. Y-connection (star connection)
2. ∆-connection (delta connection)
11
Three-phase Voltages Source
Y-connected source
∆-connected source
12
Three-phase Load
Y-connected load
∆-connected load
13
23.3 – Y-Connected Generator
If the three terminals denoted N are connected
together, the generator is referred to as a Yconnected three-phase generator.
14
Y-Connected Generator
The point at which all the terminals are connected is
called the neutral point.
1.
Two type of Y-connected generator:
Y-connected, three-phase, three-wire generator
(a conductor is not attached from this point to the load)
Y-connected, three-phase, four-wire generator
(the neutral is connected)
2.
The three conductors connected from A, B and C to the
load are called lines.
15
Y-connected, 3-phase, 3-wire
generator
16
Y-connected, 3-phase, 4-wire
generator
17
Y-Connected Generator
The voltage from one line to another is called
a line voltage
The magnitude of the line voltage of a
Y-connected generator is:
18
Definition of Phase Voltage
• In 3-phase system, for Y-connected, the voltage
from line to neutral point is called a
phase voltage.
EAN – phase A voltage
EBN – phase B voltage
ECN – phase C voltage
19
Definition of Line Voltage
• In 3-phase system, for Y-connected, the voltage
from one line to another is called a
line voltage.
EAB – voltage between
line A and B
EBC – voltage between
line B and C
ECA – voltage between
line C and A
20
Y-connected system
• Line voltage:
VAB ; VBC ; VCA
• Phase voltage:
VAN ; VBN ; VCN
21
Voltage in Y-connected system
For 3-phase Y-connected system, if the phase
voltage VAN is taken as the reference, so
VAN VAN 0
VBN VBN 120
VCN VCN 120
22
Voltage in Y-connected system
• By applying Kirchhoff’s Voltage Law, the line
voltage can be written as
VAB VAN VBN
VAN0 VBN 120
VAN (10 1 120)
VAN ((1 j0) (0.5 j0.866))
VAN (1.5 j0.866)
VAN (1.73230)
VAB 3VAN30
23
Voltage in Y-connected system
• With the same method,
VBC VBN VCN
3VBN 90
and
VCA VCN VAN
3VCN 150
• The relationship between the line voltage and
the phase voltage can be represented as
VL 3Vφ30
VL : line voltage
Vφ : phase voltage
24
Current in Y-connected system
• For the Y-connected system, it should be
obvious that the line current equals the phase
current for each phase; that is
IL Iφ
IL : line current
Iφ : phase current
25
23.4 – Phase Sequence
(Y-Connected Generator)
The phase sequence can be determined by the
order in which the phasors representing the phase
voltages pass through a fixed point on the phasor
diagram if the phasors are rotated in a
counterclockwise direction.
26
3.4 – Phase Sequence
(Y-Connected Generator)
In phasor notation,
Line voltage:
VAB VAB0 (reference )
VBC VBC 120
VCA VCA 120
VAN VAN 0 (reference )
Phase voltage:
VBN VBN 120
VCN VCN 120
27
23.5 – Y-Connected Generator
with a Y-Connected Load
Loads connected with three-phase supplies are of two
types: the Y and the ∆.
If a Y-connected load is connected to a Y-connected
generator, the system is symbolically represented by Y-Y.
28
Y-Connected Generator with a YConnected Load
If the load is balanced, the neutral connection can be
removed without affecting the circuit in any manner; that
is, if Z1 = Z2 = Z3 , then IN will be zero, IN = 0 .
Since IL = V / Z the magnitude of the current in each
phase will be equal for a balanced load and unequal for
an unbalanced load. In either case, the line voltage is
29
EXAMPLE 1
• Calculate the line currents in the three-wire Y-Y
system as shown below.
30
Solution:
Single Phase Equivalent Circuit
Phase ‘a’ equivalent circuit
31
I Aa
VAN
; ZT (5 j 2) (10 j8) 16.15521.8
ZT
I Aa
1100
6.81 21.8
16.15521.8
I Bb I Aa 120
6.81 141.8A
I Cc I Aa 240
6.81 261.8 6.8198.2A
32
23.6 – Y-Connected Generator
with a ∆-Connected Load
There is no neutral connection for the Y-∆ system
shown below.
Any variation in the impedance of a phase that
produces an unbalanced system will simply vary the
line and phase currents of the system.
33
Y-Connected Generator with a
∆-Connected Load
For a balanced load, Z1 = Z2 = Z3.
The voltage across each phase of the load is equal to the line
voltage of the generator for a balanced or an unbalanced
load: V = EL.
34
Y-Connected Generator with a
∆-Connected Load
Kirchhoff’s current law is employed instead of Kirchhoff’s
voltage law.
The results obtained are:
The phase angle between a line current and the nearest
phase current is 30°.
35
EXAMPLE 2
A balanced positive sequence Yconnected source with
VAN=10010 V is connected to a
-connected balanced load
(8+j4) per phase. Calculate the
phase and line currents.
36
Solution:
Balanced WYE source, VAN = 10010 V
Balanced DELTA load, Z = 8 + j4
Phase and line currents = ??
37
Phase Currents
Vab
I ab
ZΔ
Vab= voltage across Z
= VAB= source line voltage
VAB 3 VAN30
Vab 173.240 V
173.240
I ab
19.3613.43 A
8 j4
38
Phase Currents
I ab 19.3613.43 A
I bc I ab 13.43 120
I bc 19.36 106.57 A
I ca 19.3613.43 120
I ca 19.36133.43 A
39
Line Currents
I Aa 3 I ab 30
3 (19.36) 13.43 30
I Aa 33.53 16.57 A
I Bb I Aa 120 33.53 136.57 A
I Cc I Aa 120 33.53 103.43 A
40
23.7 – ∆-Connected Generator
In the figure below, if we rearrange the coils of
the generator in (a) as shown in (b), the system
is referred to as a three-phase, three-wire.
41
∆-Connected Generator
∆-connected ac generator
In this system, the phase and line voltages are
equivalent and equal to the voltage induced
across each coil of the generator:
E AB E AN and e AN 2 E AN sin t
EBC EBN and eBN 2 EBN sin( t 120)
ECA ECN and eCN 2 ECN sin( t 120)
or
EL = Eg
Only one voltage (magnitude) is available instead
of the two in the Y-Connected system.
42
∆-Connected Generator
Unlike the line current for the Y-connected generator, the
line current for the ∆-connected system is not equal to the
phase current. The relationship between the two can be
found by applying Kirchhoff’s current law at one of the
nodes and solving for the line current in terms of the phase
current; that is, at node A,
IBA = IAa + IAC
or
IAa = IBA - IAC = IBA + ICA
43
∆-Connected Generator
The phasor diagram is shown below for a
balanced load.
In general, line current is:
44
Definition of Phase Current
• In 3-phase system, for ∆-connected, the current
that flow from one phase to another is called a
phase current.
IBA – phase A current
ICB – phase B current
IAC – phase C current
45
Definition of Line Current
• In 3-phase system, for ∆-connected, the current
that flow through the line is called a line current.
IAa – line A current
IBb – line B current
ICc – line C current
46
∆-connected system (generator)
• Line current:
IAa ; IBb ; ICc
• Phase current:
for generator:
IBA ; IAC ; ICB
47
∆-connected system (load)
• Line current:
IAa ; IBb ; ICc
• Phase current:
for load:
Iab ; Ibc ; Ica
48
Current in ∆-connected system
(Generator side)
For 3-phase ∆-connected system (generator), if
the phase current IBA is taken as the reference,
so
IBA IBA 0
I CB ICB 120
I AC I AC120
49
Current in ∆-connected system
(Generator side)
• By applying Kirchhoff’s Current Law, the
line current can be written as
I Aa I BA I AC
I BA 0 I BA 120
I BA (10 1120)
I BA (1 j0 (0.5 j0.866))
I BA (1.5 j0.866)
I BA (1.732 30)
I Aa 3I BA 30 A
50
Current in ∆-connected system
(Generator side)
• With the same method,
I Bb I CB I BA
3I CB 150
and
I Cc I AC I CB
3I AC90
51
Current in ∆-connected system
(Load side)
For 3-phase ∆-connected system (load), if the
phase current Iab is taken as the reference, so
Iab Iab 0
I bc I bc 120
Ica Ica 120
52
Current in ∆-connected system
(Load side)
• By applying Kirchhoff’s Current Law, the
line current can be written as
I Aa I ab I ca
I ab 0 I ab 120
I ab (10 1120)
I ab (1 j0 (0.5 j0.866))
I ab (1.5 j0.866)
I ab (1.732 30)
I Aa 3Iab 30 A
53
Current in ∆-connected system
(Load side)
• With the same method,
I Bb I bc I ab
3I bc 150
and
I Cc I ca I bc
3I ca 90
54
Relationship between the phase
current and the line current
(∆-connected system)
• The relationship between the line current and
the phase current can be represented as
I L 3Iφ 30
Where;
IL : line current
Iφ : phase current
55
Voltage in ∆-connected system
• For the ∆-connected system, it should be
obvious that the line voltage equals the phase
voltage for each phase; that is
VL Vφ
VL : line voltage
V : phase voltage
56
23.8 – Phase Sequence (∆- Connected
Generator)
Even though the line and phase voltages of a ∆ connected system are the same, it is standard
practice to describe the phase sequence in terms of
the line voltages
In drawing such a diagram, one must take care to
have the sequence of the first and second
subscripts the same
In phasor notation,
VAB = VAB 0o
VBC = VBC 120o
VCA = VCA 120o
57
23.9 - ∆-Connected Generator with
a ∆-Connected Load
58
EXAMPLE 3
A balanced delta connected load
having an impedance 20 - j15 is
connected to a delta connected,
positive sequence generator having
VAB = 3300 V. Calculate the phase
currents of the load and the line
currents.
59
Solution:
ZΔ 20 j15 25 36.87
VAB 3300 V
60
Phase Currents
Vab
3300
I ab
13.236.87A
ZΔ 25 38.87
I bc I ab 120 13.2 - 83.13A
I ca I ab 120 13.2156.87A
61
Line Currents
I Aa I ab 3 30
13.236.87 3 30
22.866.87 A
I Bb I Aa 120 22.86 - 113.13 A
I Cc I Aa 120 22.86126.87 A
62
23.9 - ∆-Connected Generator with
a Y-Connected Load
63
EXAMPLE 4
• A balanced Y-connected load with a
phase impedance 40 + j25 is supplied
by a balanced, positive-sequence Δconnected source with a line voltage of
210 V. Calculate the phase currents.
Use VAB as reference.
64
Solution:
• the load impedance, ZY and the source voltage, VAB are
ZY 40 j25 47.1732
VAB 2100 V
65
Solution:
• When the ∆-connected source is transformed to
a Y-connected source,
VAB
Van
30
3
2100
1 30
3
121.2 - 30 V
66
Solution:
• The line currents are
I Aa
Van 121.2 30
2.57 - 62 A
ZY
47.1732
I Bb I Aa 120 2.57 - 182 A
I Cc I Aa 120 2.5758 A
67
Summary of Relationships in
Y and ∆-connections
Y-connection
Voltage
VL 3Vφ
magnitudes
Current
IL Iφ
magnitudes
VL leads Vφ by 30°
Phase
sequence
∆-connection
VL Vφ
I L 3I φ
IL lags Iφ by 30°
68