HC-202D Ionization Smoke Detector

Download Report

Transcript HC-202D Ionization Smoke Detector

Characteristics /
1.Has monitoring function. The LED flashes once
every 4 ~ 6 seconds.
2.There are two LEDs which can turn 360o and watch the
situation of the detector at any angle.
3.It provides the wiring (-R) function of entrance LED.
4.The use of common base is advantageous to the
exchange of detector.
Functioning way/
As there is smoke getting in the detector, the ion current will be decreased,
making the voltage increase and touching the detector to function and send out
alarm. Meanwhile, the LED will be turned on automatically. Under normal
situation, the LED has monitoring function. And as it functions, the LED keeps
turning on continuously. It is suitable for installation at the places like the
entrance of staircase, corridor, lift hall, indoor room, etc.
Specifications /
Model No
HC-202D Ionization Smoke Detector
Adopted voltage
18V-28V (DC24V)
Mainframe
Fire-resisting ABS resin
material
Monitoring
electric current
35μA
Joint
terminal
Copper rod (zinc-plated)
Functioning
electric current
60mA
Color
Suitable
temperature
-15~50° C
Suitable humidity
0~95% RH
Size
103mm x 47mm
Weight
140g
General wiring drawing /
Overall structure
Ivory
Notes
Prohibit from being installed at the
places with large volume of smoke and
steam lingering, and the inlet and outlet
of cold and warm air.
Wiring drawing of entrance LED /