Automation and Drives

Download Report

Transcript Automation and Drives

Automation and Drives
SITOP select
SITOP select
Electronic Diagnosis Module
Fault diagnosis – rapid and reliable
Automation and Drives
Blow the whistle on plant downtimes
SITOP select
Keep the overview of your 24V load
feeders.
Show the red card to downtimes
caused by faults
SITOP select fault diagnosis - rapid and reliable
A&D SE PS 23.04.2002
2
Automation and Drives
The situation today
SITOP select
The situation today
The solution
Circuit diagram
Characteristic
Circuit diagram of the power distribution for
selective protection
Power supply, e.g. SITOP power
Drop in 24 V !
+
~
=
24 V
–
Device features
Data
4A
Load 1
SITOP select fault diagnosis - rapid and reliable
6A
Load 2
10A
Load 3
10A
Load 4
A&D SE PS 23.04.2002
3
Automation and Drives
The situation today
SITOP select
The situation today
The solution
Reasons for selective triggering failure when fault occurs


Long load lines
Creeping short circuits
 Line circuit breakers dimensioned too large
Circuit diagram
Characteristic
Device features
Data

Consequences



Plant standstill due to drop in 24 V power
Trouble-shooting much more difficult
Long standstill times
Reason for undesired triggering during operation


Excessive current peaks during startup
Consequence

Malfunction, machine/plant switches off
SITOP select fault diagnosis - rapid and reliable
A&D SE PS 23.04.2002
4
Automation and Drives
The solution
SITOP select
The situation today
The solution
Circuit diagram
Characteristic
Fault paths are powered down reliably even under very
poor operational conditions.



Retension of the 24 V power for all other paths
Plant down time is reduced or even avoided.
Fast trouble-shooting and fault localization
Device features
Data
Loads with high startup current peaks power up with
current limitation.

Malfunction-free device startup
SITOP select fault diagnosis - rapid and reliable
A&D SE PS 23.04.2002
5
Automation and Drives
The solution
SITOP select
The situation today
The solution
Circuit diagram
Characteristic
Device features
Data
Selectivity and fast error diagnosis of 24 V feeder circuits


Four feeder circuits (outputs) per module
Each output can be set between 2 and 10 A using
potentiometer.
 Multi-color LED for each output for rapid fault localization
 Potential-free common signal contact for fault diagnosis
 Several modules can be connected to a single power supply.
 Simple and rapid installation using standard mounting rail
 Additional line protection and gradual equipment
commissioning with exchangeable FK2 blade-type fuse
SITOP select fault diagnosis - rapid and reliable
A&D SE PS 23.04.2002
6
Automation and Drives
Circuit diagram
SITOP select
The situation today
The solution
Circuit diagram
Characteristic
Diagnosis module with 4 outputs for current distribution
Power supply, e.g. SITOP power
+
~
=
24 V
–
SITOP select
Reset
Device features
Data
Control Logics
Potential-free
signalling
contact
SITOP select fault diagnosis - rapid and reliable
Load 1
Load 2
Load 3
Load 4
A&D SE PS 23.04.2002
7
Automation and Drives
Switching characteristic
SITOP select
The situation today
The solution
Irated can be adjusted from 2 to 10 A per output circuit. Characteristics per current
requirements depend on the output circuit.



Circuit diagram
Characteristic

From 0 A to the set value ( I/ Irated=100%)  without switching off
From set value up to 130%
 switch off after approx. 5 sec
Above 130% of set value
 current limiting to 130% for 50 to
100 msec, next switch off
Over the set value with simultaneous
collapse of the supply voltage below 20V  immediate switch off
Device features
Data
100.0 sec
t
10.0 sec
5.0 sec
1.0 sec
0.10 sec
0.1 sec
0.0 sec
0%
50%
100%
150%
I / I rated
SITOP select fault diagnosis - rapid and reliable
A&D SE PS 23.04.2002
8
Automation and Drives
Device features
SITOP select
The situation today
Output terminals
Common signalling contact
The solution
Circuit diagram
Blade-type
FK2 fuse
Characteristic
Device features
Data
Two-color
LED
Labeling field
Potentiometer
Input terminals
SITOP select fault diagnosis - rapid and reliable
Reset
A&D SE PS 23.04.2002
9
Automation and Drives
Ordering data, technical specifications
SITOP select
The situation today
The solution
Circuit diagram
Characteristic
Device features
Order Number
Input
•Rated voltage Vin rated
•Voltage range
•Input current
Output
•Number of output channels
•Rated voltage Vout rated
•Rated current Iout up to +60 °C
•Setting range
Efficiency at V out rated ,I out rated
Protection and monitoring
•Wire protection
Data
•Operation indication
(two-color LED per channel)
•Signalling contact
Class of protection
Degree of protection
CE certification
TÜV type approval
UL/cUL (CSA) approval
Electromagnetic compatibility EMC
•Emitted interference
•Noise immunity
Ambient temperature range
Dimensions (width x height x depth)
Weight
6EP1961-2BA00
DC 24 V
22 to 30 V
40 A max.
4 per module
Vin -0.5 V
10 A per channel
2 to 10 A per channel
Approx. 97%
One blade-type FK2 15 A fuse per channel
Externally accessible
Green for switched output
Red for output switched off due to overload/short-circuit
Common signalling contact (N/O contact)
Class III (IEC 536; VDE 0106 T1)
IP 20 (EN 60 529; VDE 0470 T1)
Yes
Yes
UL 508, File 197259
EN 50081-1, EN 55022 class B
EN 50082-2
0 to +60 °C with natural air circulation
72 x 90 x approx. 90 mm
Approx. 0.4 kg
SITOP select fault diagnosis - rapid and reliable
A&D SE PS 23.04.2002
10