EPack is fully configurable/upgradable except

Download Report

Transcript EPack is fully configurable/upgradable except

EPack relaunch
●1. Reduce your equipment costs
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
2
EPack - What is it?
A new range of power controllers
 1 phase products for the moment
 Complement range to Epower
 Low to middle current ratings (16A to 125A)
 Advanced product (levels 1 and 2)
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
3
General overview
Supplies
Auxiliary
supplies
Voltage
Connexions line/load
reference
Relay
Coloured TFT display
Analog./ Digital
inputs
Touch buttons
Dual Ethernet port
Inputs/Outputs
Line connexion
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
Load connexion
4
32A
63A
100A
125A
Hardware variants
EPack is fully configurable/upgradable except :
- The mechanics (32A, 63A, 100A or 125A)
- The voltage of the auxiliary voltage
(24V AC/DC or 100-500V AC)
These options require a different build of the
product and can’t be changed in the field.
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
5
Supplies
The product is equipped with two supplies :
o Power > thyristor
o Auxiliary > comms and display
Why?
 We cannot use power voltage for configuration
 Potential at the output of the product at 0% of setpoint => Safety
issues
To run comms even in case of power fault
 Can provide diagnostics in every condition
To be able to configure the product without dangerous voltage
 Configuration can be made with presence of 24V only
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
6
Firing modes
All firing modes are available in standard
Burst modes
 Fixed burst (100 periods by default, adjustable from 25 to 1000)
 Variable burst (16 periods by default, adjustable from 1 to 100)
 Intelligent half cycle
Phase angle
Progressive start-up (phase angle ramp)
Delay triggering (First firing delay)
Switch phase angle/ burst
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
7
Control modes
EPack is able to deliver the power based on the following controls
V² control
 Suitable for pure resistive loads (constant resistance)
V² control with current limit (V2CL)
 Suitable for primaries of transformers with pure resistive loads
I² control
 Suitable for HTCL loads / bushing
True Power control
 Suitable whose resistance changes according to age or temperature
(TTDL)
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
8
I/O and relay
IO connector (5 points)
1 analog input fully configurable
 Function : SP, limit….
 Type : 0-5V, 1-5V, 0-10V, 2-10V,
0-20mA, 4-20mA
 2 digital inputs fully configurable
 Function DI1 : enable signal by default
 Function DI2 : fully configurable
 Type : voltage or contact
Relay connector (3 points)
 2A relays
 2 contacts (NO and NC)
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
9
3 configuration methods
1. Complete oder code – 19 fields
 Defines completely the product : fit for purpose
 No adjustment in case of replacement
2. Quick code – 11 fields
 Hardware and software options defined by order code
 Configuration through set of questions
 More than 80% of applications are covered
3. Itools
 Same as quick code for HW and SW definition
 Access to all parameters of the product / with help available
 Saving and cloning capabilities
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
10
Comms
 Protocol
 Modbus TCP for the moment
 Other protocols to come…
 Connection
 Direct
 Through a switch
 Daisy chain
Dual Ethernet port
with integrated
switch
 Cable
 Straight
 Cross
 Used for
 Itools configuration
 Fieldbus connection
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
11
Zero conf protocol
What is it?
 Zero configuration networking (zeroconf) is a set of techniques that
automatically creates a usable Internet Protocol (IP) network without
manual operator intervention or special configuration servers
How does it work?
 It allocates dynamically the IP addresses to the slaves if no address is
affected by DHCP server (Auto-IP)
What does it result in?
 A plug a play Ethernet connection!
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
12
Fuse options
No internal fuse
Fusing methods depends on the option
Without fuse
 for loads generating high surge current (typically SWIR)
 Requires protection against overloads and short circuit
High speed fuse
 Protect thyristor against short circuit
 Requires additional line protection
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
13
Standard vs options
Standard
Chargeable
Firing modes
All modes
None
Control modes
V², V²CL
I², True Power
Transfer
Without
I² transfer
Input types
All types
None
32A mechanics
16A
25A, 32A
63A mechanics
40A
50A,63A
100A mechanics
80A
100A
Fuse
Without
Yes
Energy counter
Without
yes
Graphical wiring
Without
yes
Custom labelling
Eurotherm label
yes
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
14
Typical schemes
24V version
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
500V version
15
Standards
1.Product standard IEC 60947-4-3
2.UL/c-UL 60947 with SCCR @ 100kA
3.RoHS (RoHS 2 pending)
4.GOST exemption
5.CCC self certification
Schneider Electric -
Industrial – Eurotherm – 08/04/2016
16