SKEU2413 - Chapter 1 Part 2 transformer
Download
Report
Transcript SKEU2413 - Chapter 1 Part 2 transformer
Topic 1 : Magnetic Concept and
Transformer
Introduction
Two winding transformers
Construction and principles
Equivalent circuit
Determination of equivalent circuit parameters
Voltage regulation
Efficiency
Auto transformer
3 phase transformer
Introduction
Different variety of transformers
Introduction
Introduction
The word “Transformer” means an electromagnetic
device which transforms electrical power from one end to
another at different voltages and different currents
keeping frequency constant.
Unlike motor and generator it is static machine with
different turns ratio of primary and secondary windings
through which voltage/current is changed.
The transfer of energy takes place through the magnetic
field and all currents and voltages are AC.
The rating of transformer is either in kVA or MVA
because load to be connected is unknown
Introduction
Transformers are adapted to numerous engineering
applications and may be classified in many ways:
Power level (from fraction of a volt-ampere (VA) to over a
thousand MVA),
Application (power supply, impedance matching, circuit
isolation),
Frequency range (power, audio, radio frequency (RF))
Voltage class (a few volts to about 750 kilovolts)
Cooling type (air cooled, oil filled, fan cooled, water cooled,
etc.)-ONAN, ONAF
Purpose (distribution, rectifier, arc furnace, amplifier output,
etc.).
Introduction
Examples of transformer classifications:
Power Three phase transformers (Step up) used for transmission
of power (3-phase) at a distance
Distribution transformer (Step down) used for utilization of power
3-pahse/1-phase
Instrument Transformer (VT & CT) used for
measurement/practical
Auto Transformer (Single limb, electrically connected) used for
measurement, practical, supply/utilization
Isolation Transformer (having winding ratio of 1:1) used for safety
of human and equipment for sensitive appliances or practical
purpose
Introduction
The invention of transformer caused transmission
of heavy AC electrical power possible thus plays
important role in electrical power technology
Functions of transformer:
Raise or lower voltage or current in AC circuit
Isolate circuit from each other
Enable to transmit electrical power energy over large
distances at about >1200kV
Provides electrical power according to the utilization
needs
Transformer- Introduction
Power transmission
Introduction
A typical power system consists of generation, transmission
and distribution.
Power from plant/station is generated around 11-13-20-30kV
(depending upon manufacturer and demand).
This voltage is carried out at a distance to reach for utilization
through transmission line system by step up transformer at
different voltage levels depending upon distance and losses.
Its distribution is made through step down transformer
according to the consumer demand.
Here again at this stage, a transformer play an important role
to reduce the voltage to suit the consumer need.
Introduction
Power Transmission
Introduction
Transformer is a device that makes use of the
magnetically coupled coils to transfer energy.
It is typically consists of one primary winding coil
and one or more secondary windings.
The primary winding and its circuit is called the
Primary Side of the transformer.
The secondary winding and its circuit is called the
Secondary Side of the transformer.
A magnetic circuit provides the link between
primary and secondary.
Introduction
When an AC voltage Vp is applied to the primary winding of the
transformer, an AC current Ip will result.
Ip sets up a time-varying magnetic flux Ф in the core.
A voltage Vs is induced in the secondary circuit according to the
Faraday’s law.
Construction
The magnetic (iron) core is made
of thin laminated steel sheet.
to minimize the eddy current loss by
reducing thickness.
There are two common cross
section of core
square or (rectangular) for small
transformers
circular (stepped) for the large and 3
phase transformers.
Construction
Core (U/I) Type:
Constructed from a stack of U and I shaped laminations.
The primary and secondary windings are wound on two
different legs of the core.
Shell Type:
Constructed from a stack of E and I shaped laminations.
The primary and secondary windings are wound on the
same leg of the core, as concentric windings, one on top
of the other.
Construction
Construction
Construction
Construction
Ideal Transformer
Winding resistances are zero, no leakage inductance and iron
loss
Magnetization current generates a flux that induces voltage in
both windings
Current, voltages and flux in an unloaded ideal transformer
Ideal Transformer
Currents and fluxes in a loaded ideal
transformer
Ideal Transformer
Turn ratio
If the primary winding has N1 turns and secondary
winding has N2 turns, then:
The input and output complex powers are equal
Ideal Transformer
Functional description of a transformer:
a = 1
Isolation Transformer
| a | < 1
Step-Up Transformer
Voltage is increased from Primary side to secondary side
| a | > 1
Step-Down Transformer
Voltage is decreased from Primary side to secondary side
Ideal Transformer
Transformer Rating
Practical transformers are usually rated
based on:
Voltage Ratio (V1/V2) which gives us
the turns-ratio
Power Rating, small transformers are
given in Watts (real power) and Larger
ones (Power Transformers) are given in
kVA (apparent power)
Ideal Transformer
Example 1
Determine the turns-ratio of a 5 kVA
2400V/120V Power Transformer
Turns-Ratio = a = V1/V2 = 2400/120 = 20/1 = 20
This means it is a Step-Down transformer
Ideal Transformer
Example 2
A 480/2400 V (r.m.s) step-up ideal transformer
delivers 50 kW to a resistive load. Calculate:
the turns ratio,
(0.2)
the primary current,
(104.17A)
the secondary current.
(20.83A)
Ideal Transformer
Exercise 1
A 250kVA, 1100V/400v, 50Hz single-phase
transformer has 80 turns on the secondary.
Calculate:
the approximate values of the primary and secondary
currents
(227A, 625A)
the approximate number of primary turns
(220)
the maximum value of the flux
(22.5mWb)
Ideal Transformer
Nameplate of a transformer
Ideal Transformer
Equivalent circuit of an ideal transformer
Ideal Transformer
Equivalent circuit of an ideal transformer
Transferring impedances through a transformer
Ideal Transformer
Equivalent circuit when
secondary impedance is
transferred to primary side
and ideal transformer
eliminated.
Equivalent circuit when
primary source is
transferred to secondary
side and ideal transformer
eliminated.
Practical Transformer
Equivalent Circuit
In a practical magnetic core having finite
permeability, a magnetizing current Im is
required to establish a flux in the core.
This effect can be represented by a magnetizing
inductance Lm.
The core loss can be represented by a
resistance Rc.
Equivalent Circuit
Rc :core loss component
Xm : magnetization component
Equivalent Circuit
Phasor diagram of an unloaded transformer
Equivalent Circuit
Winding resistance and leakage flux
The effects of winding resistance and leakage flux are
respectively accounted for by resistance R and leakage
reactance X (2πfL).
Equivalent Circuit
Rc :core loss component
Xm : magnetization component
R1 and R2 are resistance of the primary and secondary winding
X1 and X2 are reactance of the primary and secondary winding
Equivalent Circuit
Phasor diagram of a loaded transformer
(secondary)
Equivalent Circuit
Phasor diagram of a loaded transformer
(primary)
Approximate Equivalent Circuit
Since no load current is very small(3-5% of full load), the
parallel circuit of Rc and Xm can be moved close to the
supply without significant error in calculation.
Calculations becomes easier
Approximate Equivalent Circuit
Calculations will be much more easy if the primary and
secondary circuit are combined.
Transfer the secondary circuit to the primary circuit
Approximate Equivalent Circuit
Phasor diagram of a loaded transformer
(primary)
Approximate Equivalent Circuit
For convenience, the turns is usually not shown
The resistance and reactance can be lumped together
We can also transfer the primary circuit to the secondary circuit
Approximate Equivalent Circuit
Example 3
A 100kVA transformer has 400 turns on the primary and 80
turns on the secondary. The primary and secondary
resistance are 0.3 ohm and 0.01 ohm respectively and the
corresponding leakage reactances are 1.1 ohm and 0.035
ohm respectively. The supply voltage is 2200V. Calculate:
the equivalent impedance referred to the primary circuit
(2.05 ohm)
the equivalent impedance referred to the secondary
circuit
(0.082)
Transformer Test
The equivalent circuit model for the actual transformer
can be used to predict the behavior of the transformer.
The parameters Rc, Xm, R1, X1, R2, X2 and N1/N2 must
be known so that the equivalent circuit model can be
used.
These parameters can be directly and more easily
determined by performing tests:
No load test (or open circuit test)
Short circuit test
Transformer Test
No load/Open circuit test
Provides magnetizing reactance (Xm) and core loss
resistance (Rc)
Obtain components are connected in parallel
Short circuit test
Provides combined leakage reactance and winding
resistance
Obtain components are connected in series
Transformer Test – Open Circuit
Equivalent circuit for open circuit test, measurement at the primary
side
Simplified equivalent circuit
Transformer Test – Open Circuit
Open circuit test evaluation
.
.
Transformer Test – Short
Circuit
Short circuit test
Secondary (normally the LV winding) is shorted, that
means there is no voltage across secondary
terminals; but a large current flows in the secondary.
Test is done at reduced voltage (about 5% of rated
voltage, with full-load current in the secondary.
Hence the induced flux are also 5%) The core losses is
negligible since it is approximately proportional to the square
of the flux.
So, the ammeter reads the full-load current; the wattmeter
reads the winding losses, and the voltmeter reads the applied
primary voltage.
Transformer Test – Short
Circuit
Equivalent circuit for short circuit test, measurement at the primary
side
Simplified equivalent circuit
Transformer Test – Short
Circuit
Simplified circuit for calculation of series impedance
Primary and secondary impedances are combined
.
.
Transformer Test – Short
Circuit
Short circuit test evaluation
.
.
Transformer Test
Equivalent circuit for a real transformer resulting
from the open and short circuit tests.
Transformer Test
Example 4
Obtain the equivalent circuit of a 200/400V,
50Hz 1-phase transformer from the following test
data:O/C test : 200V, 0.7A, 70W - on L.V. side(LV data)
S/C test : 15V, 10A, 85W - on H.V. side(HV data)
(Rc =571.4 ohm, Xm=330 ohm, Re=0.21ohm,
Xe=0.31 ohm)
Voltage Regulation
Most loads connected to the secondary of a transformer
are designed to operate at essentially constant voltage.
However, as the current is drawn through the
transformer, the load terminal voltage changes because
of voltage drop in the internal impedance.
To reduce the magnitude of the voltage change, the
transformer should be designed for a low value of the
internal impedance Zeq
The voltage regulation is defined as the change in
magnitude of the secondary voltage as the load current
changes from the no-load to the loaded condition.
Voltage Regulation
The voltage regulation is expressed as follows:
V2NL= secondary voltage (no-load condition)
V2L = secondary voltage (full-load condition)
Voltage Regulation
For the equivalent circuit referred to the primary:
V1 = no-load voltage
V2’ = secondary voltage referred to the primary (full-load condition)
Voltage Regulation
Consider the equivalent circuit referred to the
secondary,
(-) : leading power factor
(+) : lagging power factor
Voltage Regulation
Consider the equivalent circuit referred to the
primary,
(-) : leading power factor
(+) : lagging power factor
Voltage Regulation
Example 5
Based on Example 3 calculate the voltage
regulation and the secondary terminal voltage for
full load having a power factor of
0.8 lagging
(0.0336pu,425V)
0.8 leading
(-0.0154pu,447V)
Approximate Equivalent Circuit
Example 3
A 100kVA transformer has 400 turns on the primary and 80
turns on the secondary. The primary and secondary
resistance are 0.3 ohm and 0.01 ohm respectively and the
corresponding leakage reactances are 1.1 ohm and 0.035
ohm respectively. The supply voltage is 2200V. Calculate:
the equivalent impedance referred to the primary circuit
(2.05 ohm)
the equivalent impedance referred to the secondary
circuit
(0.082)
Voltage Regulation
Efficiency
Losses in a transformer
Copper losses in primary and secondary
windings
Core losses due to hysteresis and eddy
current. It depends on maximum value of flux
density, supply frequency and core
dimension. It is assumed to be constant for all
loads
Efficiency
Equipment is desired to operate at a high efficiency.
Efficiency is defined as
Since it is a static device, losses in transformers are
small
The losses in the transformer are the core loss (Pc) and
copper loss (Pcu)
Efficiency
The copper loss can be determined if the winding currents and
their resistances are known:
The copper loss is a function of the load current.
The core loss depends on the peak flux density in the core,
which in turn depends on the voltage applied to the
transformer
Since a transformer remains connected to an essentially constant
voltage, the core loss is almost constant
Efficiency
If the parameters of the equivalent circuit of a
transformer are known, the efficiency of the
transformer under any operating condition may be
determined
.
Normally, load voltage remains fixed
Therefore efficiency depends on load current and load
power factor
Efficiency
Efficiency on full load
where S is the apparent power (in volt amperes)
Efficiency for any load equal to n x full load
where corresponding total loss =
Efficiency
Example 6
The following results were obtained on a 50 kVA
transformer:
open circuit test – primary voltage, 3300 V; secondary
voltage, 400 V; primary power, 430W.
Short circuit test – primary voltage, 124V;primary current,
15.3 A; primary power, 525W; secondary current, full load
value.
Calculate the efficiency at full load and half load for
0.7 power factor.
(97.3%, 96.9%)
Efficiency
Exercise 2
The primary and secondary windings of a 500kVA
transformer have resistance of 0.42 ohm and 0.0019
ohm respectively. The primary and secondary
voltages are 11000V and 400V respectively and the
core loss is 2.9kW, assuming the power factor of the
load to be 0.8. Calculate the efficiency on
Full load
half load
(98.3%, 98.1%)
Efficiency
For constant values of the terminal voltage V2
and load power factor angle θ2 , the maximum
efficiency occurs when
If this condition is applied, the condition for
maximum efficiency is
that is, core loss = copper loss.
Efficiency
Exercise 3
Assuming the power factor of the load to be 0.8,
find the output power at which the efficiency of the
transformer of Exercise 2 is a maximum and
calculate its value
(346.4kW, 98.4%)