POWER QUALITY IN THE PHILIPPINES
Download
Report
Transcript POWER QUALITY IN THE PHILIPPINES
POWER QUALITY AND THE
PHILIPPINE GRID CODE
Power Quality during the late 90’s
PQ was dominated by Fluke and LEM
Power Utilities has just started talking about
standards to be followed
National Power Corporation, Meralco - main
proponents in the utility companies involved
in setting up the standards
A very few manufacturing companies are
aware of the need of PQ for their facilities
Power Quality in the 2000’s
More players came in (RPM, Dranetz-DMI, Hioki,
EIG, AEMC, Unipower, etc)
Philippine Grid Code was published and started
to be implemented (2001)
Philippine Distribution Code was published and
started to be implemented (2001)
TransCo was separated from the National Power
Corporation (2003)
National Power Corporation, TransCo, Meralco became models in the PQ standardization
Power Quality in the 2000’s (cont..)
Privatization of the government owned
Power Plants
TransCo became the National Grid
Corporation of the Philippines (NGCP)
Models for PQ originates from NGCP and
Meralco using the PGC and PDC as basis for
the standards
Manufacturing facilities engineers became
aware of the need to implement PM involving
PQ
Grid Code PQ Requirements
Power Quality Performance (Article 3.2)
System Frequency Deviation
Voltage Magnitudes Variations
Voltage Fluctuations
Harmonic Frequencies
Voltage Unbalance
Transient Voltage Variations
Grid Code PQ Requirements
Frequency Variations
Nominal Frequency – 60 Hz
Maintain Frequency during normal conditions
Limits: 59.4 Hz ≤ f ≤ 60.6 Hz
Grid Code PQ Requirements
Voltage Variations
Long Duration Voltage Variation
Duration greater than 1 minute
Undervoltage (RMS value is less than or equal to 90%
of the nominal value)
Overvoltage (RMS value is greater than or equal to
110% of the nominal value)
95% ≤ RMS nominal voltage ≤ 105%
Grid Code PQ Requirements
Voltage Variations
Short Duration Voltage Variation
Duration greater than ½ cycle but not exceeding 1
minute
Voltage Swell (RMS value increases between 110%
and 180% of the nominal value)
Voltage Sag (RMS value decreases between 10% and
90% of the nominal value)
Grid Code PQ Requirements
Voltage Fluctuation
Random amplitude changes of RMS value
between 90% to 110% of the nominal voltage
Voltage fluctuation shall not exceed 1% of the
nominal voltage for every step change, which
may occur repetitively
Large voltage fluctuation other than a step
change maybe allowed up to 3% provided will
not put risk to the Grid or any User system
Grid Code PQ Requirements
Flicker Severity
Short Term Flicker Severity (PST) – short duty
cycle fluctuation,shall be computed over a 10minute period
Short Term Flicker Severity (PLT) – long and
variable duty cycle fluctuation, derived from
PST levels
Grid Code PQ Requirements
Harmonics
Total Harmonic Distortion (THD) – ratio of the
RMS value of the harmonic content to the
RMS value of the fundamental quantity in
percent
Grid Code PQ Requirements
Harmonics
Total Demand Distortion (TDD) – ratio of the
RMS value of the harmonic content to the
RMS value of the rated or maximum
fundamental quantity in percent
Grid Code PQ Requirements
Voltage Unbalance
Refers to negative sequence unbalance factor
or zero unbalance factor
Negative Sequence Unbalance Factor = Negative Sequence Components of Voltages
Positive Sequence Components of Voltages
Zero Sequence Unbalance Factor = Zero Sequence Components of Voltages
Positive Sequence Components of Voltages
Compliance:
Voltage Unbalance ≤ 1% for 115 kV and above
Voltage Unbalance ≤ 2.5% for 69 kV and below
Grid Code PQ Requirements
Transient Voltage Variations
High frequency overvoltages shorter in duration
compared to short duration voltage variations
In-frequent short-duration may exceed levels of
harmonics limits provided such increases do not
compromise service to End-users or cause
damage to Grid equipment
In-frequent short-duration with a maximum value of
2% maybe permitted for Voltage Unbalance
subject to terms of Connection Agreement
END OF PRESENTATION
THANK YOU