Transcript Lecture 9
Power System Fundamentals
EE 317
Lecture 9
27 October 2010
Aims
Chapter 6 – Parallel Operation of Synchronous
Generators
Chapter 6
Rationale for paralleling
Conditions for paralleling
Procedure for paralleling
Characteristics of a Synchronous Generator
Operation with an Infinite Bus
Operating with another of similar size
Paralleling generators
Why?
Higher loads
Increased reliability under failure
Maintenance
More efficient operation of the fleet
Conditions for paralleling
Rms line voltages must be equal
Same phase sequence
Phase angles must be equal
Frequency of new generator (oncoming unit)
must be slightly higher the frequency of the
running system
procedure
First – verify terminal voltage of oncoming generator
equals line voltage of system
Second – verify that the phase sequence of the
oncoming generator is the same as the phase
sequence of the running system (motor, bulbs)
Third – adjust the frequency of the oncoming unit to be
slightly higher than the frequency of the running system
(synchroscope)
Close circuit breaker when 1-3 are satisfied and the
generator is in phase with the power system
synchroscope
Measures the difference in phase angle between
the phases of two systems
Dial shows the difference between two a or b or
c phases
Faster (desirable) means clockwise from straight
up (which means in phase)
Characteristics of a
Synchronous Generator
When operating alone its P&Q supplied will
depend entirely on the P&Q demanded by the
load
Governor – sets the frequency and resulting
Real Power output of the synch. Generator
Field Current – controls the output terminal
voltage VT and resulting Reactive Power
Operation with an Infinite Bus
Infinite bus – a power system so large that any draw of
reactive and real power will not affect frequency and
voltage
Result: no reasonable action on the part of one
generator will cause an observable change in system
overall
Imperative that frequency of connected devices be
higher than system frequency when connecting
Reverse-power trip
Most real generators are equipped with a
reverse power trip so that if they do begin
to consume power they will disconnect
automatically.
Operating with another of similar
size
Sum of load P&Q is supplied by the n generators
Increase in governor set-point on one generator:
Increases system frequency
Decreases power supplied by other, up on this one
Increase in field current of one generator:
System terminal voltage is increased
Reactive power supplied by other is decreased
Paralleling Generators
Ch. 7 - Induction Machines
Motors and generators whose magnetic field current is
supplied by magnetic induction (transformer action) into
the field windings of the rotor (a DC power source is not
required)
Although induction machines can be motors or
generators they have many disadvantages as
generators. Thus, they are referred to typically as
induction motors. Most popular type of AC motor