presentation_rarf_q_and_a_session_01102008

Download Report

Transcript presentation_rarf_q_and_a_session_01102008

RARF Addendum
Information / QnA Session
Dana Showalter
January 10, 2008
Addendum Summary
• Send dates:
– Addendum and Guide sent to Resource Entity Authorized
Representatives between January 4 and January 10
– If no addendum received, most likely a problem with the RARF
submitted on Nov 9
– Contact [email protected] with questions or to
request the addendum
• Due to ERCOT on January 31
– Send to [email protected] or submit via TML
• Column A
– Only “new fields” will be read into the database
– Any “existing” fields will continue to be read into the database off
of the RARF
2
Important Information (from Guide)
• The purpose is to gather additional planning data for EDS 4
RARF
• The Addendum has locked fields – these are typically
information gathered from the RARF and used as reference.
Corrections to these fields should be made on the RARF itself
• All data in this addendum is unit or site specific. No CC train or
CC configuration information is included nor requested
• For both the RARF and the Addendum, the unit and site codes
should not be changed, as these correlate to existing codes
used in ERCOT systems
• Pre-populated fields contain data from RARFs received prior to
December 18, 2007
3
Important Information (continued)
• Why do Resource Entities need to fill out this Addendum and
correct the RARF?
– In order to avoid manual data corrections in the database, each
field (row) of the RARF and addendum are only read into the
database from one form. If the field is on the RARF – it will
continue to be read from the RARF. Only new fields identified on
the Addendum will be read into the ERCOT database. This helps
with quality control and limits manual loading of information.
4
Additional Assets Addendum – Why?
5
Additional Assets Addendum
• ERCOT Branch Data can assist with filling this out
– Found in Operations Model Data folder on secure Operations
and System Planning Website
– http://oldercot.ercot.com/tmaps/login.cfm
• TSP will be familiar with naming conventions and may be able
to provide assistance
• Additional questions should be directed to
[email protected] who will redirect to ERCOT
planning
6
Private Use Network Addendum
• Should only be on Addendums for PUN Resources
• Site and unit information requested
• Site information includes:
– Totals of MWs, MVARs
– Totals of Gross Generation, Average Load, and Average Net to
grid
• Injection (positive) OR consumption (negative)
– Load characteristics (in %, should add to 100% for MW and
100% for MVAR)
• Unit information includes:
– Allocating the MWs and MVARs across the units (should sum up
to site totals)
– Unit trip information
7
Private Use Network Addendum – Site Information
•
•
•
Enter totals for site (all units represented on RARF)
Please note that these values should be gross generation and load and only net
values for specific rows.
A simple check would be: Net Interchange = Gross Capability – Self Serve Load
GENERAL
Existing RARF
(locked)
Notes
ERCOT Station Code Mnemonic for Generator Site
Populated to match RARF - this field should not be changed.
PRIVATE NETWORK - SITE INFORMATION
Existing RARF
(locked)
New Field
Private Network (Y or N)
Enter as Y or N
Average Amount of Self-Serve private load (MW)
Site Total MW Load (also remains on RARF where load is allocated to
each unit).
Site Total MVAR Load (also new field on Gen/CC tab to allocate to
each unit).
Enter as MW - typical net interchange for the site. Positive values
indicate net generator on grid. Negative values indicate net load on
grid.
Enter as MVAR - typical net interchange for the site. Positive values
indicate net generator on grid. Negative values indicate net load on
grid.
Total generation capability of all the private network generators at the
site in MW.
Total reactive capability of all the private network generators at the site
in MVAR.
New Field
Average Amount of Self-Serve private reactive load (MVAR)
New Field
Expected Typical Private Network Net Interchange (MW)
New Field
Expected Typical Private Network Net Reactive Interchange (MVAR)
New Field
Private Network Gross Unit Capability (MW)
New Field
Private Network Gross Unit Reactive Capability (MVAR)
8
Private Use Network Addendum – Site Information
•
•
•
Enter on RARF in Unit 1 column
If multiple tabs, enter same data on all tabs in Unit 1 column
Resistive MVAR load is not needed
Existing RARF
(locked)
Load Characteristics:
--Large Motor, percent of total MW load
Existing RARF
(locked)
-Small Motor, percent of total MW load
Existing RARF
(locked)
-Resistive (Heating) Load, percent of total MW load
Existing RARF
(locked)
-Discharge Lighting, percent of total MW load
Existing RARF
(locked)
-Other, percent of total MW load
Existing RARF
(locked)
--Large Motor, percent of total MVAR load
Existing RARF
(locked)
-Small Motor, percent of total MVAR load
Existing RARF
(locked)
-Discharge Lighting, percent of total MVAR load
Existing RARF
(locked)
-Other, percent of total MVAR load
Defined by electrical connection of 4160V and up. Enter as a
percentage of total MW Load (Average Amount of Self-Serve private
load MW)
Defined as electrically connected at voltage less than 2400/4160V.
Enter as a percentage of total MW Load (Average Amount of SelfServe private load MW)
Enter as a percentage of total MW Load (Average Amount of SelfServe private load MW)
Enter as a percentage of total MW Load (Average Amount of SelfServe private load MW)
Enter as a percentage of total MW Load (Average Amount of SelfServe private load MW). The Large Motor, Small Motor, Resistive,
Discharge Lighting, and Other should total 100% of the Total MW
Load.
Defined by electrical connection of 4160V and up. Enter as a
percentage of total MVAR Load (Average Amount of Self-Serve private
reactive load MVAR)
Defined as electrically connected at voltage less than 2400/4160V.
Enter as a percentage of total MVAR Load (Average Amount of SelfServe private reactive load MVAR)
Enter as a percentage of total MVAR Load (Average Amount of SelfServe private reactive load MVAR)
Enter as a percentage of total MVAR Load (Average Amount of SelfServe private reactive load MVAR). The Large Motor, Small Motor,
Discharge Lighting, and Other should total 100% of the Total MVAR
Load.
9
Private Use Network Addendum – Unit Information
•
•
•
Allocate site totals across units
Sum of allocation to equal site totals
Enter unit trip information as applicable
PRIVATE NETWORK - Unit Information
Existing RARF
(locked)
Private Network (Y or N)
Existing RARF
(locked)
Average Amount of Self-Serve private load (MW)
Carry over from PN Tab. If N - disregard this section. If Y allocate totals from PN Tab across the unit fields
Total MW Load allocated across the units.
Average Amount of Self-Serve private reactive load (MVAR)
Total MVAR Load allocated across the units.
Expected Typical Private Network Net Interchange (MW)
Private Network Gross Unit Capability (MW)
Enter as MW - typical net interchange - allocated across the
units. Positive values indicate net generator on grid. Negative
values indicate net load on grid.
Enter as MVAR - typical net interchange - allocated across the
units. Positive values indicate net generator on grid. Negative
values indicate net load on grid.
Total generation capability of each unit.
Private Network Gross Unit Reactive Capability (MVAR)
Total reactive capability of each unit.
If Generation trips, does Load trip?
If the unit trips, does the load associated with this unit trip?
New Field
Existing RARF
(locked)
New Field
Existing RARF
(locked)
New Field
Existing RARF
(locked)
Existing RARF
(locked)
Expected Typical Private Network Net Reactive Interchange (MVAR)
If load trips, approximately what percentage of the associated
load will trip within 1 minute?
If yes, approximate percentage of Load that will trip?
10
Gen and CC Addendum Error
• MW and MVAR values are swapped on Addendum only
– Values in database correspond to values on RARF
– No changes needed due to this mis-population as it was
provided for reference only
• To avoid in future
– Test load with column name, which can be verified against RARF
field
11
Gen and CC Addendum
•
•
Please ensure we get four ratings – the generator nameplate ratings in
MVA, MW, and MVAR and the turbine rating in MW.
Please note the nameplate ratings should correspond to a nameplate
power factor.
– New: Turbine Rating (MW)
– Renamed: Generator Name Plate Rating (MVA)
– Corrected: label error noted in previous WebEx conversations where
Rating (MVA) was used for reactive power. Please check this and
correct on RARF if needed.
GENERAL
Notes
Existing RARF ERCOT Unit Code Mnemonic for Generator Site
(locked)
Populated to match RARF - this field should not be
changed.
Generator Unit Information
Existing RARF
(locked)
Existing RARF
(locked)
Existing RARF
(locked)
New Field
Nameplate MVA of generator unit. Provided as a reference.
Generator Name Plate Rating (MVA)
Rating (MW)
Nameplate MW of generator unit. Provided as a reference.
Rating (MVAR)
Nameplate MVAR of generator unit. Provided as a reference.
MW rating of Turbine if different (larger or smaller) than
Generator.
Turbine Rating (MW)
12
Gen and CC Addendum
•
•
•
The two sections pictured below are omissions from the RARF.
The voltage connection is needed for the step up transformer and was
originally requested on the Generation Data Forms.
As noted in previous WebEx sessions, details about the total unit
auxiliary load were missing.
– The auxiliary load characteristics should be completed on the RARF for
each unit in percentage of total aux load.
– The percentages should add up to 100%, as it is allocating the total aux
load that will now associated with the generator with these new fields.
Generator Step Up Transformer
New Field
High Voltage Connection - Wye or Delta
Select high voltage connection - WYE or DELTA.
New Field
Low Voltage Connection - Wye or Delta
Select low voltage connection - WYE or DELTA.
Generator Aux Load
New Field
Average Amount of Auxiliary load (MW)
Total MW Auxiliary Load. Fill out load characteristics on RARF.
New Field
Average Amount of Auxiliary reactive load (MVAR)
Total MVAR Auxiliary Load. Fill out load characteristics on
RARF.
13
Gen and CC Addendum
•
Please answer these questions and when ERCOT needs the additional
forms, they will be distributed to those that are affected
PSSE Model - Non-Wind Generation Resources
New Field
Existing RARF
(locked)
Turbine-Governor Form on file with ERCOT? (Y or N)
Existing RARF
(locked)
Excitation Form on file with ERCOT? (Y or N)
Existing RARF
(locked)
Do you have a Power System Stabilizer?
Existing RARF
(locked)
Existing RARF
(locked)
New Field
New Field
New Field
New Field
Select Y or N. ERCOT will work with you to find an answer if it
is not readily available.
Select Y or N. A possible source of information include
previously signed GARF. This is provided for reference. To
correct/enter this field, please use the RARF.
Select Y or N. A possible source of information include
previously signed GARF. This is provided for reference. To
correct/enter this field, please use the RARF.
Select Y or N. A possible source of information include
previously signed GARF. This is provided for reference. To
correct/enter this field, please use the RARF.
Select Y or N. A possible source of information include
previously signed GARF. This is provided for reference. To
correct/enter this field, please use the RARF.
Select Y or N. A possible source of information include
previously signed GARF. This is provided for reference. To
correct/enter this field, please use the RARF.
Select Y or N.
Generator Form on file with ERCOT? (Y or N)
If so, is Stabilizer Form on file with ERCOT? (Y or N)
Compensator Form on file with ERCOT? (Y or N)
Do you have a Over Excitation Limiter?
If so, is Over Excitation Limiter Form on file with ERCOT? (Y or N)
Do you have a Under Excitation Limiter?
If so, is Under Excitation Limiter Form on file with ERCOT? (Y or N)
14
Select Y or N. ERCOT will work with you to find an answer if it
is not readily available.
Select Y or N.
Select Y or N. ERCOT will work with you to find an answer if it
is not readily available.
Wind Addendum
•
Add rating for each turbine model of a wind unit
GENERAL
Notes
Existing RARF ERCOT Unit Code Mnemonic for Generator Site
(locked)
Populated to match RARF - this field should not be
changed.
Generator Unit Information
New Field
Added MW design ratings for each turbine group corresponding
to the models and quantities on the RARF.
Added MW design ratings for each turbine group corresponding
to the models and quantities on the RARF.
Added MW design ratings for each turbine group corresponding
to the models and quantities on the RARF.
Added MW design ratings for each turbine group corresponding
to the models and quantities on the RARF.
Added MW design ratings for each turbine group corresponding
to the models and quantities on the RARF.
Group 1 - MW Rating per Turbine
New Field
Group 2 - MW Rating per Turbine
New Field
Group 3 - MW Rating per Turbine
New Field
Group 4 - MW Rating per Turbine
New Field
Group 5 - MW Rating per Turbine
15
Wind Addendum
•
The voltage connection is needed for the step up transformer and was
originally requested on the Generation Data Forms
•
Please answer these questions and when ERCOT needs the additional
forms, they will be distributed to those that are affected
Generator Step Up Transformer
New Field
High Voltage Connection - Wye or Delta
Select high voltage connection - WYE or DELTA.
New Field
Low Voltage Connection - Wye or Delta
Select low voltage connection - WYE or DELTA.
PSSE Model - Non-Wind Generation Resources
New Field
New Field
Select Y or N. ERCOT will work with you to find an answer if it
PSSE Compatible Wind Generator Models submitted to ERCOT? (Y or N)is not readily available.
Select Y or N.
Do you have a Dynamic Reactive Device? (Y or N)
New Field
Select Y or N. A possible source of information include
previously signed GARF. This is provided for reference. To
correct/enter
If so, is corresponding Dynamic Reactive Device Form on file with ERCOT?
(Y or N) this field, please use the RARF.
16
RARF Update
• To protect database integrity
– RARFs must be submitted by Resource Entity
– DUNs numbers of entities (submitting and owners) must align
with proper entity
– General Information tab must be complete
– Resource Entities are being asked to clarify this information if
conflicts exist
• Additional RARF corrections may be requested as more data is
applied to ERCOT Nodal Systems
– Every attempt will be made to clearly state what needs corrected
and why (i.e. if the field requires KV and 138000 is entered)
– RARF will need to be corrected on the RE end and submitted to
ERCOT to keep the database matching the currently submitted
RARF (the process will be after the certified RARF)
– Working together we can get the most complete, accurate RARF
• Internal effort by Registration Team to encourage data is being
validated by systems proactively.
17
RARF Update
• Scorecards will be updated with RARF data – Target Date
January 18, 2008
• TPTF Update during the January 21-23, 2008 meeting will
identify upcoming dates and events
• Combined Cycle units may have a forthcoming addendum
• Resource Entities that have not submitted RARFs will be
identified at the February, 2008 TAC meeting
18