The NeSSI™-bus & DOE Update

Download Report

Transcript The NeSSI™-bus & DOE Update

Progress and Developments
in Network Solutions for
NeSSI Generation II
CPAC May 2005
John Mosher – Honeywell Sensing & Control
The Network “Rail” Enables Information
Communications Interface “Rail”
The Area Between the Enabling “Rails” is Where
Sensor and Instrument Vendors Add Value and
Commercialize Intellectual Property.
Physical Interface “Rail” – ANSI/SP76
NeSSI-Net
• NeSSI Generation II Network Requirements:
- Intrinsically Safe
- Multi-variable Capability
- Configuration Storage and Update Capability
- Diagnostic Capability
- Connectivity to Sensor Actuator Manager (SAM)
- Fault Tolerance
- Protocol administered independently (not by NeSSI/CPAC)
- Open System
- World-wide acceptance
- Petrochemical market acceptance
- Key customer acceptance
The Network Enables Information and Uptime
Foundation Fieldbus
•Foundation Fieldbus Chosen for Generation II/III
- Proposed, discussed and accepted at CPAC Fall Meeting
- Meets all criteria of requirements
- Minor engineering work to shrink network interface
- Press Release Issued at Foundation Fieldbus General Assembly
•The Fieldbus Foundation:
- Offered to help with Specification Definition
- Will coordinate resources with NeSSI product vendors
- Offered Technical Assistance in Implementing FF
- Understands Vision for MicroAnalytical Platform
- Free Device Conformance Testing
Foundation Fieldbus Value:
• FF delivers benefits today
- Wiring and cabinet savings
- Asset management for lower maintenance and fewer
incidents
- Faster startup, commissioning, maintenance
• Fieldbus supports a rich set of capabilities
- Control on the wire (the only protocol that has it)
- Automatic Addressing
- Automatic Configuration via Electronic Data Descriptions
- Automatic Replacement Device Configuration
- Built-in Alarming
- Function Blocks for Simple Device Management
- Seamless Data Transfer with FF HSE (High Speed Ethernet)
Foundation Fieldbus Users
•
•
•
•
•
•
•
•
•
•
•
•
•
BASF
BP
Bristol Myers Squibb
ChevronTexaco
ConocoPhillips
CPC
Distileria Serralles
Gaz de France
NGT
Petroquimica União
Polioles S.A.
Pride Chemical
Putra Jaya
• Qatar Petroleum
Corporation
• SASOL
• Shell Global Solutions
• Shin-Etsu
• SINOPEC
• Skandinaviska Raffinaderi
• Sokolovska Uhelna
• Solvay
• Statoil Kvitebjoern
• Sunoco
• Unocal
• Wintershall
Foundation Fieldbus Architecture for NeSSI
FOUNDATION fieldbus HSE/OPC/etc…
FF Blocks
AI
FF Interface
AI
SAM
AO
TB
TB
SAM Controller
FOUNDATION fieldbus H1
Network
A/D
PS
FISCO
Power Supply
AI
PID
Substrate
Programmable Substrate Heater
Auxiliary Heating/Cooling
DI
AO
FFB
Control Functions
FF Device Design Parameters
Recommended Parameters for Hazardous Area Devices:
Parameter
Recommended Value
Device Approval Voltage
24 V min
Device Approval Current
250 mA min
Device Input Power
1,2 W min
Device Residual Capacitance
5 nF max
Device Residual Inductance
20 uH max
I.S. Classification
EX ia IIC (gas groups A & B) T4
Source: Foundation Fieldbus Application Guide 31.25 kbp/s Intrinsically Safe Systems AG-163 Rev 2.0
Fieldbus I.S. Power Architecture
I.S. Fieldbus with Bus-Powered Devices
SAFE AREA
Ph
I.S. Interface
HAZARDOUS AREA
Th
Th
Db
Db
Db
Ph – Fieldbus Power Supply with I.S. Circuit
Db – I.S. Certified Bus-powered Device
Th – I.S. Certified Terminator
Source: Foundation Fieldbus Application Guide 31.25 kbp/s Intrinsically Safe Systems AG-163 Rev 2.0
NeSSI-Net Future Directions
• Room for Improvement?
- Extended Temperature Range
- Improved FISCO Node Count
- ProfiBus PA
• NIST Program
- Intrinsically Safe CAN bus
- Working Group Established
- Adoption of CANOpen
- Definition of Physical Layer
- Prototype in Development
- IS Certification costs Discussed
The Network Enables Information and Uptime
Honeywell Foundation Fieldbus
New Experion R300 Series C Foundation Fieldbus Module
• 4 Fieldbus H1 channels
• Fully Redundant Configuration available
• 100 Mbps to Experion Controller or directly to Server
www.honeywell.com
Thanks!
John Mosher, Honeywell Sensing & Control
(209) 339-4004
[email protected]