EPack is fully configurable/upgradable except
Download
Report
Transcript EPack is fully configurable/upgradable except
EPack relaunch
●1. Reduce your equipment costs
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
2
EPack - What is it?
A new range of power controllers
1 phase products for the moment
Complement range to Epower
Low to middle current ratings (16A to 125A)
Advanced product (levels 1 and 2)
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
3
General overview
Supplies
Auxiliary
supplies
Voltage
Connexions line/load
reference
Relay
Coloured TFT display
Analog./ Digital
inputs
Touch buttons
Dual Ethernet port
Inputs/Outputs
Line connexion
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
Load connexion
4
32A
63A
100A
125A
Hardware variants
EPack is fully configurable/upgradable except :
- The mechanics (32A, 63A, 100A or 125A)
- The voltage of the auxiliary voltage
(24V AC/DC or 100-500V AC)
These options require a different build of the
product and can’t be changed in the field.
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
5
Supplies
The product is equipped with two supplies :
o Power > thyristor
o Auxiliary > comms and display
Why?
We cannot use power voltage for configuration
Potential at the output of the product at 0% of setpoint => Safety
issues
To run comms even in case of power fault
Can provide diagnostics in every condition
To be able to configure the product without dangerous voltage
Configuration can be made with presence of 24V only
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
6
Firing modes
All firing modes are available in standard
Burst modes
Fixed burst (100 periods by default, adjustable from 25 to 1000)
Variable burst (16 periods by default, adjustable from 1 to 100)
Intelligent half cycle
Phase angle
Progressive start-up (phase angle ramp)
Delay triggering (First firing delay)
Switch phase angle/ burst
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
7
Control modes
EPack is able to deliver the power based on the following controls
V² control
Suitable for pure resistive loads (constant resistance)
V² control with current limit (V2CL)
Suitable for primaries of transformers with pure resistive loads
I² control
Suitable for HTCL loads / bushing
True Power control
Suitable whose resistance changes according to age or temperature
(TTDL)
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
8
I/O and relay
IO connector (5 points)
1 analog input fully configurable
Function : SP, limit….
Type : 0-5V, 1-5V, 0-10V, 2-10V,
0-20mA, 4-20mA
2 digital inputs fully configurable
Function DI1 : enable signal by default
Function DI2 : fully configurable
Type : voltage or contact
Relay connector (3 points)
2A relays
2 contacts (NO and NC)
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
9
3 configuration methods
1. Complete oder code – 19 fields
Defines completely the product : fit for purpose
No adjustment in case of replacement
2. Quick code – 11 fields
Hardware and software options defined by order code
Configuration through set of questions
More than 80% of applications are covered
3. Itools
Same as quick code for HW and SW definition
Access to all parameters of the product / with help available
Saving and cloning capabilities
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
10
Comms
Protocol
Modbus TCP for the moment
Other protocols to come…
Connection
Direct
Through a switch
Daisy chain
Dual Ethernet port
with integrated
switch
Cable
Straight
Cross
Used for
Itools configuration
Fieldbus connection
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
11
Zero conf protocol
What is it?
Zero configuration networking (zeroconf) is a set of techniques that
automatically creates a usable Internet Protocol (IP) network without
manual operator intervention or special configuration servers
How does it work?
It allocates dynamically the IP addresses to the slaves if no address is
affected by DHCP server (Auto-IP)
What does it result in?
A plug a play Ethernet connection!
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
12
Fuse options
No internal fuse
Fusing methods depends on the option
Without fuse
for loads generating high surge current (typically SWIR)
Requires protection against overloads and short circuit
High speed fuse
Protect thyristor against short circuit
Requires additional line protection
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
13
Standard vs options
Standard
Chargeable
Firing modes
All modes
None
Control modes
V², V²CL
I², True Power
Transfer
Without
I² transfer
Input types
All types
None
32A mechanics
16A
25A, 32A
63A mechanics
40A
50A,63A
100A mechanics
80A
100A
Fuse
Without
Yes
Energy counter
Without
yes
Graphical wiring
Without
yes
Custom labelling
Eurotherm label
yes
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
14
Typical schemes
24V version
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
500V version
15
Standards
1.Product standard IEC 60947-4-3
2.UL/c-UL 60947 with SCCR @ 100kA
3.RoHS (RoHS 2 pending)
4.GOST exemption
5.CCC self certification
Schneider Electric -
Industrial – Eurotherm – 08/04/2016