Micron Transformer - Levine Lectronics and Lectric

Download Report

Transcript Micron Transformer - Levine Lectronics and Lectric

Micron Transformers
Presented by
Richard Lussier and John Levine
Levine Lectronics and Lectric
Types Of Transformers
•
•
•
•
•
Impervitran
Globaltran
LVGP
Buck Boost
Power Supplies
Impervitran
•
•
•
•
•
•
•
•
Made in USA
First Encapsulated Transformer
20 Year Warranty
Secondary Fuse Clips where applicable
Optional Primary Clips ( Factory / Field)
Touch Safe Terminal Covers
14 Standard Primary / Secondary selections
105 / 130 / 180 degree c rise
IMPERVITRAN
• Ratings UL CSA
50 – 60 HZ
Rated
• 25VA – 5 KVA open type
• Multiple Primary / Secondary
values
• Center tap secondary available
• Primary Voltages up to 600V AC
• Secondary Voltages 24V AC
• Custom Transformers
Globaltran
•
•
•
•
•
•
•
•
•
International Transformer
CE Labeled
50 – 60 HZ Ratings
Meets or exceeds IEC-742
Standard with Touch Safe
Terminals IP20
20 Year Warranty
7 Standard Pri / Sec Offerings
50 VA – 750 VA ratings
Customs Available
LVGP
Low Voltage General Purpose
• Dry Type Enclosed
Transformers
• Single Phase / Three
Phase Ratings
• Indoor / Outdoor
Ratings with optional
drip hoods
• 60 HZ Rating only
• Type 1 or 3R Enclosure
Rating Available
LVGP
Single Phase
•
•
•
•
•
•
Seven Standard Voltage Patterns
Voltage RangePri 120 to 600V
Secondary 120 – 240V AC
KVA Range 0.5 KVA – 167 KVA
Transformers 2 KVA and Below Copper
Transformers 3 KVA and Above Aluminum
LVGP
Three Phase
•
•
•
•
•
•
8 Standard Voltage Ranges
Voltage Range Primary 208V – 600V
Secondary 120V – 480V
KVA Range 3 KVA – 750 KVA
Transformers 2 KVA and Below Copper
Transformers 3 KVA and Above Aluminum
Buck Boost Transformers
• Buck Boost Transformers are used to convert a
lower or higher voltage to a more suitable
voltage.
• Ex. 230 to 208V
Buck
• 240 to 277
Boost
• Range is about 20 % voltage change
• Both Single and Three Phase Conversations
• Wired in Autotransformer configuration
•
•
•
•
•
•
•
•
•
Power Supplies
UL/ CUL/ UL508 / CE
5 Year Warranty
Voltage Input 85V – 264VAC
Secondary Voltage 12/24/48VDC
Wattage 60 – 480
Current 2.5 – 13.3 amps
Operating Temp - 10 Deg – 60 deg C
DIN Rail Mounting
Power Boost 25% for
5 sec
Power Supply
•
•
•
•
•
•
First IP67 Power Supply on Market
UL Recogonized, CUR, CE
Voltage 90 -264 V Primary
24 VDC Secondary
2 or 4 amp version
50 – 100 watt
Micron Transformers
Capabilities Module
Product Capabilities
•
•
ENCAPSULATED CONTROL TRANSFORMERS
IMPERVITRAN DESIGN -- Part numbers beginning with B
VOLTAGE CAPABILITY
– Primary 100V through 600V
– Secondary 5V through 240V
•
VA RANGE
– 25VA through 5000 VA
•
TEMPERATURE CLASS 105, 130 & 180
• Terminations available
– 4-terminal block-standard
– 6-terminal block-optional
– Fastons-optional
• Installed fusing capabilities
– Type "K" (13/32 x 1-1/2) secondary clips (standard
for most part numbers)
– Class "CC" primary fuse block
– Type "M" (9/16 x 2) secondary clips
– Type "Q" (1/4 x 1-1/4) secondary clips
– Thermal fusing
– Custom options available
Product Capabilities
III
LOW VOLTAGE GENERAL PURPOSE
(LVGP) and BUCK-BOOST
600 Volt Class
Part numbers starting with G, J
•
Single phase encapsulated and ventilated from 50VA
through 167KVA
•
Three phase encapsulated and ventilated from 3 through
750KVA
Features & Benefits
Features
ImperviTRAN designs
feature Class 105C, 130C &
180C encapsulated
construction.
Benefits
Customers can choose the
design system that best
serves their needs.
Features
ImperviTRAN designs
feature molded terminal
block construction.
All have provision for
SafeTouch IEC-529/IP-20
rated termination covers.
Benefits
Molded terminal blocks
provide superior strength,
electrical
insulation and ease of wire
termination.
IEC-529/IP-20 terminal
covers provide unsurpassed
product safety.
Features
Provision for secondary
fusing is standard on
most designs utilizing
molded terminal blocks.
Provision for primary fusing
available on
most designs.
Benefits
Saves valuable panel space
and simplifies panel
assembly.
Features
GlobalTRAN designs are
approved to IEC-989, 742
or 61558
and
carry the CE mark.
GlobalTRAN is designed in
ImperviTRAN construction.
Benefits
Meets the requirements of
the international Low
Voltage Directive
72/73/EEC.
GlobalTRAN can be
designed to virtually any
customer application.
Features
Unprecedented 20 year
warranty on control
Transformers (600 volt
class).
Benefits
Worry free performance for
the life of the application.
Features
General purpose enclosed
units available in a wide
selection of encapsulated or
ventilated, tapped and
untapped configuration.
Benefits
Allows for one of the widest
product choices in the
industry.
Micron Transformers
Part number module
ImperviTRAN, ValuTRAN,
EconoTRAN
• All ImperviTRAN P/Ns begin with “B”
– B050BTZ13JK
• All obsolete ValuTRAN P/Ns begin with “V”
– VF1K0BTZ13JK
• All obsolete EconoTRAN P/Ns begin with “E”
– EF1K0BTZ13
GlobalTRAN
• GlobalTRAN is built in ImperviTRAN
construction.
• All GlobalTRAN P/Ns end in “GA,GAF or
GAH”
– B050-2001-GA
– B150-2004-GAF
– B1K0-2008-GAH
Frequency
• ImperviTRAN designs are rated at 50/60 Hertz
(Hz).
• A 50Hz rated device can operate at 60Hz but a
60Hz device can’t operate at 50Hz.
– A device can always operate at a frequency higher
than nameplate.
• Some P/Ns include an “F” or “N” after the
initial letter.
– VF1K0BTZ13JK
– BN1K0BTZ13
– HN1K5G1519P
• The “F” = 50/60Hz.
• The “N” = 60Hz.
Exceptions
• P/Ns that date back before 1983
– May include a letter as the 2nd or 3rd character. This
identified the customer.
– BRQX040JCBXT7-50
– May include an “X” as the 2nd – 4th character. This
identified special construction.
– BX100MBT13
– BRQX040JCBXT7-50
Temperature Class
• An ending “F” denotes Class 130°C.
• B150BTZ13JKF
– Internally, Micron may replace with a leading “M”.
• M150BTZ13JK
• An ending “H” denotes Class 180°C.
• B1K5BTZ13JKH
– Internally, Micron may replace with a leading “N”.
• N1K5BTZ13JK
VA/KVA
• VA = Volts X Amps
• KVA = VA X 1000
• The numbers following the initial letter in the P/N =
VA size.
–
–
–
–
B050BTZ13JK (50VA)
B100BTZ13JK (100VA)
B100-2003-GA
VF1K0BTZ13JK (1000VA or 1KVA)
Primary Voltages
• The letters following the VA size = primary
voltage.
– B050LP7JK
• letters and representative voltages are:
–
–
–
–
B = 230
L = 120
M = 208
Q = 277
P = 240
R = 380
T = 460
U = 480
W = 575
• A “Z” as the last letter = transformer can
handle a voltage range  5% of nominal
voltage (triple rated).
– B050BTZ13JK
• 220/230/240
– B050WZ13XK
• 550/575/600
– B1K0BTWZ37XKH
• 220/230/240, 440/460/480, 550/575/600
Exceptions
• The “Z” is deleted on triple rated P/Ns that would be
longer than 12 characters.
– B100MBT713XK
• All voltage reference is deleted from serialized P/Ns.
– B150-0484-1
– B150-2004-GAF
Secondary Voltages
• The numbers following the primary voltage =
secondary voltage
– B050LP7JK
– B050MQ15XK
– B050MBT713XK
B050PU1519JJ
EF1K0BTZ1318
• letters and representative voltages are:
– 7 = 24
– 13 = 115
– 15 = 120
18 = 230
19 = 240
34 = 110/220
Exceptions
• All voltage reference is deleted from serialized
P/Ns.
– B150-0484-1
– B150-2004-GAF
Accessories
jumpers
fuse clips
covers
Jumpers
• Jumpers are used to connect terminals together.
Common uses are to derive either 230 or 460 from a
series/parallel wound device or sometimes to connect
fuse clips on the terminal block.
• Jumpers are denoted by a “J” as one or both of the
final 2 characters on the P/N.
– B050 BTZ13JK
– B050PU1519JJ
Exceptions
• Jumpers are included but not denoted in the
following P/N constructions:
EconoTRAN
EF1K0BTZ13
GlobalTRAN
B100-2003-GA
• The letter “T” as one of the last 2 characters
denotes an optional Stack ‘n Store (J3) jumper.
– B100BTZ13TK
Secondary Fuse Clips
• Virtually all ImperviTRAN products include mounted
fuse clips for a 13/32 X 1-1/2 midget fuse on the
secondary side.
• This is denoted with a “K” at the end of the P/N, –1
on a serialized P/N & “F” on GlobalTRAN.
–
–
–
–
B050BTZ13JK
B050MQ15XK
B050-0482-1
B050-2001-GF
• Mounted fuse clips for ¼ X 1¼ or 9/16 X 2 type
secondary fuses can be ordered by substituting the
“K” with the following letter:
– Q = ¼ X 1¼
– M = 9/16 X 2
B100BTZ13JQ
B100BTZ13JM
• A “-3” at the end of a serialized P/N= no fusing
capability.
Primary Fuse Blocks
• Class ‘CC’ style & midget style fuse blocks can be
ordered as a factory installed option on
ImperviTRAN & ValuTRAN.
• The letter “R” as the next to last character = a class
‘CC’ fuse block.
– B100BTZ13RB
• The letter “N” as the next to last character = a midget
style fuse block.
– B100BTZ13NB
• A “–8” on a serialized P/N = class ‘CC’ fuse block.
– B100-0483-8
• The letter “K” at the end of a GlobalTRAN P/N =
class ‘CC’ fuse block.
– B100-2003-GK
• The letter “G” at the end of a GlobalTRAN P/N when
secondary fusing is also ordered = class ‘CC’ fuse
block.
– B100-2003-GG
Exceptions
• P/Ns dating before 1983
– Will not include characters for jumpers or fuse clips
(although installed).
– B100BTZ13
– May include a customer identifier after the secondary
voltage identifier.
– BX050ER7-FE
– May include an identifier calling out a design feature, ie:
CT = Center Tap
– B050L7-CT
Safetouch Covers
• Safetouch covers are included with all
GlobalTRAN products.
• Safetouch covers are available for all products